Loading...
FRFI - 24 (1) REQUEST FOR INFORMATION (RFI) RESPONSE Project Name: The Sergeant House Date: 11/19/2019 Client Name: Dietz & Company Architects, Inc. CEC Project#: 20170094 Attention: Ventilation System Fire dampers RFI No.: 24 Q: From: Mark Follett (Western Builders Inc.) Kyle no separation is showing between the rooms/floors. We recommend Fire/Smoke Dampers. Please advise. Dampers will need to be shown with access panels if this option is desired. Please confirm no rated wrap is required on the ducting as well. A: 1 hour fire rated walls and ceilings do not require additional rated duct wrap, due to the ductwork having a 1 hour fire rating and radiation dampers at all grilles and diffusers. We have fire smoke dampers for ERU-1 supply and return duct shafts that will require access panels. End of Response This response is given with the expressed understanding that it does not constitute a basis for any change in the contract amount or a modification to the completion schedule of the project contract. If you do not concur, DO NOT PROCEED, and notify this office IMMEDIATELY. SIGNED:_ Katherine Stellato 11/25/19 COPY TO: PROJECT FILE