CS Ceiling level Beams CalcCS Structure™ 2018.9 [Build 16]
kmBeamEngine 2018.9.0.1
Materials Database 1572
DadmunTomZoll - Level 10 6- 4-19
4:47pm
1 of 2
All product names are trademarks of their respective owners
Copyright (C) 2018 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.
**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and
Spans listed on this sheet. The design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product
installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB1 Member Type: Beam Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total 1.250" max. LL
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 18.1 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 16' 3.00" 1 102 Live
Replacement Uniform (PLF) Top 0' 0.00" 16' 3.00" 315 0 Snow
Point (LBS) Top 0' 4.63" 35 10 Snow
1 2 3
10 8 0 5 7 0
16 3 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall LVL/PSL(DF/SP) End-Grain (1000psi) N/A 1.500" 1860# --
2 10' 8.000" Wall LVL/PSL(DF/SP) End-Grain (1000psi) N/A 1.500" 4627# --
3 16' 3.000" Wall LVL/PSL(DF/SP) End-Grain (1000psi) N/A 1.500" 378# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 4# 1350# 510#
2 10# 3353# 1274#
3 1# 274# 104#
Design spans
10' 3.375" 5' 4.875"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 3 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 3790.'# 38167.'# 9% 4.5' Total Load D+S
Negative Moment 4312.'# 38167.'# 11% 10.67' Total Load D+S
Shear 2224.# 13622.# 16% 10.15' Total Load D+S
TL Deflection 0.0415" 0.5141" L/999+ 5.01' Total Load D+S
LL Deflection 0.0301" 0.3427" L/999+ 5.01' Total Load S
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Design assumes a repetitive member use increase in bending stress: 4 %
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2018.9 [Build 16]
kmBeamEngine 2018.9.0.1
Materials Database 1572
DadmunTomZoll - Level 10 6- 4-19
4:47pm
2 of 2
All product names are trademarks of their respective owners
Copyright (C) 2018 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.
**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and
Spans listed on this sheet. The design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product
installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB2 Member Type: Beam Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total 1.250" max. LL
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 11.0 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 16' 0.00" -35 -10 Snow
Replacement Uniform (PLF) Top 0' 0.00" 12' 0.00" 0 35 Live
Replacement Uniform (PLF) Top 0' 0.00" 12' 0.00" 109 0 Snow
Replacement Uniform (PLF) Top 12' 0.00" 13' 0.00" 0 32 Live
Replacement Uniform (PLF) Top 12' 0.00" 13' 0.00" 98 0 Snow
Replacement Uniform (PLF) Top 13' 0.00" 14' 0.00" 0 27 Live
Replacement Uniform (PLF) Top 13' 0.00" 14' 0.00" 83 0 Snow
Replacement Uniform (PLF) Top 14' 0.00" 15' 0.00" 0 23 Live
Replacement Uniform (PLF) Top 14' 0.00" 15' 0.00" 71 0 Snow
Replacement Uniform (PLF) Top 15' 0.00" 16' 0.00" 70 22 Snow
Point (LBS) Top 15' 7.38" 0 72 Live
Point (LBS) Top 15' 7.38" 112 0 Snow
1 2
16 0 0
16 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall LVL/PSL(DF/SP) End-Grain (1000psi) N/A 1.500" 1174# -256#
2 16' 0.000" Wall LVL/PSL(DF/SP) End-Grain (1000psi) N/A 1.500" 1251# -72#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 2# 824# 350#
2 2# 855# 396#
Design spans
15' 2.750"
Product: 1-3/4x7-1/4 VERSA-LAM 2.0 3100 SP 3 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 257lbs at bearing 1 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 4424.'# 15028.'# 29% 8' Total Load D+S
Negative Moment 980.'# 15028.'# 6% 8' Total Load D+S
Shear 1080.# 8317.# 12% 0.4' Total Load D+S
TL Deflection 0.5519" 0.7615" L/331 8' Total Load D+S
LL Deflection 0.3868" 0.5076" L/472 8' Total Load S
Control: LL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Design assumes a repetitive member use increase in bending stress: 4 %
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives