Dawn Nims 10-26-22 CAD (1)SCOPE OF WORK
TO INSTALL A ROOF MOUNTED SOLAR PHOTOVOLTAIC SYSTEM AT THE OWNER RESIDENCE
LOCATED AT 8 CHARLES ST, NORTHAMPTON, MA 01060, USA
(LATITUDE & LONGITUDE : 42.307330,-72.641472).
THE POWER GENERATED BY THE PV SYSTEM WILL BE INTERCONNECTED WITH THE UTILITY
GRID THROUGH THE EXISTING ELECTRICAL SERVICE EQUIPMENT.
THE PV SYSTEM DOES NOT INCLUDE STORAGE BATTERIES.
EQUIPMENT SUMMARY
25 Q CELLS Q.PEAK DUO BLK-G10+ 365 MODULES
25 ENPHASE IQ8PLUS -72-2-US (240V) MICROINVERTERS
GENERAL NOTES
THESE CONSTRUCTION DOCUMENTS HAVE BEEN BASED ON FIELD INSPECTIONS AND
OTHER INFORMATION AVAILABLE AT THE TIME. ACTUAL FIELD CONDITIONS MAY REQUIRE
MODIFICATIONS IN CONSTRUCTION DETAILS.
•
ARCHITECT HAS NOT BEEN RETAINED TO SUPERVISE ANY CONSTRUCTION OR
INSTALLATION OF ANY EQUIPMENT AT SITE.
•
CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, EQUIPMENT, TOOLS, OBTAINS ALL
PERMITS, LICENSES AND PAY ALL REQUIRED FEES AND COMPLETE INSTALLATION.
•
CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS
AND EXISTING CONDITIONS. ANY DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER
BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED BEFORE CONSULTATION AND
ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLE RESPONSIBILITY OF THE
CONTRACTOR AND SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL
COMPENSATION.
•
DAMAGE CAUSED TO THE EXISTING STRUCTURE, PIPES, DUCTS, WINDOWS, WALL, FLOORS,
ETC. SHALL BE REPAIRED TO THE ORIGINAL CONDITION OR REPLACED BY THE
CONTRACTOR AT NO ADDITIONAL COST.
•
THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION AND
COMPLETION OF THE WORK WITH APPROVED MATERIALS.
•
NO CHANGES ARE TO BE MADE WITHOUT THE CONSULTATION AND APPROVAL OF THE
ARCHITECT.
•
CONTRACTOR SHALL OBTAIN BULDING PERMIT. NO WORK TO START UNLESS BUILDING
PERMIT IS PROPERLY DISPLAYED.
•
ALL WORKMANSHIP AND MATERIALS SHALL BE OF FIRST QUALITY AND IN COMPLIANCE
WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, THE DEPARTMENT OF
ENVIRONMENTAL PROTECTION AND ALL PERTINENT AGENCIES.
•
IT 1S ESSENTIAL THAT ALL WORK PROCEED WITH THE MAXIMUM COOPERATION OF ALL
PARTIES AND WITH MINIMUM INTERFERENCE TO THE OCCUPANTS WITHIN THE BUILDING.
THE OWNER'S DIRECTIONS IN THIS REGARD SHALL BE FULLY COMPLIED WITH.
•
ALL EXPOSED PLUMBING, HVAC, ELECTRICAL DUCTWORK, PIPING AND CONDUITS ARE TO
BE PAINTED BY GENERAL CONTRACTOR.
•
THE CONTRACTOR SHALL PERFORM THE WORK IN STRICT CONFORMANCE WITH THE
LOCAL LAWS, REGULATIONS AND THE NATIONAL ELECTRIC CODE.
•
THE CONTRACTOR SHALL OBTAIN ALL PERMITS, APPROVALS, AFFIDAVITS, CERTIFICATIONS,
ETC. AND PAY ALL FEES AS REQUIRED BY THE LOCAL AUTHORITIES.
•
CONTRACTORS SHALL OBTAIN FIRE CERTIF. UPON COMPLETION OF WORK.•
ELECTRICAL NOTES
ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION.•
ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET
ENVIRONMENT.
•
WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY
TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY.
•
WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL
COMPLY WITH NEC 110.26.
•
WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE
CONTRACTOR SHALL SIZE THEM ACCORDINGLY.
•
ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE.•
MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE
SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURERS INSTRUCTION.
•
MODULE SUPPORT RAIL SHALL BE BONDED TO THE MODULE•
GOVERNING CODES
2015 INTERNATIONAL BUILDING CODE
2015 INTERNATIONAL FIRE CODE
2015 INTERNATIONAL RESIDENTIAL CODE
2020 NATIONAL ELECTRICAL CODE
AHJ NAME : NORTHAMPTON CITY
AHJ ADDRESS : 210 MAIN STREET NORTHAMPTON, MA 01060
AHJ CONTACT NO. : 4135871240
WIRING AND CONDUIT NOTES
ALL CONDUIT SIZES AND TYPES SHALL BE LISTED FOR ITS PURPOSE AND
APPROVAL FOR THE SITE APPLICATIONS
•
ALL PV CABLES AND HOMERUN WIRES BE #10AWG *USE-2, PV WIRE, OR
PROPRIETARY SOLAR CABLING SPECIFIED BY MFR, OR EQUIVALENT; ROUTED TO
SOURCE CIRCUIT COMBINER BOXES AS REQUIRED
•
ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT SHALL BE
DERATED ACCORDING TO AS PER LATEST NEC CODE.
•
EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 90°C RATED, WET AND UV
RESISTANT, AND UL LISTED RATED FOR 600V, UV RATED SPIRAL WRAP SHALL BE
USED TO PROTECT WIRE FROM SHARP EDGES
•
PHASE AND NEUTRAL CONDUCTORS SHALL BE DUAL RATED THHN/THWN-2
INSULATED, 90°C RATED, WET AND UV RESISTANT, RATED FOR 1000V AS PER
APPLICABLE NEC
•
4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH THE HIGHER
VOLTAGE TO GROUND MARKED ORANGE OR IDENTIFIED BY OTHER EFFECTIVE
MEANS
•
ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE CIRCUIT PROTECTION•
VOLTAGE DROP LIMITED TO 2%•
AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE A OR L1- BLACK,
PHASE B OR L2- RED, PHASE C OR L3- BLUE, NEUTRAL- WHITE/GRAY
•
VOLTAGE DROP LIMITED TO 2%•
AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE AOR L1- BLACK,
PHASE B OR L2- RED, PHASE C OR L3- BLUE, NEUTRAL- WHITE/GRAY
•
SYSTEM RATING
9.125 kWDC
7.250 kWAC
SHEET INDEX
PV1 COVER PAGE
PV2 SITE PLAN
PV3 ROOF PLAN
PV4 STRUCTURAL DETAILS
PV5 ELECTRICAL LINE & CALCS.
PV6-PV7 SIGNAGE
PV8-PV10 EQUIPMENT SPECIFICATIONS
PV11-PV12 SPAN TABLE
PV13-PV17 EQUIPMENT SPECIFICATIONS
PROJECT SITE
HOUSE PHOTO SCALE: NTS
PROJECT SITE
VICINITY MAP SCALE: NTS
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
COVER PAGE
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-1
10/26/2022
SITE NOTES
A LADDER SHALL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.•
THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS AN UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.•
THE SOLAR PV INSTALLATION SHALL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS.•
PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION [NEC 110.26]•
LEGEND
JB (N) JUNCTION BOX
UM (E) UTILITY METER
MSP (E) MAIN SERVICE PANEL
IQ (N) ENPHASE IQ COMBINER
AC (N) FUSED AC DISCONNECT
VENT, ATTIC FAN (ROOF
OBSTRUCTION)
ROOF ATTACHMENT
-------CONDUIT
ENPHASE IQ8PLUS -72-2-US (240V)
MICROINVERTER
Q CELLS Q.PEAK DUO BLK-G10+
365 MODULES
NXT HORIZON RAIL - 168" MILL
TRENCH
SCALE: 1/32"= 1'-0"
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
SITE PLAN
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-2
10/26/2022
ROOF DESCRIPTION
ROOF ROOF
TILT
AZIMUTH RAFTER
SIZE
RAFTER
SPACING
ROOF MATERIAL
#1 27°235°2" x 6"16" o.c.COMP SHINGLE
#2 27°55°2" x 6"16" o.c.COMP SHINGLE
#3 27°145°2" x 6"16" o.c.COMP SHINGLE
ARRAY AREA & ROOF AREA CALC'S
ROOF # OF MODULES ARRAY AREA (Sq. Ft.)
#1 12 231.76
#2 9 173.82
#3 4 77.26
(TOTAL ARRAY AREA/TOTAL ROOF AREA) X 100%
= (482.83/1613.24) X 100% = 29.93%
LEGEND
JB (N) JUNCTION BOX
UM (E) UTILITY METER
MSP (E) MAIN SERVICE PANEL
IQ (N) ENPHASE IQ COMBINER
AC (N) FUSED AC DISCONNECT
VENT, ATTIC FAN (ROOF
OBSTRUCTION)
ROOF ATTACHMENT
-------CONDUIT
ENPHASE IQ8PLUS -72-2-US (240V)
MICROINVERTER
Q CELLS Q.PEAK DUO BLK-G10+
365 MODULES
NXT HORIZON RAIL - 168" MILL
TRENCH
SCALE: 1/8"= 1'-0"
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
ROOF PLAN
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-3
10/26/2022
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
STRUCTURAL
DETAILS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-4
10/26/2022
ID TYPICAL INITIAL CONDUCTOR
LOCATION
FINAL CONDUCTOR
LOCATION
CONDUCTOR CONDUIT # OF
PARALLEL
CIRCUITS
CURRENT-CARRYING
CONDUCTORS IN
CIRCUIT
CONDUIT
FILL
PERCENT
OCPD EGC TEMP. CORR.
FACTOR
CONDUIT
FILL
FACTOR
CONT.
CURRENT
MAX.
CURRENT
BASE
AMP.
DERATED
AMP.
TERM.
TEMP.
RATING
LENGTH VOTAGE
DROP
1 2 ARRAY JUNCTION BOX 12 AWG Q CABLE COPPER - 1 2 N/A N/A 10 AWG BARE
COPPER
0.76 (54°C)N/A 15.73A 19.66A N/A N/A 75°C 54FT 0.76%
2 2 JUNCTION BOX IQ COMBINER BOX 10 AWG THWN 2 COPPER MIN 0.75" DIA
EMT
1 2 14.26%20A 8 AWG THWN-2
COPPER
0.96 (32°C)1 15.73A 19.66A 40A 38.40A 75°C 42FT 0.71%
3 1 IQ COMBINER BOX FUSED AC
DISCONNECT
8 AWG THWN 2 COPPER MIN 0.75" DIA
EMT
1 3 27.02%40A 8 AWG THWN-2
COPPER
0.96 (32°C)1 30.25A 37.81A 55A 52.80A 75°C 5FT 0.10%
4 1 FUSED AC
DISCONNECT
MSP 6 AWG THWN 2 COPPER MIN 0.75" DIA
EMT
1 2 25.14%N/A 8 AWG THWN-2
COPPER
0.96 (32°C)1 30.25A 37.81A 75A 72.00A 75°C 5FT 0.06%
SERVICE INFO
UTILITY PROVIDER:NATIONAL GRID
AHJ NAME:NORTHAMPTON CITY
MAIN SERVICE VOLTAGE:240V
MAIN PANEL BRAND:GE
MAIN SERVICE PANEL:200 A
MAIN BREAKER RATING:200 A
MAIN SERVICE LOCATION:SOUTH
SERVICE FEED SOURCE:OVERHEAD
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
ELECTRICAL
LINE & CALCS.
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-5
10/26/2022
1 WARNING
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES MAY
BE ENERGIZED IN THE OPEN POSITION
LABEL LOCATION:
POINT OF INTERCONNECTION, MAIN SERVICE
DISCONNECT, AC DISCONNECT, AC COMBINER,
INVERTER
PER CODE: NEC 690.13(B)
2 CAUTION : SOLAR ELECTRIC
SYSTEM CONNECTED
LABEL LOCATION:
POINT OF INTERCONNECTION & INVERTER
PER CODE: NEC 690.15 & 690.13(B)
3 SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID
SHUTDOWN SWITCH
TO THE 'OFF'
POSITION TO SHUT
DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD IN
THE ARRAY
LABEL LOCATION:
MAIN SERVICE DISCONNECT IF MSD IS OUTSIDE
PLACE IT THERE / IF MSD IS INSIDE PLACE ON THE
AC DISCONNECT
PER CODE: 2020 NEC 690.56(C)
4 PHOTOVOLTAIC SYSTEM
UTILITY DISCONNECT SWITCH
LABEL LOCATION:
AC DISCONNECT
PER CODE: NEC 690.56(C)(2)
ADHESIVE FASTENED SIGNS
THE LABEL SHALL BE SUITABLE FOR THE
ENVIRONMENT WHERE IT IS INSTALLED.
•
WHERE REQUIRED ELSEWHERE IN THIS CODE, ALL
FIELD APPLIED LABELS, WARNING AND MARKINGS
SHOULD COMPLY WITH ANSI 2535.4 [NEC 110.21(B)
FIELD MARKING].
•
ADHESIVE FASTENED SIGNS MAY BE ACCEPTABLE IF
PROPERLY ADHERED. VINYL SIGNS SHALL BE WEATHER
RESISTANT [IFC 605.11.1.3]
•
5 PHOTOVOLTAIC AC DISCONNECT
RATED AC OUTPUT CURRENT 30.25 AMPS
NOMINAL OPERATING AC VOLTAGE 240 VOLTS
LABEL LOCATION:
INTERACTIVE SYSTEM POINT OF INTERCONNECTION
PER CODE: NFPA 70, NEC 690.54
6 CAUTION
CONTAINS MULTIPLE POWER SOURCES
LABEL LOCATION:
PLACE LABEL ON ALL EQUIPMENT CONTAINING
OVERCURRENT DEVICES IN CIRCUITS SUPPLYING
POWER TO A BUSBAR OR CONDUCTORS SUPPLIED
FROM MULTIPLE SOURCES
PER CODE: NEC 705.12(C) and 690.59
7 WARNING:
PHOTOVOLTAIC POWER SOURCE
LABEL LOCATION:
CONDUIT
PER CODE: NEC 690.31(D)(2)
8 CAUTION : SOLAR CIRCUIT
LABEL LOCATION:
MARKINGS PLACED ON ALL INTERIOR AND EXTERIOR CONDUIT, RACEWAYS,
ENCLOSURES, AND CABLE ASSEMBLIES AT LEAST EVERY 1O FT, AT TURNS AND
ABOVE/BELOW PENETRATIONS AND ALL COMBINER/JUNCTION BOXES
PER CODE: IFC 606.11.1.4
9 WARNING - Electric Shock Hazard
No user serviceable parts inside
Contact authorized service provider for assistance
LABEL LOCATION:
INVERTER & JUNCTION BOXES (ROOF)
PER CODE: NEC 690.13 (G)(3) & 690.13 (G)(4)
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
SIGNAGE
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-6
LABEL LOCATION:
EACH SERVICE EQUIPMENT LOCATION AND AT THE LOCATION(S) OF THE SYSTEM DISCONNECT(S)
FOR ALL ELECTRIC POWER PRODUCTION SOURCES CAPABLE OF BEING INTERCONNECTED
(PER CODE: NEC 705.10)
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
SIGNAGE
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-7
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
EQUIPMENT
SPECIFICATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-8
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
EQUIPMENT
SPECIFICATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-9
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
EQUIPMENT
SPECIFICATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-10
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
SPAN TABLE
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-11
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
SPAN TABLE
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-12
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
EQUIPMENT
SPECIFICATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-13
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
EQUIPMENT
SPECIFICATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-14
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
EQUIPMENT
SPECIFICATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-15
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
EQUIPMENT
SPECIFICATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-16
SKYLINE SOLAR LLC
HIC : 13VH0613060
ELEC : 34EB00932200
SYSTEM INFO
(25) Q CELLS
Q.PEAK DUO BLK-G10+ 365
(25) ENPHASE
IQ8PLUS -72-2-US (240V)
DC SYSTEM SIZE: 9.125 kWDC
AC SYSTEM SIZE: 7.250 kWAC
METER: 05410585
JOB NO. : 204607
UTILITY ACC NO. : 5018593028
REVISIONS
DESCRIPTION DATE REV
PROJECT NAME & ADDRESS
DAWN NIMSRESIDENCE8 CHARLES ST, NORTHAMPTON, MA 01060, USAEMAIL ID: DAWNNIMS@GMAIL.COMPHONE NO. (802) 451-6942DATE: 10/26/2022
SHEET NAME
EQUIPMENT
SPECIFICATIONS
SHEET SIZE
ANSI B
11" X 17"
SHEET NUMBER
PV-17