32A-122 (22) L• 3d/9 /d Northampton Fire ' Department x Memorandum E 11 To: Tony Patillo ; MAY 3 0 2003 ! L. From: Duane Nichols _. .. J DEPT OF 61J LQ'M'G Ir,S2FC Date: May 29, 2003 NORTHAITION,P" CC: Brian Duggan Re: 67 King St. Northampton Cooperative Bank Secondary to a review of the plans and fire protection narrative submitted to me for review, I concur with the issuance of a building permit subject to the following conditions: • Duct detectors shall be clearly labeled, with test switches located by Fire Department when appropriate time for installation. • A graphic representation of the structure needs to be installed at the Fire Alarm Control Panel and/or Fire Alarm Annunciator Panel. The structural members should be outlined in black and each fire alarm device should be outlined in red. Points of egress should be indicated with blue shading, if the building is multi-storied floors should be shown one above another. The building name and address should be posted at the top of map. • Pull stations referenced in the fire protection narrative are to be of the double action type. • Page 1 r ► • A Fire Alarm Annunciator panel or Fire Alarm Control panel needs to be located at the front entrance. All panels need to be clearly marked with red engraved signage with one-inch white lettering clearly identifying panel. • 5 lb ABC Fire extinguishers are needed, which should be located under pull stations at each exit, in compliance with NFPA relative to maximum travel distance. Appropriate signage in compliance with ADA should be located above. • Alarm verification must be active on all smoke detection zones. • Installation of referenced items in fire protection narrative shall be in compliance with the Northampton Fire Department Fire Prevention Features for New Construction/Renovations. • The Central Station monitoring service must be UL listed, FM approved service. • Page 2