signed - Deaconess_3-19_Narrative03/19/2024
Page 1 of 4
533 CENTER STREET
P.O. BOX 582
LUDLOW, MA 01056
Tel. (413) 589-0672
March 19, 2024
Northampton Fire Department
26 Carlon Drive
Northampton, Ma 01060
Subject: Deaconess Rockridge
This letter will serve as confirmation that we have taken into consideration 780 CMR: Massachusetts
Amendments to the International Building Code (IBC) 2015, Chapter 9 “Fire Protection Systems” with regard to
the design of the automatic fire protection system and compliance with applicable codes at the above
referenced location.
Re: 780 CMR 901.2.1 Tier One, Construction Documents
(i) Basis (Methodology) of Design
Section 1 – Building Description
a. Building “Use” Group – B (Business) Bank
b. Total Square Footage: Area of Scope –1,354 sq.ft.
c. Square Footage per floor – First Floor in scope: 1,354 sq.ft.
d. Location: Main Building
e. Number of floors above grade – 1
f. Number of floors below grade – N/A
g. Type of occupancies within the building – R
h. Type(s) of construction – 2 Non-combustible
i. Liquids and Hazardous material usage and storage – N/A
j. Type of hazards:
I. Light Hazard – All areas in scope
k. Type of systems: Wet
Section 2 – Applicable Laws, Regulations and Standards:
Update pendent coverage to conform with modified ceiling layout..
The new sprinkler protection will be installed and operational in accordance with all applicable State, Local
and National Codes, as follows:
a. International Building Code (IBC) 2015
b. International Existing Building Code (IEBC) 2015
c. International Fire Code (IFC) 2015
d. International Residential Code (IRC) 2015
e. 780 CMR, Massachusetts Amendments to the International Building Code (IBC) 2015
f. 527 CMR 1.00 Massachusetts Comprehensive Fire Safety Code
03/19/2024
Page 2 of 4
g. M.G.L. Chapter 146, Section 81 through 89 and CMR 528, Section 11 and 12, (Sprinkler Contractor
and Fitters Licensing Laws and Regulations)
h. M.G.L. Chapter 148, Section 10 (Regulations relative to fire prevention)
i. M.G.L. Chapter 148, Section 28 (Regulations to prevent fire hazards and fires)
j. NFPA-13, 2013 Edition, “Standard for the Installation of Sprinkler Systems”
k. NFPA-25, 2020 Edition, “Standard for the Inspection Testing and Maintenance of Water Based Fire
Protection Systems”
l. NFPA-70, 2023 Edition (NEC)
m. NFPA-72, 2013 Edition, “National Fire Alarm Code”
Section 3 – Design Responsibility for Fire Protection Systems
a) The professional engineer (PE) fully designs (complete layout and calculations)
and specifies the fire protection system or systems to be installed, reviews and
approves the installing contractor’s shop drawings. The PE is considered the
engineer of record and certifies system installation for code compliance at
completion.
Section 4 – Features used in design methodology
a. Building occupant notification and evacuation procedures - Approved Audio/visual alarm devices
connected to the sprinkler system, activated by water flow located on the interior of the building and
throughout the building in accordance with the requirements of 780 CMR 907. (By Others)
b. Emergency response personnel, site and system features – Fire protection water is from an existing
incoming city feed located at the riser. A municipal hydrant is located on Coles Meadow Rd. Sizing will
be determined after hydraulic calculations have been performed.
c. Safeguards, fire prevention and emergency procedures during construction – n/a
d. Method for future testing and maintenance of systems and documentation – Per the requirements of
NFPA-25.
Section 5 – Special Consideration and Description
(ii) Sequence of Operation
Section 1
a. Fire protection water will be supplied from the incoming service on the first floor
“Wet System” - Thermally sensitive automatic sprinklers connected to a fixed fire protection piping
system filled with pressurized water from the incoming service used in detecting a fire. When a fire
occurs, the heat produced will fuse and operate sprinklers over the affected area distributing water to
control or extinguish the fire. As water flows through the system, a paddle type water flow alarm device
is activated which in turn initiates the Fire Protective Signaling system.
b. The operating sequence for the fire alarm system is as follows: (By Others)
c. All control, drain and test connections shall be provided with signage indicating their purpose.
(iii) Testing Criteria
Section 1
a. The Fire Sprinkler installing Contractor will be in charge of setting up and coordinating all testing.
b. The Fire Sprinkler installing Contractor will utilize telephone and e-mail to coordinate all contractors,
equipment distributors and code officials required to perform and witness all testing, testing dates and
times, fortification to public utilities personnel required to perform all required testing as a system or
individual system component testing.
c. All piping shall be hydrostatically tested per the requirements of NFPA-13 utilizing a hydrostatic test
pump as required.
d. All control valves shall be fully closed and opened under system water pressure to ensure proper
operation.
03/19/2024
Page 3 of 4
e. Supervisory tamper switches shall be tested for proper operation by closing the control valve and
verifying signal at fire alarm control panel.
f. A main drain test shall be performed per the requirements of NFPA-13 by observing and recording the
supply pressure gauge reading and then opening the main drain fully and again observing and
recording the supply pressure gauge reading.
g. The water flow detection device and associated alarm circuits shall be flow tested by opening the
inspectors test connection, and shall result in an audible alarm on the premises and activation of the
Fire Protective Signaling System within 60 seconds.
Section 2- Equipment and Tools
a. Fire Sprinkler Installing Contractors will utilize the following to verify system performance:
1. Manufacturer’s instructions and recommendations
2. Specifier’s special instructions
3. Approved narrative report, sequence of operation section
4. Approved fire sprinkler drawings
5. Communications radios
6. Notification announcements
Section 3 – Approval Requirements
a. A written approval by the Fire Department stating that the system satisfies all operational code
compliance requirements may be required.
b. When a portion of the system fails to operate satisfactorily, that portion shall be corrected and pre-
tested prior to rescheduling the final acceptance test.
c. Properly executed Material, Test, Performance and Completion Certificates will be provided to the Fire
Chief or his designee by the Fire Alarm and Sprinkler Contractor at the completion of final acceptance.
d. Confirmation by the Building Owner shall be provided to the Fire Department that as-built drawings
sealed as reviewed by the Engineer of Record have been received prior to witness of acceptance
testing.
e. At the completion of installation, the Engineer of Record (PE) shall provide a final written affidavit that
the specific fire protection system(s) for which he has design responsibility has been reviewed for
proper functional operation and applicable code installation conformance.
(1b) Building and site access for fire-fighting and/or rescue vehicle(s) and personnel – Front of Building
(1c) Fire hydrant(s) location and water supply information – Fire protection water is supplied from the public
incoming service.
(1d) Type/description and design layout of the automatic sprinkler system – The sprinkler protection will be fed
from an existing wet system sprinkler main.
(1e) Automatic sprinkler system and control equipment location – Automatic sprinkler controls are existing and
located at the front of the building
(1f) Type/description of automatic standpipe system – N/A
(1g) Standpipe system hose valve(s) type and location – N/A
(1h) Fire department connection type(s) and location – Existing fire department connection at the front of the
building
(1i) Type/description and design layout of the fire protective signaling system – By Others
(1j) Fire protective signaling system(s) control equipment and remote annunciator location – By Others
(1k) Type/description and design layout of the smoke control or exhaust system(s) – N/A
03/19/2024
Page 4 of 4
(1l) Smoke control or exhaust system(s) control equipment location – N/A
(1m) Building life safety system features (auxiliary functions) required to be integrated as part of the fire
protective signaling system – N/A
(1n) Type/description and design layout of the fire extinguishing systems – N/A
(1o) Fire extinguishing system(s) control equipment room location – N/A
(1p) Fire protection system(s) equipment room location – N/A
(1q) Fire protection system(s) equipment identification and operation signs – The sprinkler system shall
incorporate all signage as required by NFPA-13 and 780 CMR.
(1r) Fire protection system(s) alarm / supervisory signal transmission method and location – By others
(1s) Fire command center location – By others
(1t) Type/description and location of any emergency alarm system – N/A
(1u) Type/description and location of any alternative fire suppression system - N/A
(1v) Type/description of any carbon monoxide protection – By others
Sincerely,
Impact Fire
Joe Brosseau, General Manager
Scott Henderson P.E.