Bombyx Fire NarrativeSubmittlesSecurity & Fire Integrations LLC Southampton, MA 01073 413-203-2008 Fire Alarm Narrative: 9-1-2023 Location: Bombyx Florence Cong Church 130 Pine Street Florence MA 01062 Owner: John Losito 413-330-2179 Johniosito@gmall.com Building Use Group: Commercial Installing Company: Security & Fire Integrations LLC 317 main Street Southampton, MA 01073 Scope of Work: SFI LLC shall install new fire system in the Existing Hall, daycare, office areas and throughout the building. SFI LLC shall install a Voice Evac system as part of the fire system. The Voice Amp/Mic Fire call box shall be in the middle front entrance with the Fire system LCD annunciator and Knox box and outdoor red beacon. The system shall have Smoke, Heat, Pull stations for activation devices. The Notification devices shall be Speaker Strobes, Horn strobes, strobes. All devices are marked on the attached prints. Fire Alarm Monitoring: The Fire System monitoring is thru The UL Cops Monitoring Central station. The system shall be monitored for Alarms, Supervisory, and Troubles. The Central station shall call the Fire Dept and the appropriate persons on the call list provided by the owner. The Firelite system has a built in UL Fie cell module for transmitting signals form the system to the UL Central station. Operation: Upon activation of any smoke, pull station, Co detector the fire system shall go into full alarm with Horns strobes, and the recorder message thru the voice evac system, the Main control shall display the zone that is activated and report that alarm by zone to the Cops Monitoring central station. The central station shall call the Fire dept and the notify list. To Reset: Upon activation of a device and to silence and or reset. The Silence button to silence the trouble or alarm then push the system reset button to reset that device that had tripped. Note: there are no sprinkler or Ansul systems to monitoring or tied into system. Zones: Addressable the point list will be provided upon completion of the system with the NFPA 72 report 1 Firelite ES-20OX addressable control 1 Firelite LCD annunciator 1 Outdoor red strobe and outdoor Knox Box existing 6 Napco UL Cell dialer with network 1 Document cabinet 6 Addressable pull stations 31 Addressable smokes 31 Addressable Heats (135 and High heat) 1 Firelite Voice Evac 50/100 E control / amp 5 Existing horn strobes P2R 4 Wall strobes SR 34 Wall Speaker Strobes 14 Ceiling Speaker Strobes 2 Ceiling Strobes SCR m (n n z L7 o r O IT m 3P AL ° a ob Ir 3 e �1 '.ap W� N• p o JA • Y 7y Z/L- 7y s T,m o.• Y 6 4 � 2 u• ^ v a wb o 4R 8.- 4 ° R ^ ¢ 3 N u m G� • — • w n a � d is �s® D O�m > v P , o ' p m �® mom m a �\ 0AF7 c I "s 4> j W J N i i F i m C mci Z Z Z Z m mmm i --I --I—i y s m mmm T TTT O O 9 D i BOMBYX ina z * Florence Congregational 5 y Church L =o Q F c 130 PINE STREET ro a'i n m REV DATE DESCRIPTION FLORENCE, MA 0 1112120228'4131 PM m ?„ x N rn rn � n Z• E p rg O T Jsl-Z/ -1 NM3A m r EWh _< p soma v25-1aa p 7J W NNay snmaown • $ k ' 6 U � � 44 & u 41 u W d N ME I TI L _ 4 tn >>— 3 3 EW v < b pg s 4 3 .gn > A• iw� 3 w � < Wa 'ry o 2 w f N W O N ss n zz p 7 �9 �0 1s+2w-30c 1 s-}Zw30c 7� m ®_ q � ® w V ss 1-)-1/2-30c ym OE-MZ-4sl JOf-M 5-s-sl € as § 1N^ F C m' 3 v' 3 D TT rn O s n O L BOMBYX m Az a Z Florence Congregational Church �l ZA O y o ^' REV 130 PINE STREET fIORENCE, MA GATE DESCRIPTION 1/1P/20224:45:09 PM X rn � = y II Z ON _ • ^® - n O " Z O T r da < d Y n ti•�4� S•m >�w a >ry P s T® N V » �• N a' 4 'o MID A • # G® i D os s ooa m E BOMBYX Q inM z S m i a ' s Florence Congregational Church O Z O Z0 N' y '.REV 130 PINE STREET FLORENCE, MA O ^® (� o tri DATE DESCRIPTION n 1/12/20224.45:53 PM DF-60957:D ES-20OX Series Intelligent Addressable Fire Alarm Control Panels The ES-200X, ES-200XC, ES-200XI, and ES-200XP are the latest intelligent addressable Fire Alarm Control Panel (FACP) from Fire-Lite Alarms and is a direct replacement for the MS-92000DLS. The ES- 200X support up to 198 addressable devices (99 detectors and 99 modules). With an extensive list of powerful features, the ES-20OX Series programs just like Fire-Lite's other addressable products, yet fits into applications previously served only by conventional panels. The ES-20OX and ES-20OXC feature a pre -installed ]POTS-COM, a dual technology (POTS and IP) communicator. The POTS transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. The IP communicator's Inter- net monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines. Although not required, the secondary telephone line may be retained providing backup communication over the public switched telephone line. Optional cellular reporting is available using an HW-TG7F Series Communicators or the CLSS Pathway. The ES-200XP features an integrated CLSS Pathway Pro Communi- cator, a dual-SIM (AT&T/ Verizon) 5G LTE-M Communicator with optional IP connection. The CLSS Pathway Pro transmits system sta- tus (alarms, troubles, AC loss, etc.) to the Central Station using LTE CAT-M1 networks, serving as a bridge between the fire system and the CLSS Cloud. The IP communicator's Internet monitoring capability sends alarm signals over the Internet, meeting requirements for backup communication. As an integrated communicator, the CLSS Pathway Pro, typically, can transmit data faster than dial capture meth- ods. Remote and local programming of the control panel is possible using the FS-Tools Upload/Download utility. Programming databases can be uploaded/downloaded via the panel's USB port (and USB cable) or via an ethernet connection using the IPOTS-COM communicator (ES-200X and EX-20OXC only). The USB port also allows for the download or upload of the entire program, history file, walk -test data, current status and system voltages by means of a USB flash drive. The power supply and all electronics are contained on a circuit board supported on a new quick install chassis and housed in a metal cabi- net. Available accessories include local and remote upload/download software, remote annunciators, and reverse polarity/city box transmit- ter (4XTMF). Features • Listed to UL Standard 864, 10th edition • Pre -installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- phone Service) Central Station Communicator (ES-200X and EX-20OXC only) • Optional Cellular Central Station Communicators over AlarmNet® (ES-200X and EX-20OXC only) • Integrated CLSS Pathway Pro Communicator; dual SIM AT&TNeri- zon networks with LTE-CAT-M1 5G technology (EX-200XPonly) • Cloud monitoring using Honeywell's Connected Life Safety Ser- vices (CLSS) Cloud solutions software (EX-200XP only) • Automated activation of the ECC-50/100 Emergency Command Center • ECC-FFT Firefighter Telephone option • Compatible with SWIFT® wireless devices • Auto -programming (learn mode) reduces installation time. Reports two devices set to the same address • Four built-in, independently programmable, Class A or Class B NAC circuits (B Fire-LITe ALarms by Honeywel Addressable Fire Alarm Control Panels • Selectable strobe synchronization for System Sensor, Wheelock, and Gentex devices • Notification Appliance Circuit End of Line resistor matching • Four programmable function keys for ease of maintenance • Two programmable relays and one fixed trouble relay • Built-in Programmer • Integral 80-character LCD display with backlighting • Real-time clock/calendar with automatic daylight savings control • History file with 1,000 event capacity • Addressable sounder base compatibility • Mufti -criteria detector (smoke, heat, CO) with programmable response • Control module delay timer • Automatic detector sensitivity testing (NFPA 72 compliant) • Automatic device type -code verification • Point trouble identification • Waterflow selection per module point • Alarm verification selection per detector point • Maintenance alert warns when smoke detector dust accumulation is excessive • One -person audible or silent walktest with walktest leg and printout • System alarm verification selection per detector point • PAS (Positive Alarm Sequence) and Pre -signal per point (NFPA 72 compliant) • Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus • Remote Acknowledge, Alarm Silence, Reset and Drill via address- able modules or remote annunciator • Upload/Download of program and data via USB with optional FS-Tools Programming Utility SLC (DCL) COMMUNICATION LOOP • Supports LiteSpeedT" and CLIP protocols • SLC (DCL) operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire • Single addressable SLG (DCL) loop which meets NFPA Class B and Class A requirements • 198 addressable device capacity (99 addressable detectors and 99 modules) DF-609570 • 3/27/2023 — Page 1 of 4 • Compatible with Fire-Lite's addressable devices (refer to the SLC Wiring Manual) NOTIFICATION APPLIANCE CIRCUITS (NACS) • Four independently programmable output circuits. Circuits can be configured for Class A or Class B wiring • Silence Inhibit and Autosilence timer options • Continuous, March Time, Temporal, or California code for main cir- cuit board NACS with two -stage capability • Selectable strobe synchronization per NAC • 2.5 A special application, 250mA regulated, total power for NACS NOTE: Maximum or total 24VDC system power shared between all NAC circuits and the ANN-BUS is 2.7 A PROGRAMMING AND SOFTWARE • Autoprogramming (learn mode) reduces installation time • Custom English labels (per point) may be manually entered or selected from an internal library file • Two programmable Form-C relay outputs • 99 software zones • Continuous fire protection during online programming • Program Check automatically catches common errors not linked to any zone or input point • OFFLINE PROGRAMMING: Create the entire program in your office using FS-Tools, a Windows® -based software package, and upload/download system programming locally. Off line programming requires an ethernet connection. FS-Tools is available on www.firelite.com. User interface LED INDICATORS • Fire Alarm (red) • CO Alarm (yellow) • AC Power (green) • Supervisory (yellow) • Trouble (yellow) • Ground fauit (yellow) • Battery fault (yellow) • Disabled (yellow) • Maintenance (yellow) • Communication (yellow) • Alarm Silenced (yellow) • F1-F4 Programmable Function Keys (yellow) KEYPAD • 16 key alpha -numeric pad • Acknowledge • Alarm Silence • Drill (Manual Evacuate) • Four (4) programmable function keys • Reset (lamp test) PRODUCT LINE INFORMATION ES-20OX: Addressable Fire Alarm Control Panel with one SLC loop. Includes main circuit board with display, pre -installed communicator, chassis with transformer, backbox with door, plastic bag containing screws, cables, key, etc. ES-20OXC: Addressable Fire Alarm Control Panel with one DCL loop. Includes main circuit board with display, pre -installed IPOTS-COM communicator, chassis with transformer, dress panel, backbox with door, plastic bag containing screws, cables, key, etc. ES-20OXI: Addressable Fire Alarm Control Panel with one SLC loop. Includes main circuit board with display, chassis with transformer, dress panel, backbox with door, plastic bag containing screws, cables, key, etc. ES-200XP: Addressable Fire Alarm Control Panel with one SLC loop. Includes main circuit board with display, pre -installed CLSS Pathway Pro communicator, chassis with transformer, dress panel, backbox with door, plastic bag containing screws, cables, key, etc. FS-Tools: Programming software for Windows® -based PC computer. Available for download at www.firelite.com. IPOTS-COM: Dual technology (POTS and IP) communicator. (replacement board) (ES-200X and EX-20OXC only) HW-AV-LTE-M: Optional CLSS Pathway HW-TG7FS-A/HW-TG7FS-V: CLSS-Enabled 5G /LTE-M Commercial Fire Alarm Communicators for AT&T® and Verzon® HW-TG7FE-A/HW-TG7FE-V: CLSS-Enabled 5G/LTE-M Dual Path Commercial Fire Alarm Communicators for AT&T and Verizon HW-TG7FP-A/HW-TG7FP-A: CLSS-Enabled 5G/LTE-M Sole Path Commercial Fire Alarm Communicators for AT&T and Verizon DP-ES-R: Optional dress panel for the. TR-CE: Optional trim ring for semi -flush mounting. BB-2F: Optional cabinet for one or two modules. BB-6F: Optional cabinet for up to six modules mounted on CHS-6 chassis. BB-26: Battery backbox, holds up to two 25 AH batteries and CHG- 75. BB-55F: Battery box, houses two 55 AH batteries CHS-6: Chassis, mounts up to six multi -modules in a BB-6F cabinet. CHG-75: Battery charger for lead -acid batteries with a rating of 25 to 75 AH. CHG-120F: Remote battery charging system for lead -acid batteries with a rating of 55 to 120 AH. Requires additional BB-55F for mount- ing. NOTE: CHG-12OF or CHG-75 required ror batteries larger than 18AH. BAT Series: Batteries, see data sheet DF-52397. PRN Series: UL listed compatible event printer. Uses tractor -fed paper. OPTIONAL MODULES 4XTMF Reverse Polarity Transmitter Module: Provides a super- vised output for local energy municipal box transmitter, alarm and trou- ble. Includes a disable switch and disable trouble LED. PWRMOD24 Power Expander Module: Optional power module. Increases alarm power output to 6 amps. COMPATIBLE ANNUNCIATORS ANN-80: Remote LCD annunciator mimics the information displayed on the FACP LCD display. Recommended wire type is un-shielded. ANN-100: Remote LCD annunciator mimics the information displayed on the FACP LCD display. Recommended wire type is un-shielded. For use in FM applications only. ANN-VO: LED Driver Module provides connections to a user supplied graphic annunciator. (See DF-52430.) ANN-LED: Annunciator Module provides three LEDs for each zone: Alarm, Trouble, and Supervisory. Ships with red enclosure. (See DF- 60241.) ANN-BLED: Provides alarm (red) indicators for up to 30 input zones or addressable points. (See DF-60241.) ANN-RLY: Relay Module provides 10 programmable Form-C relays. Can be mounted inside the cabinet. (See DF-52431.) ANN-S/PG: Serial/Parallel Printer Gateway module provides a con- nection for a serial or parallel printer. (See DF-52429.) ADDRESSABLE DEVICES All feature a polling LED and rotary switches for addressing. SD365(A): Addressable low -profile photoelectric smoke detector. Lite- Speed only. SD365(A)-IV: Addressable low -profile photoelectric smoke detector. Ivory. LiteSpeed and CLIP mode. SD365T(A): Addressable low -profile photoelectric smoke detector with thermal sensor. LiteSpeed only. SD365T(A)-IV: Addressable low -profile photoelectric smoke detector with thermal sensor. Ivory. LiteSpeed and CLIP mode. SD365R(A): Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. LiteSpeed only. SD365R(A)-IV: Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. Ivory. LiteSpeed and CLIP mode. SD355CO: Addressable, low -profile device that provides fire, heat, and carbon monoxide (CO) detection, LiteSpeed only. SD365CO-IV: Addressable, low -profile device that provides fire, heat, and carbon monoxide (CO) detection. Ivory. LiteSpeed and CLIP mode. Page 2 of 4 — DF-609570 • 3/27/2023 H365(A): Low -profile 135"F fixed thermal sensor. LiteSpeed only. H365(A)-IV: Low -profile 135"F fixed thermal sensor. Ivory. LiteSpeed and CLIP mode. H365R(A): Low -profile, intelligent, rate -of -rise thermal sensor. Lite- Speed only. H365R(A)-IV: Low -profile, intelligent, rate -of -rise thermal sensor. Ivory. LiteSpeed and CLIP mode. H365HT(A): Low -profile intelligent 190"F/8800 fixed thermal sensor. LiteSpeed only. H365HT(A)-IV: Low -profile intelligent 190"F/88°C fixed thermal sen- sor. Ivory. LiteSpeed and CLIP mode. D365PL: Low -flow non -relay duct -detector housing; includes SD365R. Legacy Devices CP355(A): Addressable low -profile ionization smoke detector. SD355(A): Addressable low -profile photoelectric smoke detector. SD355T(A): Addressable low -profile photoelectric smoke detector with thermal sensor. SD355R(A): Remote test capable addressable photoelectric smoke detector for use with DNR(W) duct detector housing. SD355CO: Addressable, low -profile device that provides fire, heat, and carbon monoxide (CO) detection. H355(A): Fast -response, low -profile heat detector. H355R(A): Fast -response, low -profile heat detector with rate -of -rise option. H355HT(A): Fast -response, low -profile heat detector that activates at 190°F/88"C. AD355(A): Low -profile, intelligent, "Adapt" mufti -sensor detector (B350LP base included). B2005(A)(-WH)(-IV): Programmable, addressable sounder base. B200SR(A)(-WH)(-IV): Addressable sounder base. B20DS-LF(-WH)(-IV): Programmable, addressable sounder base, low - frequency. B200SR-LF(-WH)(-IV): Addressable sounder base, low -frequency. BEAM355: Intelligent beam smoke detector. BEAM355S: Intelligent beam smoke detector with integral sensitivity test. D355PL(A): InnovairFlex low -flow non -relay duct -detector housing; includes SD355R. DNR(A): InnovairFlex low -flow non -relay duct -detector housing. (Order SD355R(A)/SD365R(A) separately.) DNRW: InnovairFlex low -flow non -relay duct -detector housing, with NEMA-4 rating. Watertight. (Order SD355R(A)/SD3658(A) sepa- rately.) Addressable Modules MMF-300(A): Addressable Monitor Module for one zone of normally - open dry -contact initiating devices. Mounts in standard 4.0" (10.16 cm.) box. Includes plastic cover plate and end -of -line resistor. Module may be configured for either a Class B or Class A IDC. MDF-300(A): Dual Monitor Module. Same as MMF-300(A) except it provides two Class B-only IDCs. MMF-301(A): Miniature version of MMF-300(A). Excludes LED and Class A option. Connects with wire pigtails. May mount in device back - box. MMF-302(A): Similar to MMF-300(A). Addressable Monitor Module for one zone of conventional two -wire detectors. Requires resettable 24 VDC power. Refer to the Device Compatibility Document for listed compatible devices and quantity limitation. CMF-300(A): Addressable Control Module for one Class B or Class A zone of supervised polarized Notification Appliances. Mounts directly to a 4.0' (10.16 cm.) electrical box. NAC option requires external 24 VDC to power notification appliances. CRF-300(A): Addressable relay module containing two isolated sets of Form-C contacts, which operate as a DPDT switch. Mounts directly to a 4.0" (10.16 cm.) box, surface mount using the SMB500. BG-12LX: Addressable manual pull station with interface module mounted inside. 1300(A): This module isolates the SLC loop from short circuit condi- tions (required for Class A or Class X operation). ISO-6(A): Six -fault isolator module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chas- sis in a BB-6F cabinet. SMB500: Used to mount all modules except the MMF-301(A) and M301(A). MMF-300-10(A): Ten -input monitor module. Mount one or two mod- ules in a BB-2F cabinet (optional). Mount up to six modules on a CHS- 6 chassis in a BB-61F cabinet. MMF-302-6(A): Six -zone interface module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CMF-300-6(A): Six -circuit supervised control module. Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. CRF-300-6(A): Six -relay control module (Form-C relays). Mount one or two modules in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 chassis in a BB-6F cabinet. SWIFT Wireless Devices W-GATE(A): LiteSpeed Wireless Gateway W-SD355(A): LiteSpeed intelligent, wireless photo detector. W-H355R(A): LiteSpeed intelligent wireless rate of rise (135") heat detector. W-SD355T(A): intelligent wireless photolheat detector. W-H355(A): LiteSpeed intelligent wireless fixed -temperature (1350) heat detector. W-MMF(A): LiteSpeed Intelligent wireless monitor module. W-CRF(A): LiteSpeed Intelligent wireless relay module. W-BG12LX(A): LiteSpeed Intelligent wireless pull station. WAV-RL, WAV-WL,WAV-CRL,WAV-CWL: LiteSpeed Intelligent AV bases. W-USB: Wireless USB radio/antenna dongle that plugs into the USB port of a PC running SWIFT Tools. SWIFT Tools: Programming and diagnostic utility for the Wireless Gateway and devices. Available for download from firelite.com. NOTE: For more information on Compatible Addressable Devices for use with the ES-200X, see the following data sheets (document numbers): SD365 Series (DF-61010), H365 Series (DF-61011), AD355 (DF-52386), BG-12LX (DF-52013), CMF-300-6 (DF-52365), CRF,300-6 (DF-52374), CMF/CRF Series (DF-52130), CP355 (DF52383), H355 Series (DF- 52385), 1300 (DF-52389), ISO-6 (DF-60485), MMF-300 Series/MDF-300 (DF52121), MMF-300-10 (DF-52347), MMF-302-6 (DF-52356), SD3551 SD355T (DF-52384), and SLC Wiring Manual (51309). NOTE: Legacy 300 Series detection devices such as the CP3001CP350, SD300(7)ISD350(7) and older modules such as the M300, M301, M302, C304, and BG-10LX are not compatible with LiteSpeed polling. If the SLC contains one of these devices, polling must be set for standard CLIP proto- col. Please consult factory for further information on previous 300 Series devices. ADDRESSABLE DEVICE ACCESSORIES End -of -Line Resistor Assembly (R-47K and R-3.9K): The 47k ohm assembly supervises the MMF-300(A), MDF-300(A), MMF-301(A), and CMF-300(A) module circuits. The 3.9k ohm assembly supervises the MMF-302(A) module circuit. These resistors are included with each module. Power Supervision Relay: Supervises the power to 4-wire smoke detectors and notification appliances. Wiring Requirements While shielded wire is not required, it is recommended that all SLC (DCL) wiring be twisted -pair to minimize the effects of electrical inter- ference. Refer to the panel manual for wiring details. DF-e0957:D • 3/27/2023— Page 3 of 4 SYSTEM SPECIFICATIONS System Capacity • Intelligent Signaling Line Circuits...................................................1 • Addressable device capacity.....................................................198 • Programmable software zones....................................................99 • Annunciators................................................................................ 16 Electrical Specifications AC Power: Operates in either 120 or 240 VAC, 50/60 Hz, 3.25 A, auto -sensing- no switch required. Wire size: minimum 14 AWG (2.00 mm2) with 600 V insulation. Non -power -limited, supervised. Battery: Two 12 V 18 AH lead -acid batteries. Battery Charger Capac- ity: 7-18 AH (ES-200X cabinet holds maximum of two 18 AH batter- ies.) Communication Loop: Supervised and power -limited. Notification Appliance Circuits: Terminal Block provides connec- tions for four NACs, Class B or Class A. Special Application power. Power -limited, supervised circuitry. Maximum signaling current per cir- cuit: 2.5 amps special application, 250mA regulated. End -of -Line Resistor: 4.7kohm, Ys watt (P/N 71252 UL listed) for Class B NAC; system capable of 1.9 kQ - 22 kO ELR range. Refer to the Fire-Lite Device Compatibility Document for listed compatible devices. Two Programmable Relays and One Fixed Trouble Relay: Con- tact rating: 2.0 A @ 30 VDC (resistive), 0.5 A ® 30 VAC (resistive). Form-C relays, non -power -limited, non -supervised. Cabinet Specifications Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.72" (1.82 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 cm.) wide x 5.25" (13.34 cm.) deep. Trim Ring (TR-CE): 22.00" (55.88 cm.) high x 19.65" (49.91 cm.) wide. Shipping Specifications Weight: 26.9 lbs. (12.20 kg.) Dimensions: 20.00" (50.80 cm.) high x 22.5" (57.15 cm.) wide x 8.5" (21.59 cm.) deep. Temperature and Humidity Ranges This system meets NFPA requirements for operation at 0 — 49°C/32 — 120"F and at a relative humidity 93%: 2% RH (noncondensing) at 32"C m 2°C (90°F t 3"F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 — 27•C/60 — 80"F. Nli Standards The ES-200X complies with the following NFPA 72 Fire Alarm Sys- tems requirements: — LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi- sory). —AUXILIARY (Automatic, Manual and Waterflow) (requires 4XTMF). — REMOTE STATION (Automatic, Manual and Waterflow) (Where a DACT is not accepted, the alarm, trouble and supervisory relays may be connected to UL 864 listed transmitters. For reverse polarity signaling of alarm and trouble, 4XTMF is required.) — PROPRIETARY (Automatic, Manual and Waterflow). —CENTRAL STATION (Automatic, Manual and Waterflow, and Sprinkler Supervised). — OT, PSDN (Other Technologies, Packet -switched Data Network) — IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic). — CBC 2007 (Seismic) Agency Listings and Approvals The listings and approvals below apply to the basic ES-200X control panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for lat- est listing status. ES-200X,ES-200XC, ES-200X1 • UL: 5624 • FM approved • CSFM: 7165-0075:0500 • FDNY: COA #2021-TMCOAP-009618-AMD ES-200XP • ETL:5017286 • CSFM: 7165.0075:0511 Innovairnex*"' and LkeSpeedTM are trademarks and AlarmNets, Fire-Lite® Alarms, SWIFTS, and System Sensor® are registered trademarks of Honeywell Intemational Inc. AT&TO is a registered trademark of the AT&T Properties, L.P.Verizon® is a registered trademark of Verizon Trademark Services LLC. MlcrosofM and Windows® are registered trademarks of the Microsoft Corporation. 02023 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. IS 0 9001 We try to keep our product information up-to-date and accurate. We cannot coverall specific applirabons or anticipate all requirements. All specifications are subject to change without notice. FNIINEEAINA 8 MMAFACNAINA QUALITY SYSTEMS For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: USA www.firelite.com Page 4 of 4 — DF-60957:D • 3/2712023 181RIMUTSALarrTIS by Honeywell ES-20OX Battery Calculation Secondary Power Source Requirements Device Type Qty JStLCu_rV_tD`raw TmpTotal 1 Draw I Total Main Circuit Board 1 x 0.141000 1=1 0.141000 1 1 x 0.257000 - 0.257000 IPOTS-COM Communicator 1 x 0.040000 =1 0.040000 1 1 jxj 0.041000 1-1 0.04100 PWRMOD24 0 x 0.007000 = 0 x 0.008000 = 4XTMF 0 x 0.005000 1 0 X1 0.011000 1= ECC-FFT 0 x 0,120000 = 0 x 0.230000 = CELL -MOD -FL / CELL -CAB 1 x 0.055000 = 0.055000 1 1 1XI 0,100000 1=1 0.100000 ANN-BUS Devices ANN-80(-W) 1 X1 0.015000 = 0.015000 1 x 0.040000 = 0.040000 ANN-100 0 x 0.020000 = 0 x 0.025000 = ANN-LED 0 x 0.028000 - 0 x 0.068000 - ANWRLED 0 x 0.028000 = 0 x 0.068000 = ANWRLY 0 x 0.015000 = 0 x 0.075000 = ANN-1/0 0 x 0.035000 = 0 x 0.200000 = ANN-S/PG 0 x 0.045000 = 0 x 0.045000 = Addressable Devices BEAM355 0 X1 0.002000 = - - - BEAM355S 0 x 0.002000 = SD365CO 0 x 0.002000 = SD355CO 0 x 0.000300 CP355 0 x 0.000300 = SD355 0 x 0.000300 - SD365 8 x 0.000300 = 0.002400 SD355T 0 x 0.000300 - S0365T 0 x 0,000200 = H355 0 x 0.000300 = H365 5 x 0.000200 = 0.001000 H355HT 0 x 0.000300 - H365HT 0 x 0.000200 = H350R 0 x 0.000300 = H355R 0 x 0.000300 = H365R 0 x 0.000200 = D350RPL 0 x 0.000300 = D355PL 0 x 0.000300 = MMF-300 0 x 0.000375 = MMF-300-10 0 x 0.003500 = MDF-300 0 x 0.000750 = MMF-301 3 x 0.000350 = 0.001050 MMF-302 0 x 0.000270 - MMF-302-6 0 x 0.002000 = BG-12LX 5 x 0,000375 = 0.001875 CMF-300 0 x 0.000390 = CMF-300-6 0 xj 0.002250 = CRF-300 1 x 0.000255 = 0.000255 CRF-300-6 0 x 0.001450 = CDRM-300 0 x 0.001300 = 1300 0 x 0.000400 = ISO-6 0 x 0.002700 = B501BH-2 0 x 0.001000 = B501BHT-2 0 x 0.001000 B224RB 0 x 0.000500 E224B1 0 x 0.000450 = Fire-Lite Alarms Page 1 9/12/2023 W-GATE 0 IxI 0.024000 1=1 El Maximum alarm draw for all Addressable devices 0.400000 EOLR-1 0 x 0,020000 0 x 00200--= FCPS (Remote Sync) 1 0 jxj 0,021700 1=1 Resettable Power 4-Wire Smoke Detectors 1 0 1XI 0,000000 1 0 1XI 0.000000 1 = Auxiliary Power CMF-300 (Aux. Power) 0 IxI 0.001700 1=1 1 0 IxI 0.007000 1=1 CMF-300-6 (Aux. Power) 0 x 0.008000 = 0 x 0,020000 = MMF-302 (Aux. Power) 0 x 0.012000 = 0 x 0.090000 = MMF-302-6 (Aux. Power) 0 x 0.050000 = 0 x 0.270000 = B200SR (Aux. Power) 0 x 0.000500 = 0 x 0.035000 = B200SR-LF(Aux. Power) 0 x 0.001000 = 0 x 0.125000 1=1 SWIFT Wireless W-GATE 0 x 0.040000 = 0 x 0.040000 - Miscellaneous Devices 0 x 0.000000 =j 1 0 x 0.000000 = 0 x 0,000000 = 0 x 0,000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = 0 x 0.000000 = Output Circuits NAC/Output #1 0.000000 0.557000 = 0.557000 NAC/Output#2 0,000000 = 0.000000 = NAC/Output#3 -_ 0.000000 = 0.000000 = NAC/Output#4 0,000000 = 0.000000 = FCPS (remote Sync) 0 x 0.000000 = 0 x 0.021700 = Current Draw from TB3 0,000000 0.000000 = Total Standby Load= 0.25 558 1 Total Alarm Load 1.396000 Fire-Lite Alarms Pane 2 9/12/2023 ®Flre•UTeALarmS by Honeywell ES-20OX Battery Calculation Calculation in Total Sheet 24 Hours Standby Load Current 0.25758 Amps x 24 = 6.182 AH 5 Minutes Alarm Load Current (Amps) 1.39500 Amps x 0.084 = 0.117 AH Total Current Load 6.299 AH Multiply by the Derating Factor 1 t2 = x 1.20 Total Ampere Hours Required 7.66 AH Recommended Batteries: BAT-12120 - 12AH Batteries Battery Check mc�_ The batteries can be charged by the ES-20OX Charger. The batteries can be housed in the ES-20OX Cabinet. Current Draw Check NAC#1 current is within the limitations of the circuit. NAC#2 current is within the limitations of the circuit. NAC#3 current is within the limitations of the circuit. NAC#4 current is within the limitations of the circuit. ES-20OX Control Panel: The output current is within the panel's limitations. Fire-Lite Alarms Page 3 9/12/2023 Canadian DF-60815:8 ECC-50/100C Emergency Command Center General Fire-lite's ECC-50/100C is a multipurpose emergency voice evacuation panel for fire applications, mass notification appli- cations, or both. The Primary Operating Consoles (POC's)delivers 50 or 100 watts of audio power for distribution to up to eight speaker circuits (i.e. zones). The ECC-501100C comes standard with a single speaker circuit and a built-in 25Vrms, 50 watt amplifier. A secondary 50 watt amplifier (ECC-50W-25/70V) can be added for single speaker circuit backup or to increase system capacity to two speaker circuits and an additional 50 watts of audio power. An optional ECC- CE6 module added to the ECC-50/100C will upgrade the sys- tem to a maximum of eight speaker circuit outputs. All speaker output circuits can be wired in either Class B or Class A config- uration. The ECC-501100C has fourteen field programmable messages (up to 60 seconds each), built-in field configurable pre- and post -announce tone generators and a fully super- vised Notification Appliance Circuit (NAC) with 2.0 amps of synchronized NAC power. The ECC-50/100C includes three built-in Form-C relay contacts, (AC power, trouble and MNS active) a NAC follower input for triggering the on board NAC circuit and 500mA special application power. A built-in power supply with switch mode technology delivers operational power to the panel and on board battery charger supports charging up to 26AH batteries (ECC cabinet holds up to IBAH batteries). For fire protection applications, the ECC-50/100C is an adjunct (slave) to most ULC listed FACPs or as a stand-alone unit for non -fire applications. For seamless integration between fire and mass notification, the ECC-50/100C can be activated by the MS-9600LSC(-FR) and MS-92000DLSC(-FR) when con- nected to the serial communication bus. Activation of the ECC- 50/100C via other FACP's uses the eight on board Command Input Circuits (CMD's). Two of the eight CMD circuits (CMD 1 & CMD 2) can be individually field programmed for activation by an FACP Notification Appliance Circuit reverse polarity and all eight can be activated by a contact closure. In addition, the ECC-50/100C can be activated from a building's Private Branch Exchange (PBX) with the integral night ring feature. All ECC-501100C programming is done by using a simple, built-in programming utility accessed from any laptop. For added flexibility, the ECC-50/100C supports both 25Vrms and 70.7Vrms speaker output operation. By adding a 70V trans- former conversion module (ECC-XRM-70V) or an additional 70.7 volt secondary amplifier (ECC-50W-25/70V) the system supports 70.7 volt speaker devices. To add more control and increase system capacity, any com- bination of up to eight external remote consoles (including the ECC-LOC). TYPICAL APPLICATIONS The ECC-50/100C is used in applications that require single - channel voice evacuation for buildings with an occupancy greater than 1,000 occupants. Features Modular design for system flexibility and easy expansion Removable terminal blocks for ease of servicing and mod- ule replacement (a FIPe•LITe'ALarms by Honeywell • 50 watts of 25V audio power (expandable to 100 watts) RMS • 2 amp Notification Appliance Circuit (NAC) output, sync generator, or follower for System Sensor, or Wheelock pro- tocols • Optional 70.7V RMS conversion transformer available for the primary amplifier. (Note that speaker wiring continues to be supervised in standby, alarm and when background music is playing with this optional transformer installed) • Eight Command Input Circuits to activate messages 1 to 8: — CMD1 and CMD2 are field selectable to be activated from 12 or 24 VDC Notification Appliance Circuits (reverse polarity) or contact closures — CMD3-CMD8 are activated by contact closures • Speaker Circuits — Single Class B or Class A speaker Circuit —Two Class B or Class A speaker circuits (with optional ECC-50W-25/70V Audio Amplifier installed) — Eight Class B or Class A speaker circuits (with optional ECC-50W-25/70V and ECC-CE6 installed) • ECC-50/100C can be controlled by an FACP via the ANN/ ACS (EIA-485) link. Compatible FACPs include the MS- 9600(UD)LS and MS-92000DLS • Certified for seismic applications when used with the appro- priate seismic mounting kit • Integral supervised microphone • Microphone time-out feature which reverts back to prere- corded message if emergency page exceeds the pro- grammed time • 14 recorded messages • Field -selectable message and custom message recording capability using the local microphone, a USB port, or an external audio input • External Audio Input can be used for background music DF-60815:13 • 7/28/2015 — Pagel of 6 Up to 60 second message duration for all messages Integral tone generators field selectable for multiple tone types Powered by integral AC power supply or batteries during AC fail Programmable delay of immediate, 2 hours or 6 hours reporting of AC Loss Piezo sounder for local trouble 100 event history log Three Form-C relays: — AC Power Loss Relay - TB1 — System Trouble Relay - TB2 — MINIS Active - Ti 500mA (0.5A) Special Application (auxiliary power) output for addressable modules when interfaced with compatible addressable FACPs and End -of -Line power supervision relays System Status LEDs (refer to "Controls and Indicators" on product manual LS1 0001 -OOOFL-E) Integral Dress Panel Optional TR-CE semi -flush trim ring Any combination of up to eight (8) external remote con- soles: — Optional ECC-LOC Local operator console (includes cab- inet). See DF-60814. Optional Internal Expansion Modules ECC-CE6: Circuit Expander Module provides connections for up to six Class A or Class B speaker circuits. Circuits are con- figured through the web -based programming utility. ECC-50W-25V: 25V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-501100C power output to 100 watts or can also be used as a backup amplifier. ECC-50W-70V: 70V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100C power output to 100 watts or can also be used as a backup amplifier. ECC-XRM-70V: 70V Transformer Conversion Module. Con- verts the ECC-50/100C primary amplifier to a 70V output. This transformer mounts directly to the ECC-50/100C main control board by two metal brackets. ECC-RTZM: Remote Telephone Zone Module. Allows for secure access to the ECC via cell phone or remote telephone means; not ULC listed. Page 2 of 6—Canadian DF-60815:8.7/28/2015 O FRl OY03A1 R01NE� � IRESYSnF euE ®i OVERRIDE cpN1Xu 13p I '10 I VEMER 1113 0 ZONE1 6REAKER M20 I VEMeR 74, I Z 14 MP ZONEZ LONE 0 Np CpEt 4I VEMER ONE4 ZNE 116s SzRoFAQ 1WoRKC0pr0ap0VErpE 6p IE17p I SPEWERa ZCNE IIONS �I YEeN0E1 60 I VEMER 16p I 6RERKER ZONE 16 ®p I NE -- 70 I WINNER ZONE '1J0 I 6 KER ZONE 19 ®p I wsm,,3 6 0 I SCEMctR ZONE a 2p0 I SPEAKER ZCNE 2n ®0 I IE9910E 4 9a I ONE9[ 21e 1 WE 21R rnDI YESSAMIS iBp I1� 220 I ZONE=R �I wawaEe 11p I menreRE DJN11 230 I Z�IE pR �I Yl16REe1 120 I WEINER ZONE 12 24p I ZClIE 2< �I Yt66t(Ye W'�T1C ® Ip01BlE seEKa ® ane ur,p, neYarenwe "► a[POKp p► WM COX30LE Q D oisr MwI >aD ppoulX ERNEr p ► Eac i D oisr MlP] amD olewtxrwu p► tac2 D pnrnw3 KID welaRrewu p► pwi D D Darr •wa oor Aws >aD D oeu eusEeul we reuu p► p > RNu2 RN 9 D olar nws ► wcXcrE p> RY1 D oisr nNar 1> srsrznlRoiat p► PoA2 1> oisr uma D noon ewRluKr p ► RY3 Control and Indicators PUSH BUTTON CONTROLS All Call MNS Control System Control Speaker Select 1-24 Message Select 1-14 Diagnostic Select Trouble Silence Console Lamp Test NAC Circuit Speaker Circuits TB19 TB20 & TB21 external battery charger - J7 4 CHG-120F charger ECC-50W-25/70\/ optional amplifier Internal _ options ECC-CE6 circuit expander O1O✓U L'CCG oo t__/ o I ECC-LOC local operator console TB4 TB12whr.., TB22 ECC-50/100C Emergency Command Center (Possible Configurations) Canadian DF-60815:8 • 7/28/2015 —Page 3 of 6 LED Status Indicators (visible with door closed) Fire System Active (green) LOC/RM 1-8 Active (green) MNS Control (green) Main Console Fault (yellow) System Control (green) AC Power (green) System in Use (green) Ground Fault (yellow) Speaker Zone 1-24 Active Charger Fault (yellow) (green) Speaker Zone 1-24 Fault Battery Fault (yellow) (yellow) OK to Page (green) Data Bus Fault (yellow) Microphone Trouble (yellow) NAC Fault (yellow) Message 1-8 Active (red) NAC Active (green) Message 1-8 Fault (yellow) System Trouble (yellow) Remote Amplifier 1-8 Fault Audio Riser Fault (yellow) (yellow) LOC/RM 1-8 Fault (yellow) LED Indicators (visible with door and dress panel open) • Speaker Volume Control Fault (yellow). • Option Card Fault (yellow). • Amplifier Over Current Fault (yellow). Product Line Information ECC-50110OC: (Primary Operating Console) 50 Watt, 25VRMS single speaker zone emergency voice evacuation system, integral microphone, built in tone generator and 14 recordable messages. ECC-CE6: Speaker Circuit/Zone Expander Module. ECC-SOW-25V: 25V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-50/100C power output to 100 watts or can also be used as a backup amplifier. ECC-SOW-70V: 70V, 50 watt audio amplifier module. Adding a second speaker circuit increases the total ECC-501100C power output to 100 watts or can also be used as a backup amplifier. ECC-XRM-70V: 70V Transformer Conversion Module. Con- verts the ECC-50/100C primary amplifier to a 70V output. This transformer mounts directly to the ECC-50/100C main control board by two metal brackets. ECC-RTZM: Remote Telephone Zone Module. Allows for secure access to the ECC via cell phone or remote telephone means; not ULC listed. ECC-LOC: Local Operator Console (Complete user interface), Please refer to the data sheet DF-60814 for more information. SEISKIT-COMMENC: Seismic kit for the ECC-50/100C. Includes battery bracket for two 12 AH or 18 AH batteries. MMF-301A: Addressable Mini -Monitor Module. I30OA: SLC Line Isolation Module. TR-CE: Optional Trim Ring. THUMBLTCH: Optional Thumb Latch. (Non ULC-Listed). CHG-120F: 25-120 ampere -hours (AH) External Battery Charger. ECC-MICROPHONE: Replacement Microphone only. BAT-1270: Battery,12 volt,7.0 AH (Two required). Page 4 of 6 —Canadian DF-60815:B • 7/28/2015 BAT-12120: Battery,12 volt,12.0 AH (Two required). BAT-12180: Battery,12 volt, 18.0 AH (Two required). Wiring Requirements See product manual, part number LS10001-000FL-E for detailed wiring requirements. Total System Capacity: (ECC-50/100C only) • Total Built-in Audio Power: 50 Watts. • Total Expandable Audio Power: 100 Watts. • Total Built-in Speaker Circuits: 2. • Total Expandable Speaker Circuits: 8. • Audio Message Max Time Duration: 60 seconds. • External Audio Input: 1. Electrical Specifications PRIMARY(AC) POWER (TB15) ECC-50/100C: 120 VAC, 60 Hz, 3.5 amps (HOT, NEU). Wire size: minimum #14 AWG (2. 00mm2) with 600 V insulation. SECONDARY POWER (BATTERY) CHARGING CIR- CUIT (J7) • Supports lead -acid batteries only. • Float charge voltage at 27.3V • Maximum charge current: 1.0 Amp • Maximum battery charge capability: 2.8 Amps, 26AH (ECC cabinet holds max. 18AH battery). • Minimum Battery size:l2 Amp Hour. AC LOSS RELAY CONTACT RATING (TB3) • 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). FORM C - TROUBLE RELAY CONTACT RATING (TB2) • 2.0 amps @ 30 VDC (resistive), 0.5 amp @ 30 VAC (resistive). MNS ACTIVE RELAY CONTACT RATING (TB1) • 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). NOTIFICATION APPLIANCE CIRCUIT (NAC) OUTPUT RATING (TB19) • One (1) Class B or Class A circuit. • Power -limited circuitry, (Class 2) supervised. • Nominal operating voltage: 24 VDC. • Maximum signaling current for special application power: 2.OA. • Maximum signaling current for regulated power: 200mA. • Maximum wiring impedance: 1 Q. • Current limit: fuse -less, electronic, power -limited. • End -Of -Line Resistor: 4.7 KQ, %watt, (P/N 71252) required for Class B operation. Refer to the Device Compatibility Document 15384 for listed compatible devices. NAC FOLLOWER OUTPUT REMOTE SYNC (TB18) • Connections for FACP NAC synchronization trigger signal. • Trigger input voltage: 9 to 32 VDC, 24 VDC rated. • Input current draw in Alarm condition: 10 mA at rated volt- age. SPECIAL APPLICATION POWER (AUX. POWER) (TB17) • 500 mA @ 24 VDC • Used for powering addressable modules and associated End -of -Line power supervision relays Power -limited circuitry. Refer to the Device Compatibility Doc- ument 15384 for a list of compatible devices. SPEAKER VOLUME CONTROL OVERRIDE (TB23) • Class B or Class A circuit • Special application power • Power -limited circuitry, supervised • Nominal operating voltage: 24 VDC • Maximum signaling current: 0.25 amps • Current limit: fuse -less, electronic, power -limited • End -Of -Line Resistor: 4.7 K12, '%watt, (PIN 71252) required for Class B operation Speaker Circuits Primary Speaker Circuit (TB20) Secondary Speaker Circuit (TB21) (with optional amplifier only) — Circuit can be wired Class B or Class A — Power -limited circuitry — Normal Operating Voltage: 25 VRMS @ 2 amps max and maximum Load Impedance of 12.54 (70.7 VRMS @ 700 mA max. with maximum load Impedance of 1000 opera- tion possible by plugging optional ECC-XRM-70V conver- sion transformer into A 2 of the main control board) —Output Power: 50 watts (10 watts when background music is employed) — Frequency Range: 400Hz - 4,OOOHz — Maximum total capacitance for each speaker circuit: 250 pF — End -of -Line Resistor required for Class B circuit: 15 KS2, 1 watt (PIN: ELR-15K) Command Input Circuits (alarm polari- ties shown) CMD1 - TB4 Terminals 3(+) & 4(-) are input terminals and Ter- minals 1(-) and 2(+) are output terminals which provide feed through of the NAG circuits to NAG devices down stream. CMD2 - T85 Terminals 3(+) & 4(-) are input terminals and Ter- minals 1(-) and 2(+) are output terminals which provide feed through of the NAG circuits to NAG devices downstream. CMD3 - TB6 Terminals 1(+) & 2(-) are input terminals for con- tact closure only. CMD4 - TB6 Terminals 3(+) & 4(-) are input terminals for con- tact closure only. CMDS - TB7 Terminals 1(+) & 2(-) are input terminals for con- tact closure only. CMD6 - TB7 Terminals 3(+) & 4(-) are input terminals for con- tact closure only. CMD7 - TB8 Terminals 1(+) & 2(-) are input terminals for con- tact closure only. CMD8 - TB8 Terminals 3(+) & 4(-) are input terminals for con- tact closure only. • Power -limited and supervised circuitry • Normal Operating Voltage Range: 10.5 VDC - 29 VDC; (Maximum Voltage: 29 VDC) • NAG Reverse Polarity Current (requires End -of -Line Resis- tor from NAC): 1.6 mA maximum • Contact Closure Operation Current (requires 4.7KU, %watt End -of -Line Resistor PIN 27072): 6.6 mA maximum • Maximum Wiring Impedance CMD1 - CMD8 (Contact Clo- sure Operation): 200D NOTE., When the system is programmed for Mass Notification. CMD1and CMD2 will be programmed for Reverse Polarity only See manual P/N: LS 10001-OOOFL-E for more details. MAXIMUM INPUT IMPEDANCE: • CMD1 & CMD2 (Reverse Polarity Operation): 201<0 • CMD1 - CMD8 (Contact Closure Operation): 4.751<92 NIGHT RING INPUT - TB76, TERMINALS 1 (+) & 2 (-) • Contact closure input • Isolated, non -supervised • Operation current: 3.8 mA, maximum • Maximum wiring impedance: 30K52 • Minimum isolation withstand voltage: 1500 VRMS EXTERNAL OPERATOR INTERFACE POWER OUTPUT (TB24) • Non-resettable power for external operator interface com- ponents • Power -limited circuitry, non -supervised • Nominal operating voltage: 24 VDC • Maximum output current: 0.80 amps • Current limit: fuse -less, electronic, power -limited circuit EXTERNAL DATA BUS (EIA-485) (TB12) • Data connections for external operator interface components • Redundant transceiver circuitry for Class A operability • Power -limited circuitry, supervised • Maximum wiring impedance: 13.212. FACP DATA BUS (EIA-485) (TB13) • Dedicated connection to FACP serial bus • Output terminals: pass -through to other system components. • Isolated, supervised • Minimum isolation withstand voltage: 1500 VRMS • Maximum wiring impedance: 40D (ANN-BUS), 2652 (ACS-BUS) • External Audio Riser (TB22) • Class B or Class A audio connections to external operator interface components • Power -limited circuitry, supervised • Audio signal level: 3.85 V, maximum Frequency range: 400 Hz - 4 KHz RMS ELECTRICAL SPECIFICATIONS DISPLAY BOARD EXTERNAL AUDIO INPUT (TB5) Input Impedance: 8.51(D nominal @1 KHz Input Voltage: 700 mVrms maximum Input Current: 0.1 mA maximum @ 700 mV NOTE: Some laptopsrpersonal computers only provide an audio output for headphones. It may be necessary to adjust the head- phone output level for proper recording of voice messages. ECC-CE6 Circuit Expander Module Specifications Power -limited circuitry Canadian DF-60815:B • 7/28/2015 —Page 5 of 6 • Up to six (6) circuits on the ECC-CE6 can be wired as Class B or Class A) • Normal Operating Voltage for Speaker Circuits: 25 VRMS @ 2.0 amps max. (Maximum Load Impedance of 12.55)) • 70.0 VRMS @ 700 mA max. with maximum Load Imped- ance of 1000 operation possible for the primary circuit by plugging in an optional ECC-XRM-70V conversion trans- former into J12 of the main control board. The same opera- tion is possible for the optional 50W amplifier by selecting the ECC-50W-70V model • Speaker circuit wiring is supervised during standby, back- ground music, and alarm • Output Power: 50 watts total; Frequency Range: 400Hz - 4,000Hz • Maximum total capacitance: 250 pF. (Note that the total capacitance for the speaker outputs must not exceed the maximum of 250 pF) • End -of -Line Resistor required for Class B speaker circuit: 15 KS?, 1 watt (P/N: ELR-15K) TB13 on the main control board: ACS/ANN (EIA-485) electrically isolated link to FACP provides programmed speaker control Cabinet Specifications Backbox: 19.0"(48.26 cm) high x 16.65"(42.29 cm) wide x 5.20"(13.23 cm) deep. Door: 19.26" (48.92 cm) high x 16.82"(42.73 cm) wide x 0.12"(0.30 cm) deep. Trim Ring (TR-CE): 22.00" (55.88 cm) high x 19.65" (49.91 cm) wide. Shipping Specifications Base Unit Weight: 27.85 Ibs (12.63 kg). Temperature and Humidity ranges This system meets ULC requirements for operation at 0-490 C/ 32-1200 F and at a relative humidity 93% t 2% RH (non - condensing) at 32°C t 2°C (90"F t WF). However, the useful life of the system's standby batteries and the electronic com- ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-270 C/60-800 F. Agency Listings and Approvals The listings and approvals below apply to the basic ECC-50/ 100 control panel. In some cases, certain modules may not be listed by certain approval agencies or listing may be in pro- cess. Consult factory for latest listing status. • UL/ULC Listed S2424 • CSFM: 7300-0075:0226. • NYC Fire Dept.Certificate of Approval: #6152 • FM Approved. Standards and Codes CAN/ULC-S572. IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seis- mic). The ECC-50/100C complies with the following ULC Standards, Fire-Lite®Alarms is a registered trademark of Honeywell International Inc. International Building Codes, and with NFPA 72 Fire Alarm 02015 by Honeywell International Inc. All rights reserved. Unauthorized use system requirements. of this document is strictly prohibited. V O 9��1 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and accurate. We cannot coverall specific applications or anticipate all requirements. INiIRB11811 h1A81f1tT111111 UUft1TY SYSTEMS All specifications are subject to change without notice. For more information, contact Fine-Lite Alarms. Phone: (800) 627-3473. FAX: (877) 699-4105, www.firelite.com Page 6 of 6 — DF-60815:e • 7/2812015 OFlrteLITeALarms ECC-50/100 Battery Calculation by Honeywell Secondary Power Source Requirements IStandby Current (amps) Secondary Alarm Current (amps) Device Type Qty Current Draw Total Gly, Current Dra Total 1. System ECC-501100 Primary Console 1 X 0.2720 = 0.2720 1 X 0.4460 = 0.4460 ECC-50W-25V/70V"' 0 X 0.1000 = 0 X 0.2350 = ECC-50W-25V/70V (As Backup)" 0 X 0.1000 = 0 X 0.0000 = ECC-CE6 Circuit Expander 0 X 0.0200 = 0 X 0.1890 = ECC-RTZM 0 X 0.0550 = 0 X 0.0600 = ECC-FFT Firefighter Telephone 0 X 0.1200 = 0 X 0.2300 = 2. Operator Interface Devices (Maximum of 8 total) ECC-LOC Local Operator Console 0 X 0.0850 = 0 X 0.1000 = ECC-RM Remote Microphone 0 X 0.0500 = 0 X 0.0640 = ECC-RPU Remote Page Unit 0 X 0.0500 = 0 X 0.0680 = Total Devices: 0 3. Additional Amplifiers (Maximum of 8 total) ECC-50DA 0 X 0.0120 = 0 X 0.0120 = ECC-125DA 0 X 0.0120 = 0 X 0.0120 = ECC-50BDA 0 X 0.0120 = 0 X 0.0120 = Total Amplifiers: 0 4. Speakers (Maximum 50 Watts) 1/4 Watt 48 X 0.0000 = 0.0000 48 X 0.0170 = 0.8160 1/2 Watt 0 X 0.0000 = 0 X 0.0330 = 3/4 Watt 0 X 0.0000 = 0 X 0.0500 = 1 Watt 0 X 0.0000 - 0 X 0.0680 = 2 Watt 0 X 0.0000 = 0 X 0.1320 = Custom Watt Tap Description 0 X 0.0000 = 0 X 0.0000 = Total Watts: 12 S. Output Circuits NAC Output (2 amps maximum) 0.00000 = 0.00000 = Non-Resettable Output (0.5 amps max) 0.00000 = 0.00000 = 6. Additional Devices Power Supervision Relays 0 X 0.0250 = 0 X 0.0250 = SP-SVC Volume Control 0 X 0.0100 = 0 X 0.0100 = Total Standby Load 0.2720 Total Alarm Load 1.2620 '1 Select only one Additional Amplifier based on whether or not it will be used for backup purposes. ®FlrewreALarms by Honeywell ECC-50/100 Battery Calculation Calculation in Total Sheet Load Current (Amps) 0.2720 Amps X= ;24HoursStandby ;&528sAlarm Load Current (Amps) 1.2620 Amps X = Total Current Load 6.84 AN `Multiply by the Derating Factor 1.2 = x 1.20 Total Ampere Hours Required 8.21 AH W9 Ritz.1NAD1a;] &.b: ANN-80 SO -Character Serial LCD Annunciator General The ANN-80 annunciator is a compact, backlit, 80-character LCD fire annunciator that mimics the Fire Alarm Control Panel (FACP) display. It provides system status indicators for AC Power, Alarm, Trouble, Supervisory, and Alarm Silenced conditions. The ANN-80 and the FACP communicate over a two -wire serial interface employ- ing the ANN-Bus communication format. Connected devices are powered, via two additional wires, by either the host FACP or a remote UL-listed, filtered power supply. The ANN-80 is red; for white, orderANN-80-W. The ANN-80 displays English -language text of system point informa- tion including device type, zone, independent point alarm, trouble or supervisory status, as well as any custom alpha labels programmed into the control panel. It includes control switches for remote control of critical system functions. (A keyswitch prevents unauthorized operation of the control switches.) Up to eight ANN-80s may be connected to the ANN-Bus of each FACP. No programming is required, which saves time during system commissioning. Features • Listed to UL Standard 864, 9th Edition • Backlit 80-character LCD display (20 characters x 4 lines) • Mimics all display information from the host panel • Control switches for System Acknowledge, Signal Silence, Drill, and Reset • Control switches can be independently enabled or disabled at the FACP • Keyswitch enables/disables control switches and mechanically locks annunciator enclosure • Keyswitch can be enabled or disabled at the FACP • Enclosure supervised for tamper • System status LEDs for AC Power, Alarm, Trouble, Supervisory, and Alarm Silence • Local sounder can be enabled or disabled at the FACP • ANN-80 connects to the ANN-Bus terminal on the FACP and requires minimal panel programming • Displays device type identifiers, individual point alarm, trouble, supervisory, zone, and custom alpha labels • Time -and date display field - • Surface mount directly to wall or to single, double, or 4" square electrical box • Semi -flush mount to single, double, or 4" square electrical box. Use ANN-SB80KIT for angled view mounting • Can be remotely located up to 6,000 feet (1,800 m) from the panel • Backlight turns off during AC loss to conserve battery power but will turn back on if an alarm condition occurs • May be powered by 24 VDC from the host FACP or by remote power supply (requires 24 VDC) • Up to eight ANN-80s can be connected on the ANN-Bus Controls and Indicators • AC Power • Alarm • Trouble (a Rre•LITeALarmS by Honeywell • Supervisory • Alarm Silenced Specifications Operating voltage range: 18 VDC to 28 VDC • Current consumption @ 24 VDC nominal (filtered and non- resettable): 40 mA maximum • Ambient temperature: 32•F to 1207 (0°C to 49'C) • Relative humidity: 93% t 2% RH (non -condensing) at 32°C t 2°C (90°F t 3•F) • 5.375" (13.65 cm.) high x 6.875" (17.46 cm.) wide x 1.375" (3.49 cm.) deep • For use indoors in a dry location All connections are power -limited and supervised The ANN-Bus POWERING THE DEVICES ON THE ANN-BUS FROM AUXIL- IARY POWER SUPPLY The ANN-Bus can be powered by an auxiliary power supply when the maximum number of ANN-Bus devices exceeds the ANN-Bus power requirements. See the FACP manual for more information. ANN-BUS DEVICE ADDRESSING Each ANN-Bus device requires a unique address (ID Number) in order to communicate with the FACP. A maximum of 8 devices can be connected to the FACP ANN-Bus communication circuit. See the FACP manual for more information. WIRE REQUIREMENTS: COMMUNICATIONS CIRCUIT The ANN-80 connects to the FACP ANN-Bus communications cir- cuit. To determine the type of wire and the maximum wiring distance that can be used with FACP ANN-Bus accessory modules, it is nec- essary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. NOTE: For total worst rase current draw on a single ANN-Bus refer to appropriate FACP manual. DF-52417'.D • 3/15/2018 — Page 1 of 2 WIRE REQUIREMENTS: POWER CIRCUIT • 14 to 18 AWG (0.75 - 2.08 mm2) wire for 24 VDC power circuit is acceptable. Power wire distance limitation is set by 1.2 volt maxi- mum line drop form source to end of circuit. • All connections are power -limited and supervised. • A maximum of eight ANN-80 modules may be connected to this circuit. Ordering Options ANN-80: Red 80 character LCD Annunciator. ANN-80-W: White, 80 character LCD Annunciator. ANN-SBSOKIT-R: Red surface mount backbox with angled wedge. ANN-SB80KIT-W: White surface mount backbox with angled wedge. Agency Listings and Approvals The listings and approvals below apply to the ANN-80. In some cases, certain modules may not be listed by certain approval agen- cies, or listing may be in process. Consult factory for latest listing status. • UL: S2424 • FM approved • CSFM: 7120-0075:0211 • MEA: 442-06-E Fire-Lite®Alanns is a registered trademark of Honeywell International Inc. 02018 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. O 9001 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. V ® All specifications are subject to change without notice. 61YYEBIrS SYSTEMS !YlLIiT SYSTEMS M S For more information. contact Fire-Lite Alarms. Phone: 800 627-3473, FAX: 877 699-4105. ( ) ( ) Country of Odgin: USA v,^rnw.flrelite.com Page 2 of 2 — DF-52417:D • 3M512018 2021 Order Form #1 EMERGENCY ACCESS SYSTEMS, INC. PRICE LIST Prices and availability subject to change Email:easkeybox@aol.com Tel:401-295-7707 Fax:401-295-7708 www.easkeybox.com 9 5000 &,faoe Mounted Lift OH Door 5000R Recessed Mounted Lift Off Door EAS MODEL 5000 SURFACE MOUNTED KEY BOX 10 Key capacity 5"H x 4"W x 3'/PD Stock# Color Price 5000-1 Black $279.00 5000-2 Brown $299.00 5000-3 Gray $299.00 5000TS-4 Black w/ tamper switch $319.00 5000TS-5 Brown w/ tamper switch $339.00 5000TS-6 Gray w/ tamper switch $339.00 Shipping & Handling $20.00 per unit EAS MODEL 5000R RECESSED MOUNTED KEY BOX 10 Key capacity 5"H x 4"W x 31WID with 7" x 7" flange Stock# Color Price 5000R-1 Black $329.00 5000R-2 Brown $349.00 5000R-3 Gray $349.00 5000RTS4 Black w/ tamper Switch $369.00 5000RTS-5 Brown w/ tamper switch $389.00 5000RTS-6 Gray w/ tamper switch $389.00 5000RMK Recessed Mounting kit $105.00 (Fornew construction onty) Shipping & Handling $20.00 per unit MPL-1 MPL-2 MKS PADLOCKS and KEY SWITCH Stock# Description Price MPL-1 5116" x 2 318" Stainless Shackle $99.00 MPL-2 7/16" x 1 7/8" Stainless Shackle $105.00 MKS-1 Electric Key Switch -Red $119.00 MKSD-1 Dual Key Switch -Red $199.00 Shipping & Handling $20.00 per unit EAS MODEL 2800 TRUCK BOX Fire Department use only Apparatus key capture device Stock# Color Price 2800 Red $329.00 Shipping & Handling $20.00 per unit 6000 Surface Mounted Hinged Door SOOOR Recessed Mounted Hinged Door EAS MODEL 6000 SURFACE MOUNTED KEY VAULT 55 Key capacity 7"H x 7"W x 5"D Stock# Color Price 6000-1 Black $499.00 6000TSA Black w/ tamper switch $549.00 6000DL Dual lock option $109.00 (available on all 6000 series boxes) Shipping & Handling $33.00 per unit EAS MODEL 6000R RECESSED MOUNTED KEY VAULT 55 Key capacity 7"H x 71W x 5"D with 9%" x 9112' flange Stock# Color Price 6000R-1 Black $569.00 6000RTS-4 Black w/ tamper switch $619.00 6000RDL Dual lock option $109.00 6000RMK Recessed Mounting kit $119.00 (Fornew construction only) Shipping & Handling $33.00 per unit 1500 Surface Mounb Data Storage Box EAS MODEL 1500 DATA STORAGE BOX Data Storage 15"H x14"W x 3Y. "D Stock# Color Price 1500-1 Almond $419.00 Shipping & Handling $33.00 per unit KEY TAGS Custom made to your request ■ (examples shown to the left) Stock# Description Price ,^ CKT Yellow custom key tags PKT Fiber tags-pkg. of 10 $5.00 $5.00 4a 101 Fire Dept. Alert Decal $2.00 2500 DH Door Hung Mounted 2500 Swfe. Mounted EAS MODEL 2500 SINGLE FAMILY RESIDENTIAL KEY BOX Residential use only 1 or 2 key capacity 511H x 41W x 2"D Stock# Color Price 2500 Black Surface Mount $249.00 250ODH Black Door Hung Mount $265,00 Shipping & Handling $20.00 per unit (/2-0IllNEAS EMERGENCY ACCESS SYSTEMS, INC. WWW.EASKEYBOX.COM SOLD TO: Date: Company: Street: City/State: Zip: Contact Person: Phone: ( INSTALLATION ADDRESSES Section 3 (Required by Fire Department) List street addresses and cities where items will be installed. Attach separate sheet for additional installation addresses. �m Bldg. SHIPPING & HANDLING Section 5 All Sales + Shipping is now Taxable in RI Models 6000 and 1500 $33.00 per unit All other products $20.00 per unit Section1 2021 Order Form #1 Prices valid thru 12/31/2021 (Please call for prices thereafter) SHIP TO: (Street Address ONLY - No P.O. Box) Section 2 Company: Street: City/State: Contact Person: Phone: ( ) Zip: PAYMENT INFORMATION Section 4 ❑ Check or Money Order Exp. Date: ❑ Visa ❑ Mastercard Card Verification code: Card Billing Address #'a (Last 3 digits on back of card) Street or P.O. Box #. Zip Code: Card Number Signature I agree to pay the total amount according to card issuer agreement (A convenience fee of 3.5% is applied when using a credit card.) AUTHORIZED FIRE AGENCY SIGNATURE EASTHAMPTON FIRE DEPARTMENT FIRE DEPARTMENT Section 6 SEE PRODUCT LIST ON BACK OF THIS PAGE section 7 Qty. Stock # Item Description Color Price Ea. Total All Sales & Shipping is now taxable in RI when orders are shipped to RI addresses Shipping & Handling Please add a convenience fee of 3.5% when using a credit card SUBTOTAL MakepayableArmor;�FOR FIRE Dept. USE ONLY paymentSend this form with ❑ Check here if products ordered on this form must be rP.O. :. SUBMASTERED dd $9.00 to EACH Item ordered RI Sales Tax 7% convenience fee 3.5% $ $ - TOTAL $ 5000H 8-d.ce Mounted - Hinged poor G 5000HR Recessed Mounted - Hinged Door EAS Model 5000H (Hinged Door) SURFACE MOUNTED KEY BOX 10 Key capacity 4"Hx5"Wx3%"D EAS Model 5000HR (Hinged Door) RECESSED MOUNTED KEY BOX 10 Key capacity 4"H x 5"W x 3 %" D with 7" x 7" flange • Price Stock # Color Price 5000H-1 Black $309.00 5000HR-1 Black $359.00 5000 - $329.00 5000HR-2 Brown 5000H-3 Gray $329.00 5000HR-3 Gray$379.00 $39.00 5000HTS-0 Black w/ tamper switch $349.00 SOOOHRTSd Black w/ tamper switch $399.00 5000HTS-5 Brown w/tamper switch $369.00 5000HRTS-5 Brown w/tamper switch $419.00 5000HTS-5 Gray w/tamper switch $369.00 5000HRT5-6 Gray wt tamper switch $419.00 Shipp/ng & Handling (adding tor each unit) $20.00 5000HRMK Recessed Mountinq kit $105.00 (Forhinged box and new conshuciion only Shipping & Handling (adding for each unto $20.00 `PLEASE CALL FOR INFORMATION ON RETURN WARRANTY POLICIES" Email: easkeybox(a)aol com 401-295-7707 OR FAX: 401-295.7708 • Tinned, stripped leads for ease of wiring. • Direct -dial entry of address: 01 — 159 on MS-9600 series panels, 01 — 99 on other compatible systems 1415 0 1 ADDRESS 0 1 3 2 3 F 2 F 12 //�\\ 3 11 0 4 LOOP 4 10 5 5 9 6 7 6 9 6 7 6 TENS ONES I� I� cc W The MMF-301(A) Mini Monitor Module can be installed in a single -gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The MMF-301(A) is intended for use in intelligent, two -wire systems where the individual address of each module is selected using rotary switches. It provides a two -wire initiat- ing device circuit for normally -open -contact fire alarm devices. The MMF-301(A) can be used to replace M301(A) modules in existing systems. MMF-301(A) APPLICATIONS Use to monitor a single device or a zone of four -wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally -open dry -contact devices. May also be used to monitor normally -open supervisory devices with special supervisory indication at the control panel. Monitored circuit/ device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47K Ohm End -of -Line Resistor (provided) terminates the circuit. MMF-301(A) OPERATION Each MMF-301(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). MMF-301(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Average operating current: 350 pA, 1 communication every 5 seconds, 47k EOL; 600 pA Max. (Communicating, IDC Shorted). Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 450 pA. EOL resistance: 47K Ohms. Temperature range: 32•F to 120°F (0°C to 49`C). Humidity range: 10% to 93% noncondensing. Dimensions: 1.3" (3.302 cm) high x 2.75" (6.985 cm) wide x 0.55" (1.651 cm) deep. Wire length: 6" (15.24 cm) minimum. MMF•302(A) Interface Module • Supports compatible two -wire smoke detectors. Page 2 of 4 — DF-52121:E • 07/30/2015 • Supervises IDC wiring and connection of external power source. High noise (EMF/RFI) immunity. SEMS screws with clamping plates for ease of wiring • Direct -dial entry entry of address: 01 — 159 on MS-9600 series panels, 01 — 99 on other compatible systems. • LED flashes during normal operation. • LED latches steady to indicate alarm on command from control panel. The MMF-302(A) Interface Module is intended for use in intelli- gent, addressable systems, where the individual address of each module is selected using built-in rotary switches. This module allows intelligent panels to interface and monitor two - wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two -wire detectors being monitored must be UL compatible with the module. The MMF-302(A) can be used to replace M302(A) modules in existing systems. MMF-302 (A) APPLICATIONS Use the MMF-302(A) to monitor a zone of two -wire smoke detectors. The monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 3.9 K Ohm End -of -Line Resistor (provided) terminates the end of the Style B or D (class B or A) circuit (maximum IDC loop resistance is 25 Ohms). Install ELR across terminals 8 and 9 for Style D application. MMF-302(A) OPERATION Each MMF-302(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-302(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current drew: 5.1 mA (LED on). Maximum IDC wiring resistance: 25 Ohms. Average operating current: 270 pA, 1 communication and 1 LED flash every 5 seconds, 3.9k eol. EOL resistance: 3.9K Ohms. External supply voltage (between Terminals T10 and T11): • DC voltage: 24 volts power limited. • Ripple voltage: 0.1 Vrms maximum. • Current: 90 mA per module maximum. Temperature range: 32°F to 120°F (0°C to 49•C). Humidity range: 10%to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125' (5.398 cm) deep box. MDF-30O(A) Dual Monitor Module The MDF-300(A) Dual Monitor Module is intended for use in intelligent, two -wire systems. It provides two independent two - wire initiating device circuits (IDCs) at two separate, consecutive addresses. It is capable of monitoring normally open contact fire alarm and supervisory devices. The module has a single panel - controlled LED. INSTALLATION AND MAINTENANCE INSTRUCTIONS MMF-301 Monitor Module Firelffe warms by Honeywell One FireLite Place Northford, CT 06472 Phone: 203.484.7161 SPECIFICATIONS Nominal Operating Voltage: 15-32 VDC Average Operating Current: 375 pA (group poll); 350 pA (direct poll); 600 pA Maximum (Communicating, IDC Shorted) EOL resistance: 47K ohms Maximum IDC Resistance: 1,500 Ohms Maximum IDC Voltage: 11 Volts Maximum IDC Current: 450 pA Temperature Range: 3£F to 120' F (O'C to 49' C) Humidity: 10% to 93% Non -condensing Dimensions: 1.3- H x 2.75" W x 0.65" D Wire length: 6" minimum BEFORE INSTALLING This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the opera- tor and local authority that the system will be temporarily out of service. Dis- connect power to the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. GENERAL DESCRIPTION The MMF-301 monitor module can be installed in a single gang junction box directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting (see Figure 1). The MMF-301 is intended for use in intelligent, two -wire systems where the individual address of each module is selected using rotary switches. It provides a two -wire initiating cir- cuit for normally open contact fire alarm and security devices. This module can be used to replace an M301 module in existing systems. COMPATIBILITY REQUIREMENTS To ensure proper operation, this module should only be connected to listed compatible system control panels only. FIGURE 1: C1063-00 MOUNTING AND WIRING NOTE: This module is intended to be wired and mounted without rigid con- nections inside a standard electrical box. All wiring must conform to appli- cable local codes, ordinances, and regulations. 1. Connect the red (+) and black (-) wires to the positive and negative loop power leads of the Signaling Line Circuit (SLC). 2. Connect the violet (+) and yellow (-) wires to a two -wire, normally open initiating loop. 3. Install the specified EOL resistor value to terminate the initiating loop. 4. Set the address on the module per job drawings. S. Install the module in the desired mounting location. FIGURE 2. TYPICAL 2-WIRE STYLE B INITIATING DEVICE CIRCUIT (IDC) CONFIGURATION: COMPATIBLE CONTROL SIGNAL LINE CIRCUIT(SLC) PANEL (+)TO 1 (_) NE —p NEXT DEVICE ALL WIRING SHOWN IS ;:; SUPERVISEDAND *i arvr. POWER LIMITED 47k EOL INCLUDED (ELR-47k) C0614-02 FL-460-004 1 156-3654-002 02008 FireLfte Alarms Inc. Fire LiteCD is a registered trademark and Ute6peed"' and FireWatchTM are trademarks of Honeywell International Inc. 02015 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. I V O 9oo+1 This document is not intended to be used for installation purposes. We try to keep our product information up-to-date and aceurate. We cannot cover all specific applications or anticipate all requirements. BICREBINC C MANIkAC01MN6 QUALITY SYSTEMS All specifications are subject to change without notice. For more information, contact Fire-Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. www.firelite.com Page 4 of 4 — DF-52121:E • 07/30/2015 DF-52121:E • E-325 MMF-300(A) Series, MDF-300 Addressable Monitor Modules Four different monitor modules are available for Fire-Lite's intelligent control panels to suit a variety of applications. Moni- tor modules are used to supervise a circuit of dry -contact input devices, such as conventional heat detectors and pull stations, or monitor and power a circuit of two -wire smoke detectors (MMF-302(A)). MMF-300(A) is a standard -sized module (typically mounts to a 4" [10.16 cm] square box) that supervises either a Style D (Class A) or Style B (Class B) circuit of dry -contact input devices. MMF-301(A) is a miniature monitor module a mere 1.3" (3.302 cm) H x 2.75" (6.985 cm) W x 0.65" (1.651 cm) D that super- vises a Style B (Class B) circuit of dry -contact input devices. Its compact design allows the MMF-301(A) to be mounted in a single -gang box behind the device it monitors. MMF302(A) is a standard -sized module used to monitor and supervise compatible two -wire, 24 volt, smoke detectors on a Style D (Class A) or Style B (Class B) circuit. MDF-300(A) is a standard -sized dual monitor module used to monitor and supervise two independent two -wire Style B (Class B) dry -contact initiating device circuits (IDCs) at two separate, consecutive addresses in intelligent, two -wire sys- tems. LiteSpeed Ta is a communication protocol developed by Fire-Lite Engineering that greatly increases the speed of com- munication between analog intelligent devices. Intelligent devices communicate in a grouped fashion. If one of the devices within the group has new information, the panel CPU stops the group poll and concentrates on single points. The net effect is response speed greater than five times that of other communication protocols. MMF-3O0(A) Monitor Module • Built-in type identification automatically identifies this device as a monitor module to the control panel. • Powered directly by two -wire SLC loop. No additional power required. • High noise (EMF/RFI) immunity. • SEMS screws with clamping plates for ease of wiring. • Direct -dial entry of address: 01 — 159 on MS-9600 series panels, 01 — 99 on other compatible systems. • LED flashes during normal operation and latches on steady to indicate alarm. The MMF-300(A) Monitor Module is intended for use in intelli- gent, two -wire systems, where the individual address of each module is selected using the built-in rotary switches. It pro- vides either a two -wire or four -wire fault -tolerant Initiating Device Circuit (IDC) for normally -open -contact fire alarm and supervisory devices. The module has a panel -controlled LED indicator. The MMF-300(A) can be used to replace M300(A) modules in existing systems. MMF-300(A) APPLICATIONS Use to monitor a zone of four -wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally - open dry -contact alarm activation devices. May also be used to monitor normally -open supervisory devices with special (a FIYe•LITe'ALarms by Honeywell Addressable Devices MMF300(A) (Type H) supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K Ohm End -of -Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. MMF-300(A) OPERATION Each MMF-300(A) uses one of the available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/nor- mal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop). MMF-300(A) SPECIFICATIONS Nominal operating voltage: 15 to 32 VDC. Maximum current draw: 5.0 mA (LED on). Average operating current: 375 pA (LED flashing), 1 com- munication every 5 seconds, 47k EOL. Maximum IDC wiring resistance: 1500 Ohms. Maximum IDC Voltage: 11 Volts. EOL resistance: 47K Ohms. Temperature range: 32'17 to 120°F (0°C to 49°C). Humidity range: 10% to 93% noncondensing. Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125" (5.398 cm) deep box. MMF-301(A) Mini Monitor Module Built-in type identification automatically identifies this device as a monitor module to the panel. Powered directly by two -wire SLC loop. No additional power required. High noise (EMF/RFI) immunity. DF-52121:E • 07/30/2015 — Page 1 of 4 NOTE: The MDF-300(A) provides two Style B (Class B) IDC cir- cuits ONLY Style D (Class A) IDC circuits are NOT supported in any application. MDF-300(A) SPECIFICATIONS Normal operating voltage range: 15 to 32 VDC. Maximum current draw: 6.4 mA (LED on). Average operating current: 750 pA (LED flashing). Maximum IDC wiring resistance: 1,500 Ohms. Maximum IDC Voltage: 11 Volts. Maximum IDC Current: 240 pA EOL resistance: 47K Ohms. Temperature range: 32' to 120•F (0° to 49•C). Humidity range: 10% to 93% (non -condensing) Dimensions: 4.5" (11.43 cm) high x 4" (10.16 cm) wide x 1.25" (3.175 cm) deep. Mounts to a 4" (10.16 cm) square x 2.125' (5.398 cm) deep box. MDF-300(A) AUTOMATIC ADDRESSING The MDF-300(A) automatically assigns itself to two address- able points, starting with the original address. For example, if the MDF-300(A) is set to address "26", then it will automati- cally assign itself to addresses "26" and "27". NOTE: "Ones" addresses on the MDF-300(A) are 0, 2, 4, 6, or 6 only. Terminals 6 and 7 use the first address, and terminals 8 and 9 use the second address. CAUTION: Avoid duplicating addresses on the system. Installation MMF-300(A), MMF-302(A), and MDF-300(A) modules mount directly to a standard 4" (10.16 cm) square, 2.125" (5.398 cm) deep, electrical box. They may also be mounted to the SMB500 surface -mount box. Mounting hardware and installa- tion instructions are provided with each module. All wiring must conform to applicable local codes, ordinances, and regu- lations. These modules are intended for power -limited wiring only. The MMF-301(A) module is intended to be wired and mounted without rigid connections inside a standard electrical box. All wiring must conform to applicable local codes, ordinances, and regulations. Agency Listings and Approvals In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult fac- tory for latest listing status. • UL: S2424. • ULC: S2424. FM Approved. CSFM: 7300-0075:0185. MEA: 72-01-E. Product Line Information NOTE: A" suffix indicates ULC-listed model. MMF-300(A): Monitor module. MMF-301(A): Monitor module, miniature. MMF-302(A): Monitor module, two -wire detectors. MDF-300(A): Monitor module, dual, two independent Class B circuits. SMB500: Optional surface -mount backbox. NOTE: See installation instructions and refer to the SLC Wiring Manual, Ply 51309. Architects'/Engineers' Specifications Specifications of these devices and all FireLite products are available from FireLite. DF-52121:E - 07/30/2015 — Page 3 of 4 DF-52013:13 • E-100 BG-12LX Addressable Manual Pull Station General The Fire-Lite BG-12LX is a state-of-the-art, dual -action (i.e., requires two motions to activate the station) pull station that includes an addressable interface (mounted inside) for Fire-Lite's addressable fire alarm control panels (FACPs) Because the BG-12LX is addressable, the control panel can display the exact location of the activated manual station. This leads fire personnel quickly to the location of the alarm. Features • Maintenance personnel can open station for inspection and address setting without causing an alarm condition. • Built-in bicolor LED, which is visible through the handle of the station, flashes in normal operation and latches steady red when in alarm. • Handle latches in down position and the word "ACTIVATED" appears to clearly indicate the station has been operated. • Captive screw terminals wire -ready for easy connection to SLC loop (accepts up to 12 AWG/3.25 mm' wire). • Can be surface mounted (with SB-10 or SB-1/0) or semi - flush mounted. Semi -flush mount to a standard single - gang, double -gang, or 4° (10.16 cm) square electrical box. • Smooth dual -action design. • Meets ADAAG controls and operating mechanisms guide- lines (Section 4.1.3[13]); meets ADA requirement for 5 lb. maximum activation force. • Highly visible. • Attractive shape and textured finish. • Key reset. • Includes Braille text on station handle. • Optional trim ring (BG12TR). • Meets UL 38, Standard for Manually Actuated Signaling Boxes. Construction Shell, door, and handle are molded of durable polycarbonate material with a textured finish. Specifications • Shipping Weight: 9.6 oz. (272.15 g) • Normal operating voltage: 24 VDC. • Maximum SLC loop voltage: 28.0 VDC. • Maximum SLC standby current: 375 pA. • Maximum SLC alarm current: 5 mA. • Temperature Range: 320F to 120OF (0°C to 49°C) • Relative Humidity: 10% to 93% (noncondensing) • For use indoors in a dry location Installation The BG-12LX will mount semi -flush into a single -gang, double - gang, or standard 4" (10.16 cm) square electrical outlet box, or will surface mount to the model SB-10 or SB-1/0 surface back - box. If the BG-12LX is being semi -flush mounted, then the optional trim ring (BG12TR) may be used. The BG12TR is (a FICe•LITe'ALarms by Honeywell usually needed for semi -flush mounting with 4• (10.16 cm) or double -gang boxes (not with single -gang boxes). Operation Pushing in, then pulling down on the handle causes it to latch in the down/activated position. Once latched, the word "ACTI- VATED" (in bright yellow) appears at the top of the handle, while a portion of the handle protrudes from the bottom of the station. To reset the station, simply unlock the station with the key and pull the door open. This action resets the handle; clos- ing the door automatically resets the switch. Each manual station, on command from the control panel, sends data to the panel representing the state of the manual switch. Two rotary decimal switches allow address settings (1 - 159 with Breakaway Tab removed for MS-9600 Series, 1 - 99 and MS-92000DLS, 1 - 50 for MS-9050UD). Architectural/Engineering Specifications Manual Fire Alarm Stations shall be non -coded, with a key - operated reset lock in order that they may be tested, and so designed that after actual Emergency Operation, they cannot be restored to normal except by use of a key. An operated sta- tion shall automatically condition itself so as to be visually detected as activated. Manual stations shall be constructed of red -colored polycarbonate material with clearly visible operat- ing instructions provided on the cover. The word FIRE shall appear on the front of the stations in white letters, 1.00 inches (2.54 cm) or larger. Stations shall be suitable for surface mounting on matching backbox SB-10 or SB-I/O; or semi -flush mounting on a standard single -gang, double -gang, or 4' (10.16 cm) square electrical box, and shall be installed DF-52013:13 • 4/13/2012 — Page 1 of 2 SYSTEM SPECIFICATIONS Size: 2.0" (5.3 cm) high; base determines diameter - B300-6: 6.1" (15.6 cm) diameter - B501: 4" (10.2 cm) diameter For a complete list of detector bases see DF-60983 Shipping weight: 3.4 oz. (95 g) Operating temperature range: • H365, H365R Series: -4'F to 100°F (-20"C to 38'C) • H365H Series: -4°F to 150•F (-20°C to 66°C) Detector spacing: UL approved for 50 ft. (15.24 m) center -to -cen- ter, FM approved for 25 x 25 ft. (7.62 x 7.62 m) spacing Relative humidity: 10%-93% non -condensing Thermal ratings: fixed -temperature set point 1350F (57`C), rate -of - rise detection 15°F (8.3°C) per minute, high temperature heat 190'F (88°C) Mounting: B300-6(A) flanged base, included See "Product Line Information: Intelligent Bases," if using a dif- ferent base. ELECTRICAL SPECIFICATIONS Voltage range: 15 - 32 volts DC peak Standby current (max. avg.): 200pA @ 24 VDC (one communica- tion every 5 seconds with LED enabled) Max current: 4.5 mA @ 24 VDC ("ON") Listings and Approvals Listings and approvals below apply to the H365 Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest list- ing status. ULIULC Listing: S2517 FM Approved CSFM: 7272-0075:0501 LiteSpeedTM is a trademark and Fire•LiteO Alarms is a registered trademark of Honeywell International Inc. 02019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. 9 I 09001 0 O We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. UICIMe11NL & MANUXTINNI QUALITY SYSTEMS For more information, contact Fire•Lite Alarms.Phone:(800)627-3473,FAX:(877)699-4105. Country of Ongin: Mexico wwwArelite.com Page 3 of 3 — DF-61011:C • 1111 BI2019 DF-61010:B SD365 Series Addressable Photoelectric Smoke Detectors The Fire-Lite® Alarms SD365(A), SD365R(A), and SD365HT(A) intelli-gent plug-in smoke detectors are designed for both performance and aesthetics, and are direct replacements for the SD355 Series. A new modern, sleek, contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards. Exclusively for use with Fire-Lite's addressable fire alarm control panels, the SD365(A) Series point ID capability allows each detec- tor's address to be set with rotary, decimal address switches, provid- ing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious res- cue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. The SD365(A) Series also offers 135°F (57"C) fixed temperature thermal sensing on the SD365T(A) and a remote test capable detec- tor on the SD365R(A) for use with DNR(A)/DNRW duct smoke detector housings. Features SLC LOOP: Two -wire SLC loop connection Unit uses base for wiring • Compatible with LiteSpeedl ' and CLIP protocol systems • Stable communication technique with noise immunity ADDRESSING: • Addressable by device • Rotary, decimal addressing (Refer to the Fire-Lite panel manuals for device capacity.) ARCHITECTURE: • Sleek, low -profile, stylish design • Unique single -source design to respond quickly and dependably to a broad range of fires • Integral communications and built-in device -type identification • Built-in tamper resistant feature • Remote test feature from the panel • Walk test with address display (an address on 121 will blink th detector LED: 12-[pause]-1(LiteSpeed systems only) • Built-in functional test switch activated by external magnet • Removable cover and insect -resistant screen for simple field cleaning • Expanded color options OPERATION: • Designed to meet UL 268 7th Edition (a FIre•LITe AL8rms by Honeywell Plugs into separate base for ease of installation and maintenance Separate base allows interchange of photoelectric, ionization and thermal sensors OPTIONS: • Optional relay, isolator, and sounder bases Installation SD365 Series plug-in intelligent smoke detectors use a detachable base to simplify installation, service and maintenance. Installation instructions are shipped with each detector. Mount detector base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF-60059. NOTE: Because of the inherent supervision provided by the SLC loop, end -of -line resistors are not required. Wiring "T-taps" or branches are permitted for Style 4 (Class "B) wiring only. When using relay or sounder bases, consult the 1300(A) installation sheet 156-3626 for device limitations between isolator modules and iso- lator bases. e Construction • Factory preset at 1.5% nominal sensitivity for panel alarm thresh- old level • LED "blinks" when the unit is polled (communicating with the fire panel) and latches in alarm. • Low standby current MECHAN/CALS: • Sealed against back pressure • SEMS screws for wiring of the separate base • Designed for direct -surface or electrical -box mounting These detectors are constructed of fire-resistant plastic. The SD365 Series plug-in intelligent smoke detectors are designed to commer- cial standards and offer an attractive appearance. Operation Each SD365 Series detector uses one of the panel's addresses (total limit is panel dependent) on the Fire-Lite Signaling Line Circuit (SLC). It responds to regular polls from the control panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The SD365 Series offers features and performance that represent the latest in smoke detector technology. Detector Sensitivity Test Each detector can have its sensitivity tested (required per NFPA 72, Chapter 14 on Inspection, Testing and Maintenance) when installed/ connected to an Fire-Lite addressable fire alarm control panel. The results of the sensitivity test can be printed for record keeping. DF-61010:8 -7112019— Pagel of 3 Product Line information NOTE: "-IV" suffix indicates CLIP and LiteSpeed device. NOTE: A" suffix indicates Canadian version. SD365: White, low -profile intelligent photoelectric sensor, LiteSpeed only SD365A: Same as SD365 but with ULC listing SD365-IV: Ivory, low -profile intelligent photoelectric sensor SD365A-IV: Same as SD365-IV but with ULC listing SD365T: White, same as SD365 but includes a built-in 135°F (57'C) fixed -temperature thermal device, LiteSpeed only SD365TA: Same as SD365T but with ULC listing SD365T4V: Ivory, same as SD365T but includes a built-in 135°F (57°C) fixed -temperature thermal device SD365TA-IV: Same as SD365T-IV but with ULC listing SD365R: White, low -profile intelligent photoelectric sensor, remote test capable, for use with DNR/DNRW, LiteSpeed only SD365RA: Same as SD365R but with ULC listing, for use with DNRA SD365R-IV: Ivory, low -profile intelligent photoelectric sensor, remote test capable, for use with DNR/DNRW SD365RA-IV: Same as SD365R-IV but with ULC listing, for use with DNRA INTELLIGENT BASES NOTE: For details on intelligent bases, see DF-60059. B300-6: White, 6" base, standard flanged low -profile mounting base (CSFM: 7300-1653:0109) B300-6-IV: Ivory,6" base, standard flanged low -profile mounting base (CSFM: 7300-1653:0109) B300A-6: Same as B300-6, ULC listed B30OA-6-IV: Ivory, 6" standard flanged low -profile mounting base, ULC listed B300-6-BP: Bulk pack of B300-6, package contains 10 B501-WHITE: White, 4" standard European flangeless mounting base. UUULC listed (CSFM: 7300-1653:0109) B501-BL: Black, 4" standard European flangeless mounting base. UUULC listed (CSFM: 7300.1653:0109) B200SA-WH: Same as B200S-WH, ULC listing B200SA-IV: Same as B200S-IV, ULC listing B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications, ULC listing B200S-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) B20OS-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653:0238) B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213) B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM. 7300-1653:0213) B200SRA-WH: Same as B200SR-WH with, ULC listing B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. (CSFM: 7300-1653:0238) B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. (CSFM: 7300-1653:0238) MOUNTING KITS AND ACCESSORIES TR300: White, replacement flange for B210LP(A) base TR300-IV: Ivory, replacement flange for B210LP(A) base RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single -gang electrical box. For use with B501(A) and B300-6(A). M02-04-00: Test magnet B5014V: Ivory color, 4" standard European flangeless mounting M02-09.00: Test magnet with telescoping handle base. UVULC listed (CSFM: 7300.1653:0109) B501-WHITE-BP: Bulk pack of B501-WHITE contains 10 B224RB-WH: White, relay base (CSFM: 7300-1653:0216) B224RB-IV: Ivory, relay base (CSFM: 7300-1653:0216) B224RBA-WH: White, relay base, ULC listing B224RBA-IV: Ivory, relay base, ULC listing B224BI-WH: White, isolator detector base (CSFM: 7300-1653:0216) B224BI-IV: Ivory isolator detector base (CSFM: 7300-1653:0216) B224BIA-WH: White, isolator detector base, ULC listing B224BIA-IV: Ivory isolator detector base, ULC listing B20OS-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. (CSFM. 7300-1653:0213) B20OS-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. (CSFM: 7300-1653:0213) Page 2 of 3— DF-61010:B • 71I2019 CK300: Color Kit (includes cover and trim ring), white, 10-pack CK3004V: Color Kit (includes cover and trim ring), ivory, 10-pack CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack SYSTEM SPECIFICATIONS Sensitivity: • UL Applications: 0.5% to 4.0% per foot obscuration. • ULC Applications: 0.5% to 3.5% per foot obscuration Size: 2.0" (5.3 cm) high; base determines diameter — B300.6: 6.1" It 5.6 cm) diameter — B501: 4" (10.2 cm) diameter For a complete list of detector bases see DF-60983 Shipping weight: 3.4 oz. (95 g) Operating temperature range: • SD365: 32°F to 122°F (0°C to 50'C) • SD365T Series: 32'F to 100°F(0°C to 38°C) • SD365R Series installed in a DNR/DNRW, -4°F to 158°F (-20°C to 70-C) UUULC Listed Velocity Range: 0-4000 ft/min. (1219.2 m/min.), suitable for installation in ducts Relative humidity: 10%-93% non -condensing Thermal ratings: fixed -temperature set point 135OF (57°C), rate -of - rise detection 15'F (8.3•C) per minute, high temperature heat 190•F (88•C) ELECTRICAL SPECIFICATIONS Voltage range: 15 - 32 volts DC peak Standby current (max. avg.): 200pA @ 24 VDC (one communica- tion every 5 seconds with LED enabled) Max current: 4.5 mA@ 24 VDC ('ON") _ DETECTOR SPACING AND APPLICATIONS Fire-Lite recommends spacing detectors in compliance with NFPA 72. In low airflow applications with smooth ceiling, space detectors 30 feet (9.1m). For specific information regarding detector spacing, placement, and special applications refer to NFPA 72. A System Smoke Detector Application Guide, document A05-1003, is avail- able at www.systemsensor.com. Listings and Approvals Listings and approvals below apply to the SD365 Series detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. • UUULC Listing: S1059 • FMApproved • CSFM: 7272-0075:0502 LileSpeecl " is a trademark, and Fire -Lice® Alarms and System Sensor® are registered trademarks of Honeywell International Inc. 02019 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited. This document is not intended to be used for installation purposes. Iw O woo \V 9 We try to keep our product information up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. MUMUINL S MRUULRMNL QUALITY SYSTEMS For more information, contact Fire•Lite Alarms.Phone:(800)627-3473, FAX:(877)699Al05. Country of origin: Mexico www.firelde.com Page 3 of 3 — DF-61010:6 - 71/2019 DF-61011'.0 H365 Series Addressable Heat Detectors (a FirelITe ALaf ms by Honeywell Addressable Devices The Fire-Lite® Alarms H365(A), H365R(A), and H365HT(A) addressable plug-in thermal detectors are designed for both perfor- mance and aesthetics and are a direct replacement for the H355 Series. A new modern, sleek, contemporary design and advanced thermal technologies make the H365(A) Series ideal for both system operation and building design. Exclusively for use with Fire-Lite's addressable fire alarm control panels, the H365(A) Series point ID capability allows each detector's address to be set with rotary, decimal address switches, providing exact detector location for emergency personnel to quickly locate a fire during its early stages, potentially saving precious rescue time while also reducing property damage. Two LEDs on each sensor light to provide a local, visible sensor indication. The H365(A) Series includes fixed temperature, rate -of -rise and high heat fixed temperature detectors that provide effective, intelli- gent property protection for a variety of applications. Detectors are available for both LiteSpeedT and CLIP applications as designated. Features SLC LOOP: • Two -wire SLC loop connection • Unit uses base for wiring ADDRESSING: • Addressable by device • Rotary, decimal addressing (Refer to the Fire-Lite panel manuals for device capacity.) ARCHITECTURE: • Designed to meet UL 268 7th Edition • Sleek, low -profile, stylish design • State-of-the-art thermistor technology for fast response • Integral communications and built-in device -type identification • Built-in tamper resistant feature • Built-in functional test switch activated by external magnet OPERATION: • Fixed temperature model (H365(A)) factory preset to 135'17 (57°C) • Rate -of -rise model (H365R(A)), 15•F (8.3•C) per minute • High -temperature model (H365HT(A)) factory preset to 190°F (88•C) • 360•-field viewing angle of the two visual alarm indicators, LEDs blink red in Normal condition and turn on steady red in Alarm • LEDs blink every time the unit is polled MECHAN/CALS: • Sealed against back pressure SEMS screws for wiring of the separate base Designed for direct -surface or electrical -box mounting Plugs into separate base for ease of installation and maintenance Separate base allows interchange of photoelectric, ionization and thermal sensors OTHER SYSTEM FEATURES: • Remote test feature from the panel • Walk test with address display • Low standby current OPTIONS: • Remote LED output connection to optional RA10OZ remote LED annunciator Installation H365 Series plug-in intelligent thermal detectors use a detachable base to simplify installation, service and maintenance. Installation instructions are shipped with each detector. Mount detector base (all base types) on an electrical backbox which is at least 1.5" (3.81 cm) deep. For a chart of compatible junction boxes, see DF-60059. NOTE: Because of the inherent supervision provided by the SLC loop, end -of -line resistors are not required. tiring "Traps" or branches are permitted for Style 4 (Class "B) wiring only. Men using relay or sounder bases, consult the 1300(A) installation sheet 156-3626 for device limitations between isolator modules and iso- lator bases. Applications Use thermal detectors for protection of property. For further informa- tion, refer to 156-6525, Applications Manual for System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Construction These detectors are constructed of fire-resistant plastic. The H365 Series plug-in intelligent thermal detectors are designed to commer- cial standards and offer an attractive appearance. Operation Each H365 Series detector uses one of the panel's addresses (total limit is panel dependent) on the Fire•LiteJCI Signaling Line Circuit (SLC). It responds to regular polls from the control panel and reports its type and the status. If it receives a test command from the panel (or a local magnet test), it stimulates its electronics and reports an alarm. It blinks its LEDs when polled and turns the LEDs on when commanded by the panel. The H365 Series offers features and per- formance that represent the latest in thermal detector technology. DF-61011:C • 11/16/2019 — Pagel of 3 Product Line Information NOTE: "-IV" suffix indicates CLIP and LiteSpeed device. NOTE: A"suffx indicates Canadian version. H365: White, low -profile intelligent 135°F fixed thermal sensor, Lite- Speed only H365A: Same as H365 but with ULC listing H365-IV: Ivory, low -profile intelligent 135°F fixed thermal sensor, LiteSpeed and CLIP H365A-IV: Same as H365-IV but with ULC listing H365R: White, low -profile intelligent rate -of -rise thermal sensor, LiteSpeed only H366RA: Same as H365R but with ULC listing H365R-IV: Ivory, low -profile intelligent rate -of -rise fixed thermal sen- sor, LiteSpeed and CLIP H365RA-IV: Same as H365R-IV but with ULC listing H365HT: White, low -profile intelligent 190°F fixed thermal sensor, LiteSpeed only H365HTA: Same as H365H but with ULC listing H365HT4V: Ivory, low -profile intelligent 190°F thermal sensor, Lite- Speed and CLIP H365HTA-IV Same as H365H-IV butwith ULC listing INTELLIGENT BASES NOTE: For details on intelligent bases, see DF-60059. B300-6: White, 6" base, standard flanged low -profile mounting base (CSFM: 7300-1653:0109) B300.6-IV: Ivory,6" base, standard flanged low -profile mounting base (CSFM: 7300-1653:0109) 6300A-6: Same as B300-6, ULC listed B300A-6-IV: Ivory, 6" standard flanged low -profile mounting base, ULC listed B300-6-BP: Bulk pack of B300-6, package contains 10 B501-WHITE: White, 4" standard European flangeless mounting base. UUULC listed (CSFM: 7300-1653.,0109) 135011-BL: Black, 4" standard European flangeless mounting base. UUULC listed (CSFM.7300-1653:0109) B501-IV: Ivory color, 4" standard European flangeless mounting base. UUULC listed (CSFM: 7300-1653:0109) B601-WHITE-BP: Bulk pack of B501-WHITE contains 10 B224RB-WH: White, relay base (CSFM: 7300-1653:0216) B224RB-IV: Ivory, relay base (CSFM: 7300-1653:0216) B224RBA-WH: White, relay base, ULC listing B224RBA-IV: Ivory, relay base, ULC listing B224BI-WH: White, isolator detector base (CSFM: 7300-1653:0216) B224BI-IV: Ivory isolator detector base (CSFM: 7300-1653:0216) B224SIA-WH: White, isolator detector base, ULC listing B224BIA-IV: Ivory isolator detector base, ULC listing B20OS-WH: White, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. (CSFM: 7300-1653:0213) B20OS-IV: Ivory, Intelligent addressable sounder base capable of producing sound output in high or low volume with ANSI Temporal 3, ANSI Temporal 4, continuous tone, marching tone, and custom tone. Uses FlashScan protocol. (CSFM. 7300-1653:0213) B200SA-WH: Same as B2003-WH, ULC listing Page 2 of 3 — DF-61011:C - 11/18/2019 B200SA-IV: Same as B200S-IV, ULC listing B200SCOA-WH: White, Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications B200SCOA-IV: Ivory Intelligent, programmable sounder base in English/French (required in Canada for ULC applications with CO Series detector applications, ULC listing B20OS-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. (CSFM: 7300-1653.0238) B20OS-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA72 sleeping space requirement. (CSFM: 7300-1653.,0238) B200SR-WH: White, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213) B200SR-IV: Ivory, Intelligent sounder base capable of producing sound output with ANSI Temporal 3 or continuous tone. Intended for retrofit applications. (CSFM: 7300-1653:0213) B200SRA-WH: Same as B200SR-WH with, ULC listing B200SRA-IV: Same as B200SR-IV in Ivory color, ULC listing B200SR-LF-WH: White, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. (CSFM: 7300-1653:0238) B200SR-LF-IV: Ivory, Low Frequency Intelligent, programmable sounder base. Produces a fundamental frequency of 520 Hz +/- 10% with a square wave or its equivalent; designed to meet the NFPA 72 sleeping space requirement. Intended for retrofit applica- tions. (CSFM: 7300-1653:0238) MOUNTING KITS AND ACCESSORIES TR300: White, replacement flange for B210LP(A) base TR300-IV: Ivory, replacement flange for B210LP(A) base RA100Z(A): Remote LED annunciator. 3-32 VDC. Mounts to a U.S. single -gang electrical box. For use with B501(A) and B300-6(A). M02-04-00: Test magnet M02-09-00: Test magnet with telescoping handle CK300: Color Kit (includes cover and trim ring), white, 10-pack CK300-IV: Color Kit (includes cover and trim ring), ivory, 10-pack CK300-BL: Color Kit (includes cover and trim ring), black, 10-pack