Weis - Stamped Plan Set 59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
VICINITY MAP
AERIAL MAP PV-1
REV #1:
REV #2:
REV #3:
DATE: 9/8/2023
DRAWN BY: LV
COVER PAGE
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
WEIS RESIDENCE
PHOTOVOLTAIC SYSTEM
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
PV-1 - COVER PAGE
PV-2 - PROPERTY PLAN
PV-3 - SITE PLAN
PV-3.1 - ROOF PLAN
PV-4 - 1-LINE DIAGRAM & CALCULATIONS
PV-4.1 - 3-LINE DIAGRAM & CALCULATIONS
PV-5 - MOUNTING DETAILS AND BOM
PV-6 - ELECTRICAL LABELS & ELEVATION
PV-7 - STRING MAP
PV-8 - DATASHEETS
PV-9 - PLACARD
SHEET INDEX:
GOVERNING CODES
ALL MATERIALS, EQUIPMENT, INSTALLATION AND
WORK SHALL COMPLY WITH THE FOLLOWING
APPLICABLE CODES:
x
x
x
x
x
x
xWHERE APPLICABLE, RULES OF THE PUBLIC
UTILITIES COMMISSION REGARDING SAFETY AND
RELIABILITY
xTHE AUTHORITY HAVING JURISDICTION
xMANUFACTURERS' LISTINGS AND INSTALLATION
INSTRUCTIONS
xANY OTHER LOCAL AMENDMENTS
2023 NATIONAL ELECTRICAL CODE
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL RESIDENTIAL CODE
2021 INTERNATIONAL PLUMBING CODE
2021 INTERNATIONAL FIRE CODE
2021 INTERNATIONAL MECHANICAL CODE
GENERAL
1. UTILITY SHALL BE NOTIFIED BEFORE ACTIVATION OF
PHOTOVOLTAIC SYSTEM.
2. 110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL
BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY
RECOGNIZED TESTING LABORATORY ACCREDITED BY
THE UNITED STATES OCCUPATIONAL SAFETY HEALTH
ADMINISTRATION
3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS
PRIOR TO INITIATING CONSTRUCTION.
4. CONTRACTOR SHALL REVIEW ALL MANUFACTURER
INSTALLATION DOCUMENTS PRIOR TO INITIATING
CONSTRUCTION.
5. ALL EQUIPMENT AND ASSOCIATED CONNECTIONS, ETC,
AND ALL ASSOCIATED WIRING AND
INTERCONNECTIONS SHALL BE INSTALLED ONLY BY
QUALIFIED PERSONNEL.
6. THE CONTRACTOR OR OWNER MUST PROVIDE ROOF
ACCESS (LADDER TO ROOF) FOR ALL THE REQUIRED
INSPECTIONS. LADDERS MUST BE OSHA APPROVED,
MINIMUM TYPE I WITH A 250LB. RATING, IN GOOD
CONDITION AND DESIGNED FOR ITS INTENDED USE.
7. CONTRACTOR SHALL VERIFY THAT THE ROOF
STRUCTURE WILL WITHSTAND THE ADDITIONAL LOADS.
8. LAG SCREWS SHALL PENETRATE A MINIMUM 2" INTO
SOLID SAWN STRUCTURAL MEMBERS AND SHALL NOT
EXCEED MANUFACTURER RECOMMENDATIONS FOR
FASTENERS INTO ENGINEERED STRUCTURAL
MEMBERS.
9. AN ACCESS POINT SHALL BE PROVIDED THAT DOES
NOT PLACE THE GROUND LADDER OVER OPENINGS
SUCH AS WINDOWS OR DOORS ARE LOCATED AT
STRONG POINTS OF BUILDING CONSTRUCTION AND IN
LOCATIONS WHERE THE ACCESS POINT DOES NOT
CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS
TREE LIMBS, WIRES, OR SIGNS.
10. WHERE DC CONDUCTORS ARE RUN INSIDE BUILDING,
THEY SHALL BE CONTAINED IN A METAL RACEWAY;
THEY SHALL NOT BE INSTALLED WITHIN 10" OF THE
ROOF DECKING OR SHEATHING EXCEPT WHERE
COVERED BY THE PV MODULES AND EQUIPMENT.
11. PLUMBING AND MECHANICAL VENTS THROUGH THE ROOF
SHALL NOT BE COVERED BY SOLAR MODULES- - NO
BUILDING, PLUMBING OR MECHANICAL VENTS TO BE
COVERED, CONSTRUCTED OR ROUTED AROUND SOLAR
MODULES.
12. ALL FIELD -INSTALLED JUNCTION, PULL AND OUTLET
BOXES LOCATED BEHIND MODULES SHALL BE
ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF A
MODULE SECURED BY REMOVABLE FASTENERS.
ELECTRICAL
1. WIRING MATERIALS SHALL COMPLY WITH MAXIMUM
CONTINUOUS CURRENT OUTPUT AT 25°C AND
MAXIMUM VOLTAGE AT 600V; WIRE SHALL BE WET
RATED AT 90°C.
2. EXPOSED PHOTOVOLTAIC SYSTEM CONDUCTORS ON
THE ROOF WILL BE USE 2 OR PV-TYPE WIRE.
3. PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE
IDENTIFIED AND GROUPED. THE MEANS OF
IDENTIFICATION SHALL BE PERMITTED BY SEPARATE
COLOR-CODING, MARKING TAPE, TAGGING OR OTHER
APPROVED MEANS.
4. ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL
BE RAIN-TIGHT AND APPROVED FOR USE IN WET
LOCATIONS.
5. ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE
BONDED AND ELECTRICALLY CONTINUOUS.
6. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND
CONDUITS ARE NOT SPECIFIED, CONTRACTOR SHALL
SIZE THEM ACCORDING TO APPLICABLE CODES.
7. REMOVAL OF A UTILITY-INTERACTIVE INVERTER OR
OTHER EQUIPMENT SHALL NOT DISCONNECT THE
BUILDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PV SOURCE
AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR.
8. FOR GROUNDED SYSTEMS, THE PHOTOVOLTAIC
SOURCE AND OUTPUT CIRCUITS SHALL BE PROVIDED
WITH A GROUND-FAULT PROTECTION DEVICE OR
SYSTEM THAT DETECTS A GROUND FAULT, INDICATES
THAT FAULT HAS OCCURED AND AUTOMATICALLY
DISCONNECTS ALL CONDUCTORS OR CAUSES THE
INVERTER TO AUTOMATICALLY CEASE SUPPLYING
POWER TO OUTPUT CIRCUITS.
9. FOR UNGROUNDED SYSTEMS, THE INVERTER IS EQUIPPED
WITH GROUND FAULT PROTECTION AND A GFI FUSE
PORT FOR GROUND FAULT INDICATION.
10. PV MODULE FRAMES SHALL BE BONDED TO RACKING RAIL
OR BARE COPPER GEC/GEC PER THE MODULE
MANUFACTURER'S LISTED INSTRUCTION SHEET.
11. PV MODULE RACKING RAIL SHALL BE BONDED TO BARE
COPPER GEC VIA WEEB LUG, ILSCO GBL-4DBT LAY-IN
LUG, OR EQUIVALENT LISTED LUG.
12. THE PHOTOVOLTAIC INVERTER WILL BE LISTED AS UL 1741
COMPLIANT.
13. RACKING AND BONDING SYSTEM TO BE UL2703 RATED.
14. ANY REQUIRED GROUNDING ELECTRODE CONDUCTOR
WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS
AS BUS BARS WITHIN LISTED EQUIPMENT.
15. WHEN BACKFED BREAKER IS THE METHOD OF UTILITY
INTERCONNECTION, THE BREAKERS SHALL NOT READ
"LINE AND LOAD".
16. WHEN APPLYING THE 120% RULE, THE SOLAR BREAKER
TO BE POSITIONED AT THE OPPOSITE END OF THE BUS
BAR FROM THE MAIN BREAKER.
17. THE WORKING CLEARANCE AROUND THE EXISTING
ELECTRICAL EQUIPMENT AS WELL AS THE NEW
ELECTRICAL EQUIPMENT WILL BE MAINTAINED.
x SYSTEM SIZE: 6.32 kW-DC | 5.0 kW-AC
MODULE: (16) CANADIAN SOLAR HIKU6 MONO PERC CS6R-395MS [395W]
OPTIMIZER: (16) SOLAREDGE S440
INVERTER: (1) SOLAREDGE SE5000H-US [240V]
780 CMR 51 MASSACHUSETTS RESIDENTIAL
CODE 9TH EDITION ADOPTED 10/20/2017. TABLE
R301.2(4) SNOW LOADS AND WIND SPEEDS
9-11-2023
N
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
LEGEND:
PROPERTY LINE:
DATE: 9/8/2023
DRAWN BY: LV
PROPERTY PLAN
PV-2
DRIVEWAY:
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
SCALE: 1/16" = 1'-0"
APN: 22B-057-001
PROPERTY LINE
DETACHED
STRUCTURE
D
R
I
V
E
W
A
Y
---
S
P
R
I
N
G
S
T
.
-
-
-
93'-6"
82'-11"
136'-10"
137'-9"MAIN HOME17'-6"
15'
44'-10"
68'-1"
FENCE
CHIMNEY FENCE:
9-11-2023
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
N SYSTEM LEGEND
UM
MP
MAIN SERVICE METER AND SERVICE POINT
MAIN SERVICE PANEL
SCALE: 1/8" = 1'-0"
CONDUIT TO BE RUN IN ATTIC IF POSSIBLE,
OTHERWISE CONDUIT BLOCKS MIN. 1"/MAX 6"
ABOVE ROOF SURFACE, CLOSE TO RIDGE LINES,
AND UNDER EAVES; TO BE PAINTED TO MATCH
EXTERIOR/EXISTING BACKGROUND COLOR OF ITS
LOCATION; TO BE LABELED AT MAX 10' INTERVALS.
CONDUIT RUNS ARE APPROXIMATE AND ARE TO
BE DETERMINED IN THE BY THE INSTALLERS
CONDUIT RUN
FIRE CODE SETBACK (18"MIN./ 36" MAX.)
(16) CANADIAN SOLAR HiKu6 MONO PERC
CS6R-395MS [395W] WITH (16) SOLAREDGE
S440 POWER OPTIMIZERS MOUNTED UNDER
EACH MODULE
ROOF SECTION 1: 6 MODULES
AZIMUTH: 133°
PITCH: 35°
ROOF TYPE: ASPHALT SHINGLE
ROOF SECTION 2: 5 MODULES
AZIMUTH: 134°
PITCH: 29°
ROOF SECTION 3: 5 MODULES
AZIMUTH: 134°
PITCH: 18°
ROOF DETAIL
1
2
3
DATE: 9/8/2023
DRAWN BY: LV
SITE PLAN
PV-3
JUNCTION BOX AND CONDUIT
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
I (1) SOLAREDGE SE5000H-US [240V]
INVERTER WITH INTEGRATED DC DISCONNECT
PHOTOVOLTAIC SYSTEM:
DC SYSTEM SIZE: 6.32 kW
AC SYSTEM SIZE: 5.00 kW
AC UTILITY AC DISCONNECT
UM1IMDMPAC MD MAIN SERVICE DISCONNECT
2
3
3'
3'
3'
9-11-2023
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
N
SYSTEM LEGEND
ELEVATION DETAIL
FIRE CODE SETBACK (18" MIN./ 36" MAX.)
ROOF SECTION 1: 6 MODULES
AZIMUTH: 133°
PITCH: 35°
ROOF TYPE: ASPHALT SHINGLE
ROOF SECTION 2: 5 MODULES
AZIMUTH: 134°
PITCH: 29°
ROOF SECTION 3: 5 MODULES
AZIMUTH: 134°
PITCH: 18°
ROOF DETAIL
1
2
3
ROOF ATTACHMENT POINT
DATE: 9/8/2023
DRAWN BY: LV
ROOF PLAN
PV-3.1
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
ROOF FRAMING (RAFTERS/TRUSS)
RACKING
AHJ: CITY OF NORTHAMPTON
MODULE MECHANICAL SPECIFICATIONS
DESIGN WIND SPEED 117 MPH
DESIGN SNOW LOAD 40 PSF
# OF STORIES 1
ROOF PITCH 35°, 29°, 18°
TOTAL ARRAY AREA (SQ. FT)335.84
TOTAL ROOF AREA (SQ. FT)1474
ARRAY SQ. FT / TOTAL ROOF SQ. FT 22.78%
1
SCALE: 1/8" = 1'-0"
2
ASPHALT SHINGLE
RAFTERS@24" O.C.2"X6": 2"X6"
STRUCTURAL ATTACHMENT
MODULE
3
22'-9"18'-11"
28'-7"
4' (TYP.)
3'
3'
3'
9-11-2023
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
PHOTOVOLTAIC SYSTEM:
DC SYSTEM SIZE: 6.32 kW
AC SYSTEM SIZE: 5.00 kW
INVERTER: (1) SOLAREDGE SE5000H-US
[240V]
MODULE: (16) CANADIAN SOLAR HIKU6
MONO PERC CS6R-395MS [395W]
NOTES:
1. MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM -
INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE
ATTACHED FOR SPECIFICATIONS IF APPLICABLE
2. PV DC SYSTEM IS UNGROUNDED
3. PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE
WITH NEC 250.58 AND 690.47(A)
4. PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS
SHALL COMPLY WITH NEC 690.1(G)
5. BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS
BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE
INSTALLED PER SYSTEM SIGNAGE, PAGE
6. BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP;
WHEN PRESENT, THE GEC TO BE CONTINUOUS
7. INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A
8. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY
FIELD CONDITIONS
9. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY
FIELD CONDITIONS.
OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS
INVERTER TYPE SOLAREDGE
5000H-US
# OF INVERTERS 1
MAX CONTINUOUS OUTPUT CURRENT 21A
(# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <=
OCPD RATING
(1 x 21A x 1.25)= 26.25A <= 30A, OK
DATE: 9/8/2023
DRAWN BY: LV
1-LINE DIAGRAM & CALCULATIONS
PV-4
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
PV MODULE ELECTRICAL SPECIFICATIONS
MODULE TYPE
CANADIAN SOLAR HIKU6
MONO PERC CS6R-395MS
[395W]
POWER MAX (PMAX) 395W
OPEN CIRCUIT VOLTAGE (VOC) 36.6V
SHORT CIRCUIT CURRENT (ISC)13.77A
MAX POWER-POINT VOLTAGE (VMP) 30.6V
MAX POWER-POINT CURRENT (IMP)12.91A
SERIES FUSE RATING 25A
POWER OPTIMIZER ELECTRICAL SPECIFICATIONS
OPTIMIZER TYPE SOLAREDGE S440
RATED INPUT DC POWER 440W
MAXIMUM INPUT VOLTAGE (VOC) 60V
MAXIMUM SHORT CIRCUIT CURRENT (ISC) 14.5A
MAXIMUM OUTPUT CURRENT 15A
MAXIMUM OUTPUT VOLTAGE 60V
MINIMUM STRING LENGTH 8
MAXIMUM POWER PER STRING 5700W
CONDUCTOR AND CONDUIT SCHEDULE
TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE
1 PV WIRE #10 4 - L1 L2 FREE AIR N/A
1 BARE COPPER #6 1 - BARE FREE AIR N/A
2 THWN-2 #10 4 - L1 L2 EMT 3/4"
2 THWN-2 EGC #10 1 - GND EMT 3/4"
3 THWN-2 #10 3 - L1 L2 N EMT 3/4"
3 THWN-2 EGC #10 1 - GND EMT 3/4"
4 THWN-2 #10 3 - L1 L2 N EMT 3/4"
4 THWN-2 EGC #10 1 - GND EMT 3/4"
INVERTER ELECTRICAL SPECIFICATIONS
INVERTER TYPE SOLAREDGE SE5000H-US
MAX INPUT DC VOLTAGE 480V
MAX INPUT CURRENT 13.5A
NOMINAL DC INPUT VOLTAGE 380V
MAXIMUM OUTPUT POWER 5000H
NOMINAL AC OUTPUT VOLTAGE 240V
MAXIMUM CONT. OUTPUT CURRENT 21A
CEC EFFICIENCY 99%
STRING 1: 8 MODULES - CANADIAN SOLAR HIKU6 MONO PERC
CS6R-395MS [395W]
=
=
=
=
=
=
=
=
=
=
=
=
7
STRING 2: 8 MODULES - CANADIAN SOLAR HIKU6 MONO PERC
CS6R-395MS [395W]
7
NEMA3R RATED JUNCTION
BOX: SHALL COMPLY W/
NEC 110.3 & 314.6
SOLAREDGE S440
OPTIMIZER
UTILITY INTERACTIVE SINGLE
PHASE INVERTER
SOLAREDGE SE5000H-US [240V]
INTEGRATED DC DISCONNECT
UL1741 CERTIFIED
1
1
(N) PV OCPD
2P - 30A
(E) LOADS
(E) 200A
MAIN
DISCONNECT
UTILITY SERVICE
120/240V
SINGLE PHASE
(E) 200A RATED
MAIN SERVICE
PANEL
FACILITY GROUND
(E) GROUND ROD
L1
G N-G
NOTE: ALL DC CONNECTOR TO MODULES OR INVERTERS MUST
BE OF MATCHING MANUFACTURING BRAND AND STYLE. DO NOT
USE 'COMPATIBLE' CONNECTORS WHICH HAVE NOT BEEN UL
TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE
MAY RESULT FROM MISMATCHED CONNECTOR USEAGE.
(N) AC DISCONNECT
240V30A NEMA 3R
FUSIBLE W/ 30A FUSES,
VISIBLE-LOCKABLE
LABELED
BUSBAR CALCULATIONS - PV BREAKER - 120% RULE
MAIN BUS RATING 200
MAIN DISCONNECT RATING 200
PV BREAKER RATING 30
(MAIN BUS RATING x 1.2) - MAIN DISCONNECT RATING >= OCPD RATING
(200A x 1.2) - 200A >= 30A, OK
9-11-2023
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
3-LINE DIAGRAM & CALCULATIONS
PV-4.1
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
NOTES:
1. MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM -
INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE
ATTACHED FOR SPECIFICATIONS IF APPLICABLE
2. PV DC SYSTEM IS UNGROUNDED
3. PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE
WITH NEC 250.58 AND 690.47(A)
4. PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS
SHALL COMPLY WITH NEC 690.1(G)
5. BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS
BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE
INSTALLED PER SYSTEM SIGNAGE, PAGE
6. BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP;
WHEN PRESENT, THE GEC TO BE CONTINUOUS
7. INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A
8. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY
FIELD CONDITIONS
9. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE
REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY
FIELD CONDITIONS.
AHJ: CITY OF NORTHAMPTON
PHOTOVOLTAIC SYSTEM:
DC SYSTEM SIZE: 6.32 kW
AC SYSTEM SIZE: 5.00 kW
INVERTER: (1) SOLAREDGE SE5000H-US
[240V]
MODULE: (16) CANADIAN SOLAR HIKU6
MONO PERC CS6R-395MS [395W]
NOTE: ALL DC CONNECTOR TO MODULES OR INVERTERS MUST
BE OF MATCHING MANUFACTURING BRAND AND STYLE. DO NOT
USE 'COMPATIBLE' CONNECTORS WHICH HAVE NOT BEEN UL
TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE
MAY RESULT FROM MISMATCHED CONNECTOR USAGE.
DATE: 9/8/2023
DRAWN BY: LV
OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS
INVERTER TYPE SOLAREDGE
5000H-US
# OF INVERTERS 1
MAX CONTINUOUS OUTPUT CURRENT 21A
(# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <=
OCPD RATING
(1 x 21A x 1.25)= 26.25A <= 30A, OK
PV MODULE ELECTRICAL SPECIFICATIONS
MODULE TYPE
CANADIAN SOLAR HIKU6
MONO PERC CS6R-395MS
[395W]
POWER MAX (PMAX) 395W
OPEN CIRCUIT VOLTAGE (VOC) 36.6V
SHORT CIRCUIT CURRENT (ISC)13.77A
MAX POWER-POINT VOLTAGE (VMP) 30.6V
MAX POWER-POINT CURRENT (IMP)12.91A
SERIES FUSE RATING 25A
INVERTER ELECTRICAL SPECIFICATIONS
INVERTER TYPE SOLAREDGE SE5000H-US
MAX INPUT DC VOLTAGE 480V
MAX INPUT CURRENT 13.5A
NOMINAL DC INPUT VOLTAGE 380V
MAXIMUM OUTPUT POWER 5000H
NOMINAL AC OUTPUT VOLTAGE 240V
MAXIMUM CONT. OUTPUT CURRENT 21A
CEC EFFICIENCY 99%
CONDUCTOR AND CONDUIT SCHEDULE
TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE
1 PV WIRE #10 4 - L1 L2 FREE AIR N/A
1 BARE COPPER #6 1 - BARE FREE AIR N/A
2 THWN-2 #10 4 - L1 L2 EMT 3/4"
2 THWN-2 EGC #10 1 - GND EMT 3/4"
3 THWN-2 #10 3 - L1 L2 N EMT 3/4"
3 THWN-2 EGC #10 1 - GND EMT 3/4"
4 THWN-2 #10 3 - L1 L2 N EMT 3/4"
4 THWN-2 EGC #10 1 - GND EMT 3/4"
POWER OPTIMIZER ELECTRICAL SPECIFICATIONS
OPTIMIZER TYPE SOLAREDGE S440
RATED INPUT DC POWER 440W
MAXIMUM INPUT VOLTAGE (VOC) 60V
MAXIMUM SHORT CIRCUIT CURRENT (ISC) 14.5A
MAXIMUM OUTPUT CURRENT 15A
MAXIMUM OUTPUT VOLTAGE 60V
MINIMUM STRING LENGTH 8
MAXIMUM POWER PER STRING 5700W
STRING 1: 8 MODULES - CANADIAN SOLAR HIKU6 MONO
PERC CS6R-395MS [395W]
=
=
=
=
=
=
=
=
=
=
=
=
7
STRING 2: 8 MODULES - CANADIAN SOLAR HIKU6 MONO
PERC CS6R-395MS [395W]
7
NEMA3R RATED JUNCTION
BOX: SHALL COMPLY W/
NEC 110.3 & 314.6
SOLAREDGE S440
OPTIMIZER
UTILITY INTERACTIVE SINGLE
PHASE INVERTER
SOLAREDGE SE5000H-US [240V]
INTEGRATED DC DISCONNECT
UL1741 CERTIFIED
(N) AC DISCONNECT
240V/30A NEMA 3R
FUSIBLE W/ 30A FUSES,
VISIBLE-LOCKABLE
LABELED
(N) PV OCPD
2P - 30A
(E) LOADS
(E) 200A
MAIN
DISCONNECT
UTILITY SERVICE
120/240V
SINGLE PHASE
(E) 200A RATED
MAIN SERVICE
PANEL
FACILITY GROUND
(E) GROUND ROD
L2
L1
N
G N-G
BUSBAR CALCULATIONS - PV BREAKER - 120% RULE
MAIN BUS RATING 200
MAIN DISCONNECT RATING 200
PV BREAKER RATING 30
(MAIN BUS RATING x 1.2) - MAIN DISCONNECT RATING >= OCPD RATING
(200A x 1.2) - 200A >= 30A, OK
9-11-2023
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
PV MODULE FRAME
IRONRIDGE AIRE A1 RAIL
DETAIL, END CLAMP (UFO) FRONT
IRONRIDGE STOPPER SLEEVEIRONRIDGE UNIVERSAL
FASTENING OBJECTPV MODULE FRAME
IRONRIDGE AIRE A1 RAIL
DETAIL, END CLAMP (UFO) PLAN
IRONRIDGE STOPPER
SLEEVE
IRONRIDGE UNIVERSAL
FASTENING OBJECT
PV MODULE FRAME
IRONRIDGE AIRE A1 RAIL
DETAIL, MID CLAMP FRONT
IRONRIDGE UNIVERSAL
FASTENING OBJECTPV MODULE FRAME
DETAIL, MID CLAMP PLAN
IRONRIDGE UNIVERSAL
FASTENING OBJECT
IRONRIDGE AIRE A1 RAIL
IRONRIDGE FLASHFOOT-2
IRONRIDGE AIRE A1 RAIL
PV MODULE
IRONRIDGE STOPPER SLEEVE
IRONRIDGE UNIVERSAL
FASTENING OBJECT
IRONRIDGE FLASHFOOT2IRONRIDGE UNIVERSAL
FASTENING OBJECT
1.0000
PV-5
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
MOUNTING DETAILS AND BOM
ATTACHMENT TYPE: IRONRIDGE FLASHFOOT2
WITH IRONRIDGE AIRE A1 RAIL
ROOF TYPE: ASPHALT SHINGLE ,ROOF TILT: 35°, 29°, 18°
MODULE WEIGHT: 47 LBS
MODULE DIMENSIONS: 5.65' X 3.72'
MODULE WEIGHT/ SQ. FOOT: 2.24 LBS
TOTAL NO. OF MODULES: 16
TOTAL MODULE WEIGHT: 752.0 LBS
ATTACHMENT DETAILS
(N.T.S.)
1
AHJ: CITY OF NORTHAMPTON
/>>K&DdZ/>
Yh/WDEd D<YhEd/dz
DKh>E/E^K>Z,ŝ<ƵϲDKEKWZ^ϲZͲϯϵϱD^
ϯϵϱt ϭϲ
/EsZdZ ^K>Z'^ϱϬϬϬ,Ͳh^ϮϰϬs ϭ
KWd/D/Z^^K>Z'^ϰϰϬKWd/D/Z ϭϲ
E>DW^DKh>E>DW^dEZϭϮ
D/>DW^DKh>D/>>DW^d^dEZ;/Ed'Zd
'ZKhE/E'Ϳ Ϯϲ
DKhEd/E'WK/Ed^/ZKEZ/'&>^,&KKdϮ ϰϬ
DKhEd/E'Z/>^/ZKEZ/'/Z/Z/> ϭϭ
hd/>/dz
/^KEEd
Ws^z^dDhd/>/dz/^KEEdϯϬZdt/d,
ϯϬ&h^^ϭ
DATE: 9/8/2023
DRAWN BY: LV
9-11-2023
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
PV-6
LABELS ARE NOT DRAWN TO SCALE
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
ELECTRICAL LABELS & ELEVATION
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2023
NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE
CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE
AUTHORITY HAVING JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO
WITHSTAND THE ENVIRONMENT INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8”
AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER”
WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE
ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW
BACKGROUND. [ANSI Z535]
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE
LOCATION OF THE SERVICE DISCONNECTING MEANS AND
THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF
NOT IN THE SAME LOCATION
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED
FROM EACH OTHER, A DIRECTORY IN ACCORDANCE
WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM
DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS
SHALL NOT BE INSTALLED IN BATHROOMS
[NEC 690.4(D),(E)]
ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE
WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT
BE HAND-WRITTEN PER NEC 110.21(B)
AHJ: CITY OF NORTHAMPTON
! WARNING !
DUAL POWER SOURCES.
SECOND SOURCE IS PV SYSTEM
LABEL 7
PHOTOVOLTAIC
AC DISCONNECT
OPERATING CURRENT: 21 A AC
OPERATING VOLTAGE: 240 V AC
LABEL 5
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS
[NEC 690.54]
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION.
LABEL 3
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.13 AND 690.15]
PHOTOVOLTAIC
DC DISCONNECT
UTILITY
AC DISCONNECT
LABEL 10
AT EACH DC DISCONNECTING MEANS
[NEC 690.13(B)]
LABEL 12
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS.
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
LABEL 13
AT EACH AC DISCONNECTING MEANS
[NEC 690.13(B)]
! CAUTION !
PHOTOVOLTAIC SYSTEM
CIRCUIT IS BACKFED
! WARNING !
POWER SOURCE OUTPUT
CONNECTION - DO NOT RELOCATE
THIS OVERCURRENT DEVICE
LABEL 14
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE
[NEC 705.12(B)(2)(3)(B)]
LABEL 9
AT UTILITY METER
[NEC 690.56(B)]
LABEL 4
AT EACH DC DISCONNECTING MEANS
[NEC 690.53]
LABEL 11
AT RAPID SHUTDOWN SWITCH
[NEC 690.56(C)].
LETTERS AT LEAST 3/8 INCH; WHITE ON RED
BACKGROUND; REFLECTIVE
[IFC 605.11.1.1]
LABEL 8
AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 7 OR LABEL 8 MUST IDENTIFY
PHOTOVOLTAIC SYSTEM
[NEC 705.12(B)(4)]
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUTDOWN
PV SYSTEM AND REDUCE
SHOCK HAZARD IN ARRAY
LABEL 1
AT RAPID SHUTDOWN SYSTEM
[NEC 690.56(C)(1)(A)].
! WARNING !
ELECTRIC SHOCK HAZARD
TERMINALS ON THE LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION.
DC VOLTAGE IS ALWAYS PRESENT WHEN
SOLAR MODULES ARE EXPOSED TO SUNLIGHT
LABEL 2
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT
[NEC 690.15]
MAXIMUM VOLTAGE: 480 V DC
MAXIMUM CIRCUIT CURRENT: 13.5 A DC
MAX RATED OUTPUT CURRENT OF
THE CHARGE CONTROLLER
OR DC-TO-DC CONVERTER
(IF INSTALLED): 15 A DC
LABEL 6
AT RAPID SHUTDOWN DISCONNECT SWITCH
[NEC 690.56(C)(3)].
#03-359 LOCAL CODES
BI-DIRECTIONAL METER
WARNING: PHOTOVOLTAIC
POWER SOURCE
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH RAPID
SHUTDOWN
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
SOLAR ELECTRIC
PV PANELS
WARNING
THIS SERVICE METER
IS ALSO SERVED BY A
PHOTOVOLTAIC SYSTEM
MAIN SERVICE PANEL
FOR ILLUSTRATION ONLY
(NOT ACTUAL MSP)
INVERTERJUNCTION
BOX
(IF USED)4
7
8 92
2
2
1
611
14
3
3
TO SOLAR
ARRAY UTILITY AC
DISCONNECT
5
2 6
3
MAIN SERVICE
METER
DATE: 9/8/2023
DRAWN BY: LV9-11-2023
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
FOR INSTALLER USE ONLY
STRING MAP
PV-7
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
STRING DETAIL
SOLAREDGE STRINGS
STRING DETAIL
SOLAREDGE STRINGS
STRING DETAIL
SOLAREDGE STRINGS
STRING DETAIL
SOLAREDGE STRINGS
STRING # 1: 8 MODULES
STRING DETAIL
SOLAREDGE STRINGS
DATE: 9/8/2023
DRAWN BY: LV
STRING -1
STRING -2
STRING # 2: 8 MODULES
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
MODULE DATASHEET
PV-8.1
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
DATE: 9/8/2023
DRAWN BY: LV
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
INVERTER DATASHEET
PV-8.2
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
DATE: 9/8/2023
DRAWN BY: LV
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
OPTIMIZERS DATASHEET
PV-8.3
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
DATE: 9/8/2023
DRAWN BY: LV
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
RACKING DATASHEET
PV-8.4
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
DATE: 9/8/2023
DRAWN BY: LV
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102
ROOF ATTACHMENT DATASHEET
PV-8.5
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
AHJ: CITY OF NORTHAMPTON
DATE: 9/8/2023
DRAWN BY: LV
59C NORTH ST., HATFIELD MA 01038
TEL. NO.(413) 338-7555
INSIGHT SOLAR
LIC. NO. HIC - MA 192102N
DATE: 9/8/2023
DRAWN BY: LV
PLACARD
PV-9
WEIS, RICHARD
40 SPRING ST.
FLORENCE, MA 01062
CAUTION
POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED AS SHOWN
!!
SERVICE 1 OF 1
40 SPRING ST.FLORENCE, MA 01062
UTILITY METER
AHJ: CITY OF NORTHAMPTON
UTILITY AC DISCONNECT
MAIN SERVICE
PANEL
INVERTER
SOLAR PV ARRAY