Loading...
North Commons at Village Hill TAB ReportPROJECT # 282 FOMER ROAD SOUTHAMPTON, MA 01073 #BB977252T T.A.B.B. CERTIFIED LOCATION: 140 ORLANDER NORTHAMPTON, MA ARCHITECT:DAVIS SQUARE ARCHITECTS ENGINEER: BUILDING ENGINEERING RESOURCES, INC. CUSTOMER: DEE SERVICE 413·527·1682 DATE: 1/14/2022 11221 PROJECT:NORTH COMMONS AT VILLAGE HILL TABLE OF CONTENTS SHEET PAGE(S) COVER SHEET 1 TABLE OF CONTENTS 2 ABBREVIATIONS 3 ERV-1 DATA 4 ERV-1 AIR READINGS 5 ERV-2 DATA 6 ERV-2 READINGS 7 - 11 ERV-3 DATA 12 ERV-3 READINGS 13 - 17 UNIT TOTALS 18 PROJECT NAME NORTH COMMONS AT VILLAGE HILLPROJECT №11221 2 OF 18 ABBREVIATIONS AHU AIR HANDLING UNIT LPS LOW PRESSURE STEAM AC or ACU AIR CONDITIONER UNIT LT LIGHT TROFFER ACCU AIR COOLED CONDENSING UNIT LWG LOW WALL GRILLE AMP AMPERAGE LWT LEAVING WATER TEMPERATURE AVG AVERAGE MAU / MUA MAKE UP AIR UNIT A.D.AIR DENSITY MBH 1,000 BTU'S PER HOUR BHP BRAKE HORSEPOWER N/A NOT ACCESSIBLE CB CIRCUIT BREAKER NI NOT INSTALLED CD CEILING DIFFUSER NL NOT LISTED CFM CUBIC FEET PER MINUTE NA NOT APPLICABLE CE CEILING EXHAUST N.Z.NOZZLE CH CHILLER O.D.OUTSIDE DIAMETER CHW CHILLED WATER O/A MIN OUTDOOR AIR MINIMUM CR CEILING RETURN OAT OUTSIDE AIR TEMPERATURE CP CIRCULATING PUMP PF POWER FACTOR CC COOLING COIL PHC PRE-HEAT COIL CT COOLING TOWER PH PHASE CW CONDENSER WATER PMP CIRCULATING PUMP DB DRY BULB PSI POUNDS PER SQUARE INCH. DD DIRECT DRIVE RA RETURN AIR DIA DIAMETER RF RETURN FAN DP DIFFERENTIAL PRESSURE R.G.RETURN GRILLE EAT ENTERING AIR TEMPERATURE RHC RE-HEAT COIL EDC ELECTRIC DUCT COIL RPM REVOLUTIONS PER MINUTE EDH ELECTRIC DUCT HEATER RTU ROOF TOP UNIT EF EXHAUST FAN RVA ROTATING VANE ANEMOMETER EMCS ENERGY MGMT. CONTROL SYSTEM SA SUPPLY AIR EWT ENTERING WATER TEMPERATURE SAT SUPPLY AIR TEMPERATURE FCU FAN COIL UNIT S.D.SUPPLY DIFFUSER FH FUME HOOD SEF SMOKE EXHAUST FAN FG FLOOR GRILLE SF (AIR)SUPPLY FAN FE FLOOR EXHAUST OR RETURN SF (ELEC.)SERVICE FACTOR FLA FULL LOAD AMPERAGE SHC STEAM HEATING COIL FPB FAN POWERED BOX S.P."W.C."STATIC PRESSURE IN WATER COLUMN FPT FAN POWERED TERMINAL S.W.E.SIDEWALL EXHAUST FPM FEET PER MINUTE S.W.R.SIDEWALL RETURN FS FLOOR SUPPLY S.W.S.SIDEWALL SUPPLY FSR FLOOR SUPPLY REGISTER TAB TESTING ADJUSTING & BALANCING FT HD FEET OF HEAD TSP TOTAL STATIC PRESSURE FTU FAN TERMINAL UNIT UH UNIT HEATER GPM GALLONS PER MINUTE V VOLTS HC HEATING COIL VEL VELGRID HEPA HIGH-EFFICIENCY PARTICLE ARRESTANCE VAV VARIABLE AIR VOLUME HF HEPA FILTER VD VOLUME DAMPER HOA HAND / OFF / AUTO SWITCH VFD VARIABLE FREQUENCY DRIVE HP HORSEPOWER VP VELOCITY PRESSURE HRC HEAT RECOVERY COIL VPT VELOCITY PRESSURE TRAVERSE HVAC HEATING, VENTILATION & AIR CONDITIONING W WATTS HWR HOT WATER RETURN WB WEB BULB HWS HOT WATER SUPPLY W.D.WATER DENSITY HX HEAT EXCHANGER W.G.WATER GAUGE ID INSIDE DIAMETER F FAHRENHEIT IGV INLET GUIDE VANES ΔP DIFFERENTIAL PRESSURE LAT LEAVING AIR TEMPERATURE ΔT DIFFERENTIAL TEMPERATURE LD LINEAR DIFFUSER Ø ROUND 3 OF 18 ERV TEST REPORT PROJECT NAMEPROJECT №DATE 1/14/2022 UNIT INFORMATION DESIGNATION №ERV-1 MANUFACTURER VENTACITY SYSTEMS LOCATION ROOF MODEL №VS3000 Rte (ERV) SERVICE CORE VENTILATION SERIAL №L46-20-ZOE2002615-3000150831 SUPPLY EXHAUST MOTOR INFORMATION MOTOR INFORMATION MANUFACTURER N/A MANUFACTURER N/A CATALOG №N/A CATALOG №N/A HORSEPOWER N/A HORSEPOWER N/A RPM N/A RPM N/A SERVICE FACTOR N/A SERVICE FACTOR N/A POWER FACTOR N/A POWER FACTOR N/A EFFICIENCY N/A EFFICIENCY N/A FRAME N/A FRAME N/A DRIVE INFORMATION DRIVE INFORMATION MOTOR SHEAVE / BORE DIRECT DRIVE MOTOR SHEAVE / BORE DIRECT DRIVE FAN PULLEY / BORE DIRECT DRIVE FAN PULLEY / BORE DIRECT DRIVE BELTS - QTY / SIZE DIRECT DRIVE BELTS - QTY / SIZE DIRECT DRIVE SHEAVE POSITION DIRECT DRIVE SHEAVE POSITION DIRECT DRIVE CENTER TO CENTER DIRECT DRIVE CENTER TO CENTER DIRECT DRIVE TEST INFORMATION TEST INFORMATION DESIGN CFM 1,110 DESIGN CFM 1,110 CONNECTED CFM 1,110 CONNECTED CFM 1,110 MEASURED CFM 1,154 MEASURED CFM 1,158 DESIGN E.S.P.N/A DESIGN E.S.P.N/A DELIVERED E.S.P..25''DELIVERED E.S.P..32'' PLENUM S.P..0''PLENUM S.P.-.32'' DISCHARGE S.P..25''DISCHARGE S.P..0'' DESIGN FAN RPM N/A DESIGN FAN RPM N/A ACTUAL FAN RPM N/A ACTUAL FAN RPM N/A VOLTAGE-PHASE 208-3 VOLTAGE-PHASE N/A MEASURED VOLTAGE 207/208/208 MEASURED VOLTAGE N/A MOTOR AMPS RATED 10.7 MOTOR AMPS RATED N/A MEASURED AMPERAGE 1.5/1.3/1.3 MEASURED AMPERAGE N/A VFD SETTING N/A VFD SETTING N/A S.P.C.P.N/A NORTH COMMONS AT VILLAGE HILL11221 4 OF 18 AIR OUTLET TEST REPORT PROJECT NAMEPROJECT №DATE №OUTLET AREA K (AK)NOTE SIZE FPM CFM FPM CFM RM. № SUPPLY 3RD FL. CORRIDOR N 1 D8 150 165 3RD FL. CORRIDOR S 2 D8 120 120 2ND FL. CORRIDOR N 3 D8 150 160 2ND FL. CORRIDOR S 4 D8 120 123 1ST FL. CORRIDOR S 5 D8 85 86 FITNESS 6 D8 90 92 AHU RETURN 7 8" Ø 0.349 VPT 0.349 630 220 643 224 COMMUNITY ROOM 8 D8 110 119 1ST FL. CORRIDOR N 9 D8 65 65 1,110 1,154 EXHAUST 3RD FL. CORRIDOR 1 Y12 200 204 JANITOR 2 Z8 0.250 0.8 0.200 350 70 365 73 2ND FL. CORRIDOR 3 Y12 200 207 JANITOR 4 Z8 0.250 0.8 0.200 350 70 368 74 1ST FL. CORRIDOR 5 Y12 400 426 JANITOR 6 Z8 0.250 0.8 0.200 350 70 372 74 TOILET 7 Z8 50 50 TOILET 8 Z8 50 50 1,110 1,158 NORTH COMMONS AT VILLAGE HILL112211/14/2022 ERV-1 DESIGN ACTUAL 5 OF 18 ERV TEST REPORT PROJECT NAMEPROJECT №DATE 1/14/2022 UNIT INFORMATION DESIGNATION №ERV-2 MANUFACTURER VENTACITY SYSTEMS LOCATION ROOF MODEL №VS3000 Rte (ERV) SERVICE SOUTH VENTILATION SERIAL №L46-20-ZOE2002615-3000150832 SUPPLY EXHAUST MOTOR INFORMATION MOTOR INFORMATION MANUFACTURER N/A MANUFACTURER N/A CATALOG №N/A CATALOG №N/A HORSEPOWER N/A HORSEPOWER N/A RPM N/A RPM N/A SERVICE FACTOR N/A SERVICE FACTOR N/A POWER FACTOR N/A POWER FACTOR N/A EFFICIENCY N/A EFFICIENCY N/A FRAME N/A FRAME N/A DRIVE INFORMATION DRIVE INFORMATION MOTOR SHEAVE / BORE DIRECT DRIVE MOTOR SHEAVE / BORE DIRECT DRIVE FAN PULLEY / BORE DIRECT DRIVE FAN PULLEY / BORE DIRECT DRIVE BELTS - QTY / SIZE DIRECT DRIVE BELTS - QTY / SIZE DIRECT DRIVE SHEAVE POSITION DIRECT DRIVE SHEAVE POSITION DIRECT DRIVE CENTER TO CENTER DIRECT DRIVE CENTER TO CENTER DIRECT DRIVE TEST INFORMATION TEST INFORMATION DESIGN CFM 1,575 DESIGN CFM 1,575 CONNECTED CFM 1,575 CONNECTED CFM 1,575 MEASURED CFM 1,568 MEASURED CFM 1,616 DESIGN E.S.P.N/A DESIGN E.S.P.N/A DELIVERED E.S.P..38''DELIVERED E.S.P..69'' PLENUM S.P..0''PLENUM S.P.-.69'' DISCHARGE S.P..38''DISCHARGE S.P..0'' DESIGN FAN RPM N/A DESIGN FAN RPM N/A ACTUAL FAN RPM N/A ACTUAL FAN RPM N/A VOLTAGE-PHASE 208-3 VOLTAGE-PHASE N/A MEASURED VOLTAGE 208/207/206 MEASURED VOLTAGE N/A MOTOR AMPS RATED 10.7 MOTOR AMPS RATED N/A MEASURED AMPERAGE 2.4/2.5/2.6 MEASURED AMPERAGE N/A VFD SETTING N/A VFD SETTING N/A S.P.C.P.N/A NORTH COMMONS AT VILLAGE HILL11221 6 OF 18 AIR OUTLET TEST REPORT PROJECT NAMEPROJECT №DATE №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST SUPPLY RM. № UNIT 319 BED 1 319 1 B8 20 20 BED 2 319 2 B8 20 20 BED 3 319 3 B8 20 21 LIVING / DINING 319 4 B8 25 28 BATHROOM 319 5 Z8 25 25 BATHROOM 319 6 Z8 25 27 KITCHEN 319 7 Z6 35 29 85 85 89 81 UNIT 318 STUDIO 318 1 B8 45 45 KITCHEN 318 2 Z6 25 25 BATHROOM 318 3 Z8 20 23 45 45 45 48 UNIT 317 STUDIO 317 1 B8 45 49 KITCHEN 317 2 Z6 25 27 BATHROOM 317 3 Z8 20 22 45 45 49 49 UNIT 316 LIVING / DINING 316 1 B8 25 26 BED 316 2 B8 20 23 KITCHEN 316 3 Z6 25 25 BATHROOM 316 4 Z8 20 24 45 45 49 49 UNIT 315 LIVING / DINING 315 1 B8 25 29 BED 315 2 B8 20 21 KITCHEN 315 3 Z6 25 26 BATHROOM 315 4 Z8 20 22 45 45 50 48 UNIT 314 STUDIO 314 1 B8 45 39 KITCHEN 314 2 Z6 25 28 BATHROOM 314 3 Z8 20 22 45 45 39 50 NORTH COMMONS AT VILLAGE HILL112211/14/2022 ERV-2 DESIGN ACTUAL 7 OF 18 AIR OUTLET TEST REPORT №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST SUPPLY RM. № ERV-2 DESIGN ACTUAL UNIT 313 STUDIO 313 1 B8 45 48 KITCHEN 313 2 Z6 25 26 BATHROOM 313 3 Z8 20 24 45 45 48 50 UNIT 312 LIVING / DINING 312 1 B8 25 27 BED 312 2 B8 20 21 KITCHEN 312 3 Z6 25 25 BATHROOM 312 4 Z8 20 23 45 45 48 48 UNIT 311 LIVING / DINING 311 1 B8 25 25 BED 311 2 B8 20 21 KITCHEN 311 3 Z6 25 27 BATHROOM 311 4 Z8 20 22 45 45 46 49 UNIT 310 BED 1 310 1 B8 20 20 BED 2 310 2 B8 20 19 LIVING / DINING 310 3 B8 25 28 KITCHEN 310 4 Z6 35 38 BATHROOM 310 5 Z8 30 40 65 65 67 78 UNIT 218 BED 1 218 1 B8 20 22 BED 2 218 2 B8 20 25 BED 3 218 3 B8 20 26 LIVING / DINING 218 4 B8 25 29 BATHROOM 218 5 Z8 25 27 BATHROOM 218 6 Z8 25 25 KITCHEN 218 7 Z6 35 35 85 85 102 87 UNIT 217 LIVING / DINING 217 1 B8 25 27 BED 217 2 B8 20 22 KITCHEN 217 3 Z6 25 26 BATHROOM 217 4 Z8 20 23 45 45 49 49 8 OF 18 AIR OUTLET TEST REPORT №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST SUPPLY RM. № ERV-2 DESIGN ACTUAL UNIT 216 LIVING / DINING 216 1 B8 25 29 BED 216 2 B8 20 19 KITCHEN 217 3 Z6 25 25 BATHROOM 217 4 Z8 20 21 45 45 48 46 UNIT 215 LIVING / DINING 215 1 B8 25 31 BED 1 215 2 B8 20 24 BED 2 215 3 B8 20 24 KITCHEN 215 4 Z6 35 36 BATHROOM 215 5 Z8 30 35 65 65 79 71 UNIT 214 LIVING / DINING 214 1 B8 25 30 BED 1 214 2 B8 20 24 BED 2 214 3 B8 20 25 KITCHEN 214 4 Z6 35 38 BATHROOM 214 5 Z8 30 37 65 65 79 75 UNIT 213 LIVING / DINING 213 1 B8 25 33 BED 1 213 2 B8 20 23 BED 2 213 3 B8 20 24 KITCHEN 213 4 Z6 35 36 BATHROOM 213 5 Z8 30 39 65 65 80 75 UNIT 212 LIVING / DINING 212 1 B8 25 30 BED 1 212 2 B8 20 21 BED 2 212 3 B8 20 22 KITCHEN 212 4 Z6 35 35 BATHROOM 212 5 Z8 30 33 65 65 73 68 UNIT 211 LIVING / DINING 211 1 B8 25 27 BED 1 211 2 B8 20 25 BED 2 211 3 B8 20 26 KITCHEN 211 4 Z6 35 38 BATHROOM 211 5 Z8 30 33 65 65 78 71 9 OF 18 AIR OUTLET TEST REPORT №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST SUPPLY RM. № ERV-2 DESIGN ACTUAL UNIT 116 LIVING / DINING 116 1 B8 25 31 BED 1 116 2 B8 20 24 BED 2 116 3 B8 20 25 BED 3 116 4 B8 20 24 KITCHEN 116 5 Z6 35 39 BATHROOM 116 6 Z8 25 28 BATHROOM 116 7 Z8 25 28 85 85 104 95 UNIT 115 LIVING / DINING 115 1 B8 25 33 BED 115 2 B8 20 23 KITCHEN 115 3 Z6 25 25 BATHROOM 115 4 Z8 20 23 45 45 56 48 UNIT 114 LIVING / DINING 114 1 B8 25 33 BED 114 2 B8 20 28 KITCHEN 114 3 Z6 25 27 BATHROOM 114 4 Z8 20 23 45 45 61 50 UNIT 113 LIVING / DINING 113 1 B8 25 31 BED 1 113 2 B8 20 24 BED 2 113 3 B8 20 25 KITCHEN 113 4 Z6 35 38 BATHROOM 113 5 Z8 30 37 65 65 80 75 UNIT 112 LIVING / DINING 112 1 B8 25 30 BED 1 112 2 B8 20 26 BED 2 112 3 B8 20 24 KITCHEN 112 4 Z6 35 38 BATHROOM 112 5 Z8 30 36 65 65 80 74 10 OF 18 AIR OUTLET TEST REPORT №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST SUPPLY RM. № ERV-2 DESIGN ACTUAL UNIT 111 LIVING / DINING 111 1 B8 25 27 BED 1 111 2 B8 20 23 BED 2 111 3 B8 20 23 KITCHEN 111 4 Z6 35 36 BATHROOM 111 5 Z8 30 33 65 65 73 69 UNIT 110 LIVING / DINING 110 1 B8 25 30 BED 1 110 2 B8 20 22 BED 2 110 3 B8 20 24 KITCHEN 110 4 Z6 35 36 BATHROOM 110 5 Z8 30 31 65 65 76 67 UNIT 109 LIVING / DINING 109 1 B8 25 29 BED 1 109 2 B8 20 24 BED 2 109 3 B8 20 24 KITCHEN 109 4 Z6 35 34 BATHROOM 109 5 Z8 30 34 65 65 77 68 UNIT 108 LIVING / DINING 108 1 B8 25 26 BED 1 108 2 B8 20 23 BED 2 108 3 B8 20 25 KITCHEN 108 4 Z6 35 35 BATHROOM 108 5 Z8 30 32 65 65 74 67 11 OF 18 ERV TEST REPORT PROJECT NAMEPROJECT №DATE 1/14/2022 UNIT INFORMATION DESIGNATION №ERV-3 MANUFACTURER VENTACITY SYSTEMS LOCATION ROOF MODEL №VS3000 Rte (ERV) SERVICE NORTH VENTILATION SERIAL №L46-20-ZOE2002615-3000150830 SUPPLY EXHAUST MOTOR INFORMATION MOTOR INFORMATION MANUFACTURER N/A MANUFACTURER N/A CATALOG №N/A CATALOG №N/A HORSEPOWER N/A HORSEPOWER N/A RPM N/A RPM N/A SERVICE FACTOR N/A SERVICE FACTOR N/A POWER FACTOR N/A POWER FACTOR N/A EFFICIENCY N/A EFFICIENCY N/A FRAME N/A FRAME N/A DRIVE INFORMATION DRIVE INFORMATION MOTOR SHEAVE / BORE DIRECT DRIVE MOTOR SHEAVE / BORE DIRECT DRIVE FAN PULLEY / BORE DIRECT DRIVE FAN PULLEY / BORE DIRECT DRIVE BELTS - QTY / SIZE DIRECT DRIVE BELTS - QTY / SIZE DIRECT DRIVE SHEAVE POSITION DIRECT DRIVE SHEAVE POSITION DIRECT DRIVE CENTER TO CENTER DIRECT DRIVE CENTER TO CENTER DIRECT DRIVE TEST INFORMATION TEST INFORMATION DESIGN CFM 1,410 DESIGN CFM 1,410 CONNECTED CFM 1,510 CONNECTED CFM 1,410 MEASURED CFM 1,561 MEASURED CFM 1,420 DESIGN E.S.P.N/A DESIGN E.S.P.N/A DELIVERED E.S.P..49''DELIVERED E.S.P..46'' PLENUM S.P..0''PLENUM S.P.-.46'' DISCHARGE S.P..49''DISCHARGE S.P..0'' DESIGN FAN RPM N/A DESIGN FAN RPM N/A ACTUAL FAN RPM N/A ACTUAL FAN RPM N/A VOLTAGE-PHASE 208-3 VOLTAGE-PHASE N/A MEASURED VOLTAGE 208/207/208 MEASURED VOLTAGE N/A MOTOR AMPS RATED N/A MOTOR AMPS RATED N/A MEASURED AMPERAGE 1.7/2.0/1.9 MEASURED AMPERAGE N/A VFD SETTING N/A VFD SETTING N/A S.P.C.P.N/A NORTH COMMONS AT VILLAGE HILL11221 12 OF 18 AIR OUTLET TEST REPORT PROJECT NAMEPROJECT №DATE №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST RM. № UNIT 301 LIVING / DINING 301 1 B8 25 28 BED 1 301 2 B8 20 22 BED 2 301 3 B8 20 23 KITCHEN 301 4 Z6 35 38 BATHROOM 301 5 Z8 30 34 65 65 73 72 UNIT 302 BED 1 302 1 B8 20 26 BED 2 302 2 B8 20 21 LIVING / DINING 302 3 B8 25 20 KITCHEN 302 4 Z6 35 38 BATHROOM 302 5 Z8 30 34 65 65 67 72 UNIT 303 STUDIO 303 1 B8 45 50 KITCHEN 303 2 Z6 25 29 BATHROOM 303 3 Z8 20 25 45 45 50 54 UNIT 304 STUDIO 304 1 B8 45 42 KITCHEN 304 2 Z6 25 27 BATHROOM 304 3 Z8 20 21 45 45 42 48 UNIT 305 STUDIO 305 1 B8 45 39 KITCHEN 305 2 Z6 25 27 BATHROOM 305 3 Z8 20 15 45 45 39 42 UNIT 306 LIVING / DINING 306 1 B8 25 23 BED 306 2 B8 20 21 KITCHEN 306 3 Z6 25 29 BATHROOM 306 4 Z8 20 21 45 45 44 50 NORTH COMMONS AT VILLAGE HILL112211/14/2022 ERV-3 DESIGN ACTUAL 13 OF 18 AIR OUTLET TEST REPORT №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST RM. № ERV-3 DESIGN ACTUAL UNIT 307 LIVING / DINING 307 1 B8 25 22 BED 307 2 B8 20 20 KITCHEN 307 3 Z6 25 26 BATHROOM 307 4 Z8 20 22 45 45 42 48 UNIT 308 STUDIO 308 1 B8 45 45 KITCHEN 308 2 Z6 25 28 BATHROOM 308 3 Z8 20 23 45 45 45 51 UNIT 309 LIVING / DINING 309 1 B8 25 26 BED 309 2 B8 20 21 KITCHEN 309 3 Z6 25 26 BATHROOM 309 4 Z8 20 20 45 45 47 46 UNIT 201 LIVING / DINING 201 1 B8 25 31 BED 1 201 2 B8 20 25 BED 2 201 3 B8 20 26 BED 3 201 4 B8 20 26 KITCHEN 201 5 Z6 35 41 BATHROOM 201 6 Z8 25 32 BATHROOM 201 7 Z8 25 26 85 85 108 99 UNIT 202 LIVING / DINING 202 1 B8 25 29 BED 1 202 2 B8 20 22 BED 2 202 3 B8 20 20 KITCHEN 202 4 Z6 35 38 BATHROOM 202 5 Z8 30 33 65 65 71 71 UNIT 203 BED 1 203 1 B8 20 19 LIVING / DINING 203 2 B8 25 27 KITCHEN 203 3 Z6 25 29 BATHROOM 203 4 Z8 20 22 45 45 46 51 14 OF 18 AIR OUTLET TEST REPORT №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST RM. № ERV-3 DESIGN ACTUAL UNIT 204 BED 1 204 1 B8 20 24 LIVING / DINING 204 2 B8 25 28 KITCHEN 204 3 Z6 25 27 BATHROOM 204 4 Z8 20 20 45 45 52 47 UNIT 205 BED 1 205 1 B8 20 26 LIVING / DINING 205 2 B8 25 29 KITCHEN 205 3 Z6 25 26 BATHROOM 205 4 Z8 20 24 45 45 55 50 UNIT 206 LIVING / DINING 206 1 B8 25 25 BED 1 206 2 B8 20 21 BED 2 206 3 B8 20 24 KITCHEN 206 4 Z6 35 39 BATHROOM 206 5 Z8 30 39 65 65 70 78 UNIT 207 LIVING / DINING 207 1 B8 25 30 BED 207 2 B8 20 20 BED 207 3 B8 20 23 KITCHEN 207 4 Z6 35 38 BATHROOM 207 5 Z8 30 38 65 65 73 76 UNIT 208 LIVING / DINING 208 1 B8 25 26 BED 1 208 2 B8 20 23 BED 2 208 3 B8 20 22 KITCHEN 208 4 Z6 35 41 BATHROOM 208 5 Z8 30 36 65 65 71 77 UNIT 209 LIVING / DINING 209 1 B8 25 25 BED 209 2 B8 20 20 KITCHEN 209 3 Z6 25 27 BATHROOM 209 4 Z8 20 25 45 45 45 52 15 OF 18 AIR OUTLET TEST REPORT №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST RM. № ERV-3 DESIGN ACTUAL UNIT 210 LIVING / DINING 210 1 B8 25 24 BED 1 210 2 B8 20 19 BED 2 210 3 B8 20 23 KITCHEN 210 4 Z6 35 38 BATHROOM 210 5 Z8 30 38 65 65 66 76 UNIT 101 LIVING / DINING 101 1 B8 25 28 BED 1 101 2 B8 20 26 BED 2 101 3 B8 20 21 KITCHEN 101 4 Z6 35 42 BATHROOM 101 5 Z8 30 35 65 65 75 77 UNIT 102 LIVING / DINING 102 1 B8 25 31 BED 1 102 2 B8 20 25 BED 2 102 3 B8 20 21 KITCHEN 102 4 Z6 35 41 BATHROOM 102 5 Z8 30 24 65 65 77 65 UNIT 103 LIVING / DINING 103 1 B8 25 30 BED 103 2 B8 20 26 KITCHEN 103 3 Z6 25 33 BATHROOM 103 4 Z8 20 26 45 45 56 59 UNIT 104 LIVING / DINING 104 1 B8 25 31 BED 1 104 2 B8 20 21 KITCHEN 104 3 Z6 25 30 BATHROOM 104 4 Z8 20 26 45 45 52 56 UNIT 105 LIVING / DINING 105 1 B8 25 30 BED 1 105 2 B8 20 27 KITCHEN 105 3 Z6 25 30 BATHROOM 105 4 Z8 20 23 45 45 57 53 16 OF 18 AIR OUTLET TEST REPORT №OUTLET NOTE SIZE SUPPLY EXHAUST SUPPLY EXHAUST RM. № ERV-3 DESIGN ACTUAL UNIT 106 LIVING / DINING 106 1 B8 25 29 BED 1 106 2 B8 20 21 BED 2 106 3 B8 20 22 KITCHEN 106 4 Z6 35 33 BATHROOM 106 5 Z8 30 24 65 65 72 57 UNIT 107 LIVING / DINING 107 1 B8 25 32 BED 1 107 2 B8 20 26 KITCHEN 107 3 Z6 25 27 BATHROOM 107 4 Z8 20 25 45 45 58 52 17 OF 18 VELOCITY PRESSURE TRAVERSE REPORT PROJECT NAMEPROJECT №DATE AREA STATIC WIDTH HEIGHT FPM CFM FPM CFM PRESS. SUPPLY 16 16 1.778 624 1,110 631 1,122 .31'' EXHAUST 18 16 2.000 555 1,110 595 1,190 -.37'' SUPPLY MAIN BRANCH 16 16 1.778 780 1,387 .41'' BRANCH 1 6 Ø 0.196 465 91 .39'' BRANCH 2 6 Ø 0.196 247 48 .38'' BRANCH 3 4 Ø 0.087 235 21 .02'' BRANCH 4 4 Ø 0.087 238 21 .36'' 1,575 1,568 EXHAUST 16 18 2.000 788 1,575 808 1,616 .49'' SUPPLY 16 16 1.778 793 1,410 799 1,420 1.36'' EXHAUST 18 16 2.000 705 1,410 710 1,420 -.4'' ERV-2, 1300 CFM SETPOINT, 5% OFFSET ERV-3, 1300 CFM SETPOINT, 5% OFFSET ERV-1, 950 CFM SETPOINT, -10% OFFSET NORTH COMMONS AT VILLAGE HILL112211/6/2022 UNIT TOTALS DUCT DESIGN ACTUAL 18 OF 18