Loading...
Weis - Stamped Plan Set 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 VICINITY MAP AERIAL MAP PV-1 REV #1: REV #2: REV #3: DATE: 9/8/2023 DRAWN BY: LV COVER PAGE WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 WEIS RESIDENCE PHOTOVOLTAIC SYSTEM 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON PV-1 - COVER PAGE PV-2 - PROPERTY PLAN PV-3 - SITE PLAN PV-3.1 - ROOF PLAN PV-4 - 1-LINE DIAGRAM & CALCULATIONS PV-4.1 - 3-LINE DIAGRAM & CALCULATIONS PV-5 - MOUNTING DETAILS AND BOM PV-6 - ELECTRICAL LABELS & ELEVATION PV-7 - STRING MAP PV-8 - DATASHEETS PV-9 - PLACARD SHEET INDEX: GOVERNING CODES ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL COMPLY WITH THE FOLLOWING APPLICABLE CODES: x x x x x x xWHERE APPLICABLE, RULES OF THE PUBLIC UTILITIES COMMISSION REGARDING SAFETY AND RELIABILITY xTHE AUTHORITY HAVING JURISDICTION xMANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS xANY OTHER LOCAL AMENDMENTS 2023 NATIONAL ELECTRICAL CODE 2015 INTERNATIONAL BUILDING CODE 2015 INTERNATIONAL RESIDENTIAL CODE 2021 INTERNATIONAL PLUMBING CODE 2021 INTERNATIONAL FIRE CODE 2021 INTERNATIONAL MECHANICAL CODE GENERAL 1. UTILITY SHALL BE NOTIFIED BEFORE ACTIVATION OF PHOTOVOLTAIC SYSTEM. 2. 110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION 3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO INITIATING CONSTRUCTION. 4. CONTRACTOR SHALL REVIEW ALL MANUFACTURER INSTALLATION DOCUMENTS PRIOR TO INITIATING CONSTRUCTION. 5. ALL EQUIPMENT AND ASSOCIATED CONNECTIONS, ETC, AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE INSTALLED ONLY BY QUALIFIED PERSONNEL. 6. THE CONTRACTOR OR OWNER MUST PROVIDE ROOF ACCESS (LADDER TO ROOF) FOR ALL THE REQUIRED INSPECTIONS. LADDERS MUST BE OSHA APPROVED, MINIMUM TYPE I WITH A 250LB. RATING, IN GOOD CONDITION AND DESIGNED FOR ITS INTENDED USE. 7. CONTRACTOR SHALL VERIFY THAT THE ROOF STRUCTURE WILL WITHSTAND THE ADDITIONAL LOADS. 8. LAG SCREWS SHALL PENETRATE A MINIMUM 2" INTO SOLID SAWN STRUCTURAL MEMBERS AND SHALL NOT EXCEED MANUFACTURER RECOMMENDATIONS FOR FASTENERS INTO ENGINEERED STRUCTURAL MEMBERS. 9. AN ACCESS POINT SHALL BE PROVIDED THAT DOES NOT PLACE THE GROUND LADDER OVER OPENINGS SUCH AS WINDOWS OR DOORS ARE LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION AND IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES, OR SIGNS. 10. WHERE DC CONDUCTORS ARE RUN INSIDE BUILDING, THEY SHALL BE CONTAINED IN A METAL RACEWAY; THEY SHALL NOT BE INSTALLED WITHIN 10" OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE COVERED BY THE PV MODULES AND EQUIPMENT. 11. PLUMBING AND MECHANICAL VENTS THROUGH THE ROOF SHALL NOT BE COVERED BY SOLAR MODULES- - NO BUILDING, PLUMBING OR MECHANICAL VENTS TO BE COVERED, CONSTRUCTED OR ROUTED AROUND SOLAR MODULES. 12. ALL FIELD -INSTALLED JUNCTION, PULL AND OUTLET BOXES LOCATED BEHIND MODULES SHALL BE ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF A MODULE SECURED BY REMOVABLE FASTENERS. ELECTRICAL 1. WIRING MATERIALS SHALL COMPLY WITH MAXIMUM CONTINUOUS CURRENT OUTPUT AT 25°C AND MAXIMUM VOLTAGE AT 600V; WIRE SHALL BE WET RATED AT 90°C. 2. EXPOSED PHOTOVOLTAIC SYSTEM CONDUCTORS ON THE ROOF WILL BE USE 2 OR PV-TYPE WIRE. 3. PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED. THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATE COLOR-CODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS. 4. ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN-TIGHT AND APPROVED FOR USE IN WET LOCATIONS. 5. ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS. 6. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, CONTRACTOR SHALL SIZE THEM ACCORDING TO APPLICABLE CODES. 7. REMOVAL OF A UTILITY-INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BUILDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PV SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR. 8. FOR GROUNDED SYSTEMS, THE PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS SHALL BE PROVIDED WITH A GROUND-FAULT PROTECTION DEVICE OR SYSTEM THAT DETECTS A GROUND FAULT, INDICATES THAT FAULT HAS OCCURED AND AUTOMATICALLY DISCONNECTS ALL CONDUCTORS OR CAUSES THE INVERTER TO AUTOMATICALLY CEASE SUPPLYING POWER TO OUTPUT CIRCUITS. 9. FOR UNGROUNDED SYSTEMS, THE INVERTER IS EQUIPPED WITH GROUND FAULT PROTECTION AND A GFI FUSE PORT FOR GROUND FAULT INDICATION. 10. PV MODULE FRAMES SHALL BE BONDED TO RACKING RAIL OR BARE COPPER GEC/GEC PER THE MODULE MANUFACTURER'S LISTED INSTRUCTION SHEET. 11. PV MODULE RACKING RAIL SHALL BE BONDED TO BARE COPPER GEC VIA WEEB LUG, ILSCO GBL-4DBT LAY-IN LUG, OR EQUIVALENT LISTED LUG. 12. THE PHOTOVOLTAIC INVERTER WILL BE LISTED AS UL 1741 COMPLIANT. 13. RACKING AND BONDING SYSTEM TO BE UL2703 RATED. 14. ANY REQUIRED GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AS BUS BARS WITHIN LISTED EQUIPMENT. 15. WHEN BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THE BREAKERS SHALL NOT READ "LINE AND LOAD". 16. WHEN APPLYING THE 120% RULE, THE SOLAR BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. 17. THE WORKING CLEARANCE AROUND THE EXISTING ELECTRICAL EQUIPMENT AS WELL AS THE NEW ELECTRICAL EQUIPMENT WILL BE MAINTAINED. x SYSTEM SIZE: 6.32 kW-DC | 5.0 kW-AC MODULE: (16) CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] OPTIMIZER: (16) SOLAREDGE S440 INVERTER: (1) SOLAREDGE SE5000H-US [240V] 780 CMR 51 MASSACHUSETTS RESIDENTIAL CODE 9TH EDITION ADOPTED 10/20/2017. TABLE R301.2(4) SNOW LOADS AND WIND SPEEDS 9-11-2023 N 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 LEGEND: PROPERTY LINE: DATE: 9/8/2023 DRAWN BY: LV PROPERTY PLAN PV-2 DRIVEWAY: WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON SCALE: 1/16" = 1'-0" APN: 22B-057-001 PROPERTY LINE DETACHED STRUCTURE D R I V E W A Y --- S P R I N G S T . - - - 93'-6" 82'-11" 136'-10" 137'-9"MAIN HOME17'-6" 15' 44'-10" 68'-1" FENCE CHIMNEY FENCE: 9-11-2023 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 N SYSTEM LEGEND UM MP MAIN SERVICE METER AND SERVICE POINT MAIN SERVICE PANEL SCALE: 1/8" = 1'-0" CONDUIT TO BE RUN IN ATTIC IF POSSIBLE, OTHERWISE CONDUIT BLOCKS MIN. 1"/MAX 6" ABOVE ROOF SURFACE, CLOSE TO RIDGE LINES, AND UNDER EAVES; TO BE PAINTED TO MATCH EXTERIOR/EXISTING BACKGROUND COLOR OF ITS LOCATION; TO BE LABELED AT MAX 10' INTERVALS. CONDUIT RUNS ARE APPROXIMATE AND ARE TO BE DETERMINED IN THE BY THE INSTALLERS CONDUIT RUN FIRE CODE SETBACK (18"MIN./ 36" MAX.) (16) CANADIAN SOLAR HiKu6 MONO PERC CS6R-395MS [395W] WITH (16) SOLAREDGE S440 POWER OPTIMIZERS MOUNTED UNDER EACH MODULE ROOF SECTION 1: 6 MODULES AZIMUTH: 133° PITCH: 35° ROOF TYPE: ASPHALT SHINGLE ROOF SECTION 2: 5 MODULES AZIMUTH: 134° PITCH: 29° ROOF SECTION 3: 5 MODULES AZIMUTH: 134° PITCH: 18° ROOF DETAIL 1 2 3 DATE: 9/8/2023 DRAWN BY: LV SITE PLAN PV-3 JUNCTION BOX AND CONDUIT WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON I (1) SOLAREDGE SE5000H-US [240V] INVERTER WITH INTEGRATED DC DISCONNECT PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 6.32 kW AC SYSTEM SIZE: 5.00 kW AC UTILITY AC DISCONNECT UM1IMDMPAC MD MAIN SERVICE DISCONNECT 2 3 3' 3' 3' 9-11-2023 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 N SYSTEM LEGEND ELEVATION DETAIL FIRE CODE SETBACK (18" MIN./ 36" MAX.) ROOF SECTION 1: 6 MODULES AZIMUTH: 133° PITCH: 35° ROOF TYPE: ASPHALT SHINGLE ROOF SECTION 2: 5 MODULES AZIMUTH: 134° PITCH: 29° ROOF SECTION 3: 5 MODULES AZIMUTH: 134° PITCH: 18° ROOF DETAIL 1 2 3 ROOF ATTACHMENT POINT DATE: 9/8/2023 DRAWN BY: LV ROOF PLAN PV-3.1 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 ROOF FRAMING (RAFTERS/TRUSS) RACKING AHJ: CITY OF NORTHAMPTON MODULE MECHANICAL SPECIFICATIONS DESIGN WIND SPEED 117 MPH DESIGN SNOW LOAD 40 PSF # OF STORIES 1 ROOF PITCH 35°, 29°, 18° TOTAL ARRAY AREA (SQ. FT)335.84 TOTAL ROOF AREA (SQ. FT)1474 ARRAY SQ. FT / TOTAL ROOF SQ. FT 22.78% 1 SCALE: 1/8" = 1'-0" 2 ASPHALT SHINGLE RAFTERS@24" O.C.2"X6": 2"X6" STRUCTURAL ATTACHMENT MODULE 3 22'-9"18'-11" 28'-7" 4' (TYP.) 3' 3' 3' 9-11-2023 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 6.32 kW AC SYSTEM SIZE: 5.00 kW INVERTER: (1) SOLAREDGE SE5000H-US [240V] MODULE: (16) CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] NOTES: 1. MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS IF APPLICABLE 2. PV DC SYSTEM IS UNGROUNDED 3. PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH NEC 250.58 AND 690.47(A) 4. PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS SHALL COMPLY WITH NEC 690.1(G) 5. BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, PAGE 6. BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP; WHEN PRESENT, THE GEC TO BE CONTINUOUS 7. INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A 8. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS 9. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY FIELD CONDITIONS. OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS INVERTER TYPE SOLAREDGE 5000H-US # OF INVERTERS 1 MAX CONTINUOUS OUTPUT CURRENT 21A (# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <= OCPD RATING (1 x 21A x 1.25)= 26.25A <= 30A, OK DATE: 9/8/2023 DRAWN BY: LV 1-LINE DIAGRAM & CALCULATIONS PV-4 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON PV MODULE ELECTRICAL SPECIFICATIONS MODULE TYPE CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] POWER MAX (PMAX) 395W OPEN CIRCUIT VOLTAGE (VOC) 36.6V SHORT CIRCUIT CURRENT (ISC)13.77A MAX POWER-POINT VOLTAGE (VMP) 30.6V MAX POWER-POINT CURRENT (IMP)12.91A SERIES FUSE RATING 25A POWER OPTIMIZER ELECTRICAL SPECIFICATIONS OPTIMIZER TYPE SOLAREDGE S440 RATED INPUT DC POWER 440W MAXIMUM INPUT VOLTAGE (VOC) 60V MAXIMUM SHORT CIRCUIT CURRENT (ISC) 14.5A MAXIMUM OUTPUT CURRENT 15A MAXIMUM OUTPUT VOLTAGE 60V MINIMUM STRING LENGTH 8 MAXIMUM POWER PER STRING 5700W CONDUCTOR AND CONDUIT SCHEDULE TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE 1 PV WIRE #10 4 - L1 L2 FREE AIR N/A 1 BARE COPPER #6 1 - BARE FREE AIR N/A 2 THWN-2 #10 4 - L1 L2 EMT 3/4" 2 THWN-2 EGC #10 1 - GND EMT 3/4" 3 THWN-2 #10 3 - L1 L2 N EMT 3/4" 3 THWN-2 EGC #10 1 - GND EMT 3/4" 4 THWN-2 #10 3 - L1 L2 N EMT 3/4" 4 THWN-2 EGC #10 1 - GND EMT 3/4" INVERTER ELECTRICAL SPECIFICATIONS INVERTER TYPE SOLAREDGE SE5000H-US MAX INPUT DC VOLTAGE 480V MAX INPUT CURRENT 13.5A NOMINAL DC INPUT VOLTAGE 380V MAXIMUM OUTPUT POWER 5000H NOMINAL AC OUTPUT VOLTAGE 240V MAXIMUM CONT. OUTPUT CURRENT 21A CEC EFFICIENCY 99% STRING 1: 8 MODULES - CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] = = = = = = = = = = = = 7 STRING 2: 8 MODULES - CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] 7 NEMA3R RATED JUNCTION BOX: SHALL COMPLY W/ NEC 110.3 & 314.6 SOLAREDGE S440 OPTIMIZER UTILITY INTERACTIVE SINGLE PHASE INVERTER SOLAREDGE SE5000H-US [240V] INTEGRATED DC DISCONNECT UL1741 CERTIFIED 1 1 (N) PV OCPD 2P - 30A (E) LOADS (E) 200A MAIN DISCONNECT UTILITY SERVICE 120/240V SINGLE PHASE (E) 200A RATED MAIN SERVICE PANEL FACILITY GROUND (E) GROUND ROD L1 G N-G NOTE: ALL DC CONNECTOR TO MODULES OR INVERTERS MUST BE OF MATCHING MANUFACTURING BRAND AND STYLE. DO NOT USE 'COMPATIBLE' CONNECTORS WHICH HAVE NOT BEEN UL TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE MAY RESULT FROM MISMATCHED CONNECTOR USEAGE. (N) AC DISCONNECT 240V30A NEMA 3R FUSIBLE W/ 30A FUSES, VISIBLE-LOCKABLE LABELED BUSBAR CALCULATIONS - PV BREAKER - 120% RULE MAIN BUS RATING 200 MAIN DISCONNECT RATING 200 PV BREAKER RATING 30 (MAIN BUS RATING x 1.2) - MAIN DISCONNECT RATING >= OCPD RATING (200A x 1.2) - 200A >= 30A, OK 9-11-2023 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 3-LINE DIAGRAM & CALCULATIONS PV-4.1 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 NOTES: 1. MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS IF APPLICABLE 2. PV DC SYSTEM IS UNGROUNDED 3. PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH NEC 250.58 AND 690.47(A) 4. PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS SHALL COMPLY WITH NEC 690.1(G) 5. BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, PAGE 6. BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP; WHEN PRESENT, THE GEC TO BE CONTINUOUS 7. INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A 8. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS 9. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY FIELD CONDITIONS. AHJ: CITY OF NORTHAMPTON PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 6.32 kW AC SYSTEM SIZE: 5.00 kW INVERTER: (1) SOLAREDGE SE5000H-US [240V] MODULE: (16) CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] NOTE: ALL DC CONNECTOR TO MODULES OR INVERTERS MUST BE OF MATCHING MANUFACTURING BRAND AND STYLE. DO NOT USE 'COMPATIBLE' CONNECTORS WHICH HAVE NOT BEEN UL TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE MAY RESULT FROM MISMATCHED CONNECTOR USAGE. DATE: 9/8/2023 DRAWN BY: LV OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS INVERTER TYPE SOLAREDGE 5000H-US # OF INVERTERS 1 MAX CONTINUOUS OUTPUT CURRENT 21A (# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <= OCPD RATING (1 x 21A x 1.25)= 26.25A <= 30A, OK PV MODULE ELECTRICAL SPECIFICATIONS MODULE TYPE CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] POWER MAX (PMAX) 395W OPEN CIRCUIT VOLTAGE (VOC) 36.6V SHORT CIRCUIT CURRENT (ISC)13.77A MAX POWER-POINT VOLTAGE (VMP) 30.6V MAX POWER-POINT CURRENT (IMP)12.91A SERIES FUSE RATING 25A INVERTER ELECTRICAL SPECIFICATIONS INVERTER TYPE SOLAREDGE SE5000H-US MAX INPUT DC VOLTAGE 480V MAX INPUT CURRENT 13.5A NOMINAL DC INPUT VOLTAGE 380V MAXIMUM OUTPUT POWER 5000H NOMINAL AC OUTPUT VOLTAGE 240V MAXIMUM CONT. OUTPUT CURRENT 21A CEC EFFICIENCY 99% CONDUCTOR AND CONDUIT SCHEDULE TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE 1 PV WIRE #10 4 - L1 L2 FREE AIR N/A 1 BARE COPPER #6 1 - BARE FREE AIR N/A 2 THWN-2 #10 4 - L1 L2 EMT 3/4" 2 THWN-2 EGC #10 1 - GND EMT 3/4" 3 THWN-2 #10 3 - L1 L2 N EMT 3/4" 3 THWN-2 EGC #10 1 - GND EMT 3/4" 4 THWN-2 #10 3 - L1 L2 N EMT 3/4" 4 THWN-2 EGC #10 1 - GND EMT 3/4" POWER OPTIMIZER ELECTRICAL SPECIFICATIONS OPTIMIZER TYPE SOLAREDGE S440 RATED INPUT DC POWER 440W MAXIMUM INPUT VOLTAGE (VOC) 60V MAXIMUM SHORT CIRCUIT CURRENT (ISC) 14.5A MAXIMUM OUTPUT CURRENT 15A MAXIMUM OUTPUT VOLTAGE 60V MINIMUM STRING LENGTH 8 MAXIMUM POWER PER STRING 5700W STRING 1: 8 MODULES - CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] = = = = = = = = = = = = 7 STRING 2: 8 MODULES - CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W] 7 NEMA3R RATED JUNCTION BOX: SHALL COMPLY W/ NEC 110.3 & 314.6 SOLAREDGE S440 OPTIMIZER UTILITY INTERACTIVE SINGLE PHASE INVERTER SOLAREDGE SE5000H-US [240V] INTEGRATED DC DISCONNECT UL1741 CERTIFIED (N) AC DISCONNECT 240V/30A NEMA 3R FUSIBLE W/ 30A FUSES, VISIBLE-LOCKABLE LABELED (N) PV OCPD 2P - 30A (E) LOADS (E) 200A MAIN DISCONNECT UTILITY SERVICE 120/240V SINGLE PHASE (E) 200A RATED MAIN SERVICE PANEL FACILITY GROUND (E) GROUND ROD L2 L1 N G N-G BUSBAR CALCULATIONS - PV BREAKER - 120% RULE MAIN BUS RATING 200 MAIN DISCONNECT RATING 200 PV BREAKER RATING 30 (MAIN BUS RATING x 1.2) - MAIN DISCONNECT RATING >= OCPD RATING (200A x 1.2) - 200A >= 30A, OK 9-11-2023 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 PV MODULE FRAME IRONRIDGE AIRE A1 RAIL DETAIL, END CLAMP (UFO) FRONT IRONRIDGE STOPPER SLEEVEIRONRIDGE UNIVERSAL FASTENING OBJECTPV MODULE FRAME IRONRIDGE AIRE A1 RAIL DETAIL, END CLAMP (UFO) PLAN IRONRIDGE STOPPER SLEEVE IRONRIDGE UNIVERSAL FASTENING OBJECT PV MODULE FRAME IRONRIDGE AIRE A1 RAIL DETAIL, MID CLAMP FRONT IRONRIDGE UNIVERSAL FASTENING OBJECTPV MODULE FRAME DETAIL, MID CLAMP PLAN IRONRIDGE UNIVERSAL FASTENING OBJECT IRONRIDGE AIRE A1 RAIL IRONRIDGE FLASHFOOT-2 IRONRIDGE AIRE A1 RAIL PV MODULE IRONRIDGE STOPPER SLEEVE IRONRIDGE UNIVERSAL FASTENING OBJECT IRONRIDGE FLASHFOOT2IRONRIDGE UNIVERSAL FASTENING OBJECT 1.0000 PV-5 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 MOUNTING DETAILS AND BOM ATTACHMENT TYPE: IRONRIDGE FLASHFOOT2 WITH IRONRIDGE AIRE A1 RAIL ROOF TYPE: ASPHALT SHINGLE ,ROOF TILT: 35°, 29°, 18° MODULE WEIGHT: 47 LBS MODULE DIMENSIONS: 5.65' X 3.72' MODULE WEIGHT/ SQ. FOOT: 2.24 LBS TOTAL NO. OF MODULES: 16 TOTAL MODULE WEIGHT: 752.0 LBS ATTACHMENT DETAILS (N.T.S.) 1 AHJ: CITY OF NORTHAMPTON />>K&DdZ/> Yh/WDEd D<YhEd/dz DKh>E/E^K>Z,ŝ<ƵϲDKEKWZ^ϲZͲϯϵϱD^ ΀ϯϵϱt΁ ϭϲ /EsZdZ ^K>Z'^ϱϬϬϬ,Ͳh^΀ϮϰϬs΁ ϭ KWd/D/Z^^K>Z'^ϰϰϬKWd/D/Z ϭϲ E>DW^DKh>E>DW^dEZϭϮ D/>DW^DKh>D/>>DW^d^dEZ;/Ed'Zd 'ZKhE/E'Ϳ Ϯϲ DKhEd/E'WK/Ed^/ZKEZ/'&>^,&KKdϮ ϰϬ DKhEd/E'Z/>^/ZKEZ/'/Z/Z/> ϭϭ hd/>/dz /^KEEd Ws^z^dDhd/>/dz/^KEEdϯϬZdt/d, ϯϬ&h^^ϭ DATE: 9/8/2023 DRAWN BY: LV 9-11-2023 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 PV-6 LABELS ARE NOT DRAWN TO SCALE WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 ELECTRICAL LABELS & ELEVATION LABELING NOTES 1.1 LABELING REQUIREMENTS BASED ON THE 2023 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535] PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION [NEC 690.56(B)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS. PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN BATHROOMS [NEC 690.4(D),(E)] ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B) AHJ: CITY OF NORTHAMPTON ! WARNING ! DUAL POWER SOURCES. SECOND SOURCE IS PV SYSTEM LABEL 7 PHOTOVOLTAIC AC DISCONNECT OPERATING CURRENT: 21 A AC OPERATING VOLTAGE: 240 V AC LABEL 5 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS [NEC 690.54] ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. LABEL 3 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.13 AND 690.15] PHOTOVOLTAIC DC DISCONNECT UTILITY AC DISCONNECT LABEL 10 AT EACH DC DISCONNECTING MEANS [NEC 690.13(B)] LABEL 12 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)] LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 13 AT EACH AC DISCONNECTING MEANS [NEC 690.13(B)] ! CAUTION ! PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED ! WARNING ! POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVICE LABEL 14 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE [NEC 705.12(B)(2)(3)(B)] LABEL 9 AT UTILITY METER [NEC 690.56(B)] LABEL 4 AT EACH DC DISCONNECTING MEANS [NEC 690.53] LABEL 11 AT RAPID SHUTDOWN SWITCH [NEC 690.56(C)]. LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 8 AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 7 OR LABEL 8 MUST IDENTIFY PHOTOVOLTAIC SYSTEM [NEC 705.12(B)(4)] TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY LABEL 1 AT RAPID SHUTDOWN SYSTEM [NEC 690.56(C)(1)(A)]. ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPOSED TO SUNLIGHT LABEL 2 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.15] MAXIMUM VOLTAGE: 480 V DC MAXIMUM CIRCUIT CURRENT: 13.5 A DC MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED): 15 A DC LABEL 6 AT RAPID SHUTDOWN DISCONNECT SWITCH [NEC 690.56(C)(3)]. #03-359 LOCAL CODES BI-DIRECTIONAL METER WARNING: PHOTOVOLTAIC POWER SOURCE PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS WARNING THIS SERVICE METER IS ALSO SERVED BY A PHOTOVOLTAIC SYSTEM MAIN SERVICE PANEL FOR ILLUSTRATION ONLY (NOT ACTUAL MSP) INVERTERJUNCTION BOX (IF USED)4 7 8 92 2 2 1 611 14 3 3 TO SOLAR ARRAY UTILITY AC DISCONNECT 5 2 6 3 MAIN SERVICE METER DATE: 9/8/2023 DRAWN BY: LV9-11-2023 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 FOR INSTALLER USE ONLY STRING MAP PV-7 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING DETAIL SOLAREDGE STRINGS STRING # 1: 8 MODULES STRING DETAIL SOLAREDGE STRINGS DATE: 9/8/2023 DRAWN BY: LV STRING -1 STRING -2 STRING # 2: 8 MODULES 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 MODULE DATASHEET PV-8.1 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON DATE: 9/8/2023 DRAWN BY: LV 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 INVERTER DATASHEET PV-8.2 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON DATE: 9/8/2023 DRAWN BY: LV 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 OPTIMIZERS DATASHEET PV-8.3 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON DATE: 9/8/2023 DRAWN BY: LV 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 RACKING DATASHEET PV-8.4 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON DATE: 9/8/2023 DRAWN BY: LV 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102 ROOF ATTACHMENT DATASHEET PV-8.5 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 AHJ: CITY OF NORTHAMPTON DATE: 9/8/2023 DRAWN BY: LV 59C NORTH ST., HATFIELD MA 01038 TEL. NO.(413) 338-7555 INSIGHT SOLAR LIC. NO. HIC - MA 192102N DATE: 9/8/2023 DRAWN BY: LV PLACARD PV-9 WEIS, RICHARD 40 SPRING ST. FLORENCE, MA 01062 CAUTION POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN !! SERVICE 1 OF 1 40 SPRING ST.FLORENCE, MA 01062 UTILITY METER AHJ: CITY OF NORTHAMPTON UTILITY AC DISCONNECT MAIN SERVICE PANEL INVERTER SOLAR PV ARRAY