35-080 Solar test resultsUnited Power Group, Inc. Kiewit Power Constructors September 30, 2019 9701 Renner Blvd. Lenexa, KS 66219 Project Location: Northampton Solar 1010 Ryan Road Northampton Ma Scope of Work United Power Group, Inc. was commissioned to perform acceptance testing on three (3) two-winding padmount transformers, one (1) grounding transformer, one (1) metering cabinet, and five (5) sets of medium voltage cable. Transformer testing includes overall power factor, excitation on each high voltage winding, turns ratio, winding resistance, polarization index, and oil sampling. Remarks: At the conclusion of testing, it was determined that all components are in good working order and safe to energize. Please contact United Power Group, Inc. with any questions or concerns. Submitted by: Matthew Harris United Power Group, Inc Direct : 508-245-3955 Office : 508-559-1694 **Y-Y ** Winding Resistance Winding Manufacturer Serial Number Configuration Winding Temperature Temperature Rise Factory Resistance Factory Temperature Core to Earth **** Hi to Lo Guard Earth **** Lo to Earth Guard Hi **** Lo to Hi/Earth **** Hi to Earth Guard Lo **** Hi/Lo to Earth 1000.00 1980.00 3210.00 1.62 Serial #1550C * Connections Volts T1 (Mohms)T2 (Mohms)PI Insulation Resistance Core Ground Test Manufacturer Fluke * 1 CH+CHL 0.500 39.170 1.528 0.390 1 10389.941 Overall Tests Insulation Test kV mA Watts Copies Sheet #Crew Size Purchase Order Ins. Book #Duration % PF Corr. Corr Fctr Cap (pF)Manual Last Sheet #Set Bottom Serial #Travel Time Verification Date 9/27/2019 Set Top Serial #Reason Verified MH/AP Test Set Type M4000 Date Retested Tester MH/AP Work Order Date Last Tested Cloudy Air Temperature 26°C Apparatus Temperature 24°C Humidity 43 % Test Date 9/26/2019 Test Time:1:15 PM Weather kV 13.8, 0.48 VA Rating *, *, 1500, 1680, KVA Administration Oil Volume 410 UG BIL 125 kV Weight 10952 LB Mfr Location Coolant FR3 Phases Three Class ONAN Manufacturer Eaton-Cutler Hammer Configuration Y-Y Year Manufactured 2018 Tank Type N2 Blanket Division Kiewet Power Constructors Circuit Designation Nameplate - Two-winding Transformer Company United Power Group, Inc Serial Number 1950009164 Transformer A Report Source TwoWindingTransformer Session Test Date 9/26/2019 1:15:45 PM Location Northampton Solar Special ID Transformer A Report generated on 9/27/2019 7:00:23 AM 1 - 3 DETC A B C D E L Turns Ratio Tests 114.907 1011.149 L 122.137 991.7988120.659 982.964 L L 8 107.805 916.458 L 104.065 944.272 L 109.101 924.639 L 96.556 892.097 L 100.396 872.643899.170 864.239 L L 8 92.111 817.188 L 90.288 845.180 L 93.279 825.805 L 84.888 802.599 L 87.205 782.666886.038 773.655 L LTC Test kV mA Watts X mA Watts X mA Watts X Manual H1 H0/X0 H2 H0/X0 H3 H0/X0 4 4 * DETC 5 5 * DETC 2 2 * DETC 3 3 * DETC Oil Volume DETC 1 1 * Exciting Current Tests Manufacturer Type Steps Boost % *** Buck %Position Found Position Left * E C ***** E B * **** E A ***** D C * **** D B ***** D A * **** C C 360 micro Ohms **** C B 380 micro Ohms **** C A 380 micro Ohms **** B C * **** B B ***** B A * **** A C ***** A B * Calculated Resistance Correction Factor Corrected Resistance Percentage DeviationAA***** DETC LTC Phase Resistance Units **** Low Voltage E C 281.3 milli Ohms **** E B 280.7 milli Ohms **** E A 281.4 milli Ohms **** D C 288.8 milli Ohms **** D B 289.5 milli Ohms **** D A 289.4 milli Ohms **** C C 296.4 milli Ohms **** C B 296.5 milli Ohms **** C A 297.1 milli Ohms **** B C 301.7 milli Ohms **** B B 303.2 milli Ohms **** B A 303 milli Ohms **** A C 307.1 milli Ohms **** A B 308.1 milli Ohms **** A A 308.8 milli Ohms High Voltage DETC LTC Phase Resistance Units Calculated Resistance Correction Factor Corrected Resistance Percentage Deviation Report generated on 9/27/2019 7:00:23 AM 2 - 3 27.333 27.343 27.344 27.176 27.4491311048027.313 13460 480 28.042 28.088 28.094 28.091 27.901 28.182 28.763 28.768 28.766 28.606 28.8941380048028.75 14150 480 29.479 29.413 29.422 29.419 29.332 29.627 30.144 30.132 30.141 30.037 30.3381449048030.188 X3 - H0/X0 Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim Manual X1 - H0/X0 X2 - H0/X0 Wye Connections H1 - H0/X0 H2 - H0/X0 H3 - H0/X0 Wye Serial Number HV Winding LV Winding Report generated on 9/27/2019 7:00:23 AM 3 - 3 **Y-Y ** Winding Resistance Winding Manufacturer Serial Number Configuration Winding Temperature Temperature Rise Factory Resistance Factory Temperature Core to Earth **** Hi to Lo Guard Earth **** Lo to Earth Guard Hi **** Lo to Hi/Earth **** Hi to Earth Guard Lo **** Hi/Lo to Earth 1000.00 2850.00 6130.00 2.15 Serial #1550C * Connections Volts T1 (Mohms)T2 (Mohms)PI Insulation Resistance Core Ground Test Manufacturer Fluke * 1 CH+CHL 0.500 36.719 1.444 0.393 1 9739.828 Overall Tests Insulation Test kV mA Watts Copies Sheet #Crew Size Purchase Order Ins. Book #Duration % PF Corr. Corr Fctr Cap (pF)Manual Last Sheet #Set Bottom Serial #Travel Time Verification Date 9/27/2019 Set Top Serial #Reason Verified MH Test Set Type M4000 Date Retested Tester MH/AP Work Order Date Last Tested Sunny Air Temperature 24°C Apparatus Temperature 22°C Humidity 47 % Test Date 9/26/2019 Test Time:11:21 AM Weather kV 13.8, 0.48 VA Rating *, *, 1500, 1680, KVA Administration Oil Volume 410 UG BIL 125 kV Weight 10952 LB Mfr Location Coolant FR3 Phases Three Class ONAN Manufacturer Eaton-Cutler Hammer Configuration Y-Y Year Manufactured 2018 Tank Type N2 Blanket Division Kiewet Power Constructors Circuit Designation Nameplate - Two-winding Transformer Company United Power Group, Inc Serial Number 1950009166 Transformer B Report Source TwoWindingTransformer Session Test Date 9/26/2019 11:21:14 AM Location Northampton Solar Special ID Transformer B Report generated on 9/27/2019 6:48:25 AM 1 - 3 DETC A B C D E L Turns Ratio Tests 111.753 1000.492 L 117.980 985.2958115.961 964.501 L L 8 104.153 899.382 L 101.405 933.517 L 105.748 916.929 L 94.253 881.657 L 97.436 863.796896.083 848.387 L L 8 89.335 801.748 L 88.195 834.655 L 90.586 815.926 L 82.974 792.339 L 84.752 772.622883.575 759.156 L LTC Test kV mA Watts X mA Watts X mA Watts X Manual H1 H0/X0 H2 H0/X0 H3 H0/X0 4 4 * DETC 5 5 * DETC 2 2 * DETC 3 3 * DETC Oil Volume DETC 1 1 * Exciting Current Tests Manufacturer Type Steps Boost % *** Buck %Position Found Position Left * E C ***** E B * **** E A ***** D C * **** D B ***** D A * **** C C 361 micro Ohms **** C B 367 micro Ohms **** C A 370 micro Ohms **** B C * **** B B ***** B A * **** A C ***** A B * Calculated Resistance Correction Factor Corrected Resistance Percentage DeviationAA***** DETC LTC Phase Resistance Units **** Low Voltage E C 283.4 milli Ohms **** E B 283.8 milli Ohms **** E A 283.2 milli Ohms **** D C 290.6 milli Ohms **** D B 291.2 milli Ohms **** D A 291.4 milli Ohms **** C C 297.5 milli Ohms **** C B 296.9 milli Ohms **** C A 298.6 milli Ohms **** B C 304.8 milli Ohms **** B B 305.1 milli Ohms **** B A 305.6 milli Ohms **** A C 311.4 milli Ohms **** A B 311.9 milli Ohms **** A A 312.6 milli Ohms High Voltage DETC LTC Phase Resistance Units Calculated Resistance Correction Factor Corrected Resistance Percentage Deviation Report generated on 9/27/2019 6:48:25 AM 2 - 3 27.283 27.286 27.281 27.176 27.4491311048027.313 13460 480 28.042 27.993 27.985 27.999 27.901 28.182 28.753 28.755 28.746 28.606 28.8941380048028.75 14150 480 29.479 29.399 29.408 29.41 29.332 29.627 30.144 30.13 30.138 30.037 30.3381449048030.188 X3 - H0/X0 Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim Manual X1 - H0/X0 X2 - H0/X0 Wye Connections H1 - H0/X0 H2 - H0/X0 H3 - H0/X0 Wye Serial Number HV Winding LV Winding Report generated on 9/27/2019 6:48:25 AM 3 - 3 **Y-Y ** Winding Resistance Winding Manufacturer Serial Number Configuration Winding Temperature Temperature Rise Factory Resistance Factory Temperature Core to Earth **** Hi to Lo Guard Earth **** Lo to Earth Guard Hi **** Lo to Hi/Earth **** Hi to Earth Guard Lo **** Hi/Lo to Earth 1000.00 3410.00 5670.00 1.66 Serial #1550 * Connections Volts T1 (Mohms)T2 (Mohms)PI Insulation Resistance Core Ground Test Manufacturer Fluke * 1 CH+CHL 0.500 37.871 1.464 0.387 1 10045.375 Overall Tests Insulation Test kV mA Watts Copies Sheet #Crew Size Purchase Order Ins. Book #Duration % PF Corr. Corr Fctr Cap (pF)Manual Acceptance Last Sheet #Set Bottom Serial #Travel Time Verification Date Set Top Serial #Reason Verified MH/AP Test Set Type M4000 Date Retested Tester MH/AP Work Order Date Last Tested Sunny Air Temperature 21°C Apparatus Temperature 20°C Humidity 47 % Test Date 9/26/2019 Test Time:8:45 AM Weather kV 13.8, 0.48 VA Rating *, *, 1500, 1680, KVA Administration Oil Volume 410 UG BIL 125 kV Weight 10952 LB Mfr Location Coolant FR3 Phases Three Class ONAN Manufacturer Eaton-Cutler Hammer Configuration Y-Y Year Manufactured 2018 Tank Type N2 Blanket Division Kiewet Power Constructors Circuit Designation Nameplate - Two-winding Transformer Company United Power Group, Inc Serial Number 1950009165 Transformer C Report Source TwoWindingTransformer Session Test Date 9/26/2019 8:45:48 AM Location Northampton Solar Special ID Transformer C Report generated on 9/27/2019 6:26:59 AM 1 - 3 DETC A B C D E L Turns Ratio Tests 113.424 1009.298 L 119.768 985.8068120.900 991.331 L L 8 107.776 923.375 L 102.802 942.308 L 107.085 918.055 L 95.669 891.655 L 98.593 865.579895.526 890.651 L L 8 91.657 822.023 L 89.416 843.900 L 91.518 817.842 L 84.141 801.638 L 85.529 774.527885.728 778.443 L LTC Test kV mA Watts X mA Watts X mA Watts X Manual H1 H0/X0 H2 H0/X0 H3 H0/X0 4 4 * DETC 5 5 * DETC 2 2 * DETC 3 3 * DETC Oil Volume DETC 1 1 * Exciting Current Tests Manufacturer Type Steps Boost % *** Buck %Position Found Position Left * E C ***** E B * **** E A ***** D C * **** D B ***** D A * **** C C 350 micro Ohms **** C B 360 micro Ohms **** C A 380 micro Ohms **** B C * **** B B ***** B A * **** A C ***** A B * Calculated Resistance Correction Factor Corrected Resistance Percentage DeviationAA***** DETC LTC Phase Resistance Units **** Low Voltage E C 281.1 milli Ohms **** E B 280.9 milli Ohms **** E A 281.5 milli Ohms **** D C 288.1 milli Ohms **** D B 288.8 milli Ohms **** D A 289.5 milli Ohms **** C C 297.7 milli Ohms **** C B 295.2 milli Ohms **** C A 296.7 milli Ohms **** B C 302.9 milli Ohms **** B B 302.5 milli Ohms **** B A 303.8 milli Ohms **** A C 307.8 milli Ohms **** A B 307.2 milli Ohms **** A A 308.1 milli Ohms High Voltage DETC LTC Phase Resistance Units Calculated Resistance Correction Factor Corrected Resistance Percentage Deviation Report generated on 9/27/2019 6:26:59 AM 2 - 3 27.276 27.291 27.288 27.176 27.4491311048027.313 13460 480 28.042 27.997 27.999 28.004 27.901 28.182 28.686 28.715 28.751 28.606 28.8941380048028.75 14150 480 29.479 29.404 29.414 29.399 29.332 29.627 30.132 30.144 30.139 30.037 30.3381449048030.188 X3 - H0/X0 Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim Manual X1 - H0/X0 X2 - H0/X0 Wye Connections H1 - H0/X0 H2 - H0/X0 H3 - H0/X0 Wye Serial Number HV Winding LV Winding Report generated on 9/27/2019 6:26:59 AM 3 - 3 Session Notes Copies Sheet #Crew Size 1 Purchase Order Ins. Book #Duration INITIAL NEW Last Sheet #Set Bottom Serial #Travel Time Verification Date 10/1/2019 Set Top Serial #Reason Verified MH Test Set Type Date Retested Tester GM Work Order Date Last Tested Air Temperature 14°C Apparatus Temperature 14°C Humidity 44 % Test Date 9/30/2019 Test Time:8:07 AM Weather Catalog/Style Crew Size Administration Catalog #LTC Counter * Design Induction Ctrl Wire Diameter kV 13.8 Amps 63.04 Impedance 47 VA Rating * Phases Three BIL 95 kV Weight 3500 LB Oil Volume * Mfr Location USA Tank Type Select Tank Type Coolant Air (Encapsulated) Manufacturer Hammond Type Year Manufactured 2019 Class OA Location Northampton Solar Special ID Grounding Transformer #1 Division Kiewet Power Constructors Circuit Designation Nameplate - Voltage Regulator Company United Power Group Serial Number AA00732089 Neutral Grounding Transformer Report Source GroundingTransformer Session Test Date 9/30/2019 8:07:02 AM Report generated on 10/1/2019 9:47:45 AM 1 - 3 1.108 1 951.748 Good1CH8.001 3.588 0.397 % PF Corr. Corr Fctr Cap (pF)FRANKā„¢Manual Overall Tests Insulation Test kV mA Watts *****H3 3 * *****H2 2 * *****H1 1 * *****H0 4 * Bushing Nameplate Designation Serial #Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps Report generated on 10/1/2019 9:47:45 AM 2 - 3 LTC LSR mA: 85.492/85.492, 1/1 Watts: 630.935/630.935, 1/1 Cap (pF): */*, 1/1 LSR mA: 85.792/85.792, 1/1 Watts: 628.804/628.804, 1/1 Cap (pF): */*, 1/1 LSR mA: 120.375/120.375, 1/1 Watts: 905.259/905.259, 1/1 Cap (pF): */*, 1/1 X FRANKā„¢Manual 2.5 120.375 905.259 L 85.792 628.804 L 85.492 630.935 L mA Watts X mA WattsDETCTest kV mA Watts X Exciting Current Tests H1 H0 H2 H0 H3 H0 Core to Earth 0.00 *** Src/Load to Earth 5000.00 348000.00 1140000.00 3.28 Serial #* Connections Volts T1 (Mohms)T2 (Mohms)PI Insulation Resistance Core Ground Test Manufacturer * LSR mA: 3.588/3.588, 1/1 Watts: 0.397/0.397, 1/1 Cap (pF): 951.748/951.748, 1/1 Report generated on 10/1/2019 9:47:45 AM 3 - 3 (3) Metering Cabinet #1 CTs and PTs Page No. BIL Phases 3 Age kV A B C Insp.Found See 5 kV Megohms Item Dirty Remarks Phase To Ground 774000 923000 996000 Breaker Cells X Phases not under Primary Bus X Ground Bus X 5 kV Megohms A-B B-C C-A Structural Checks X Mech. Conn.X Charging Motor X Closing Springs X 425 451 448 Opening Springs X Operation Coils X Auxiliary Devices X Insulating Memb.X A B C Breaker Wiring X NA NA NA Racking Device X Heater & Lights X X 1 2 3 37 P P P Bus Test is a Go No Go Test (P = Pass) (F= Fail) Energize a Phase & Grd. All Others 66% United Power Group, Inc. SWITCHGEAR TEST AND INSPECTION REPORT CustomerKiewet Power Constructors Date 9/30/2019 Project No. Address 9701 Renner Rd Lenexa KS Air Temp.75F Rel. Humidity Owner Northampton Solar Date Last InspectionNew Address 1010 Ryan Rd. Northampton, MA Last Inspection Report No. Serial No. 95 Equipment LocationPad E Owner IdentificationMeter Cabinet #1 Switchgear Nameplate Data: ManufacturerArteche Type Metal Clad Metering Cabinet Items:& Lubed Amperes New Interrupt. Rating 15 Phase Test Data Inspection and Maintenance: Insulation Resistance Checked Cleaned test were grounded. Phase To Phase K = Number Entered Above X 1000 Contact Resistance In Microhms END TO END TEST GROUND BUS 633 GND to BLDG STEEL Phase tested Lightening Arrestors 5kV Gigohms 1 min HIPOT Tests Microamps 1 Minute Test Cubicle Wiring KV DC Bus Test Remarks: Submitted by:GM Equipment Used:DLRO, Megger MIT510/2, HIPOT 880PL (3) Metering Cabinet #1 CTs and PTs Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Rd Lenexa KS Air Temp.75F Rel. Hum.66% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd. Northampton, MA Last Inspection Report No. Equipment Location Pad E Owner Identification Meter #1 CTs Location of C.T. or P.T.Section 1 Voltage APPLIED MEASURED C.T. OR P.T.C.T. OR P.T.NAMEPLATE VOLTAGE VOLTAGE PERCENT POLARITY IDENTIFICATION SECONDARY RATIO OR OR ACCURACY TAPS CURRENT CURRENT PRIMARY SECONDARY A Phase X1-X2 100/5 10V 50.09mV OK H1 X1 B Phase X1-X2 100/5 10V 50.06mV OK H1 X1 C Phase X1-X2 100/5 10V 50.07mV OK H1 X1 desired result: 50mV Remarks Results are Satisfactory Submitted By:GM Equipment Used: F2253 United Power Group, Inc. (3) Metering Cabinet #1 CTs and PTs Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Rd Lenexa KS Air Temp.75F Rel. Hum.66% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd. Northampton, MA Last Inspection Report No. Equipment Location Pad E Owner Identification Meter #1 PTs Location of C.T. or P.T.Section 1 Voltage APPLIED MEASURED C.T. OR P.T.C.T. OR P.T.NAMEPLATE VOLTAGE VOLTAGE PERCENT POLARITY IDENTIFICATION SECONDARY RATIO OR OR ACCURACY TAPS CURRENT CURRENT PRIMARY SECONDARY A Phase X1-X2 70/1 70V 1.001V OK H1 X1 B Phase X1-X2 70/5 70V 1.001V OK H1 X1 C Phase X1-X2 70/5 70V 1.001V OK H1 X1 desired result: 1.000V Remarks Results are Satisfactory Submitted By:GM Equipment Used: F2253 United Power Group, Inc. Kiewet Power Constructors Northampton Solar Circ. Designation:Meter Cabinet #1 Type:URL-1V Arteche Insul. Type:Compound Yr. Manufactured:2019 BIL:110 kV Catalog/Style:757031070 VA Rating:500 Polarity:H1-X1 kV Rating:8400/120 Acc. Class:0.3 W,X,M,V Ratio:70/1 1. Insulation Resistance Test PT-1 Serial No. D.A. Primary to Ground, Guard Secondary at 5kV NA Megohms Megohms Primary to Secondary, Guard Ground at 5kV 13400 Megohms Megohms 1.08 Secondary to Ground, Guard Primary at 1kV 329000 Megohms Megohms 1.45 2. Insulation Resistance Test PT-2 Serial No. D.A. Primary to Ground, Guard Secondary at 5kV NA Megohms Megohms Primary to Secondary, Guard Ground at 5kV 156000 Megohms Megohms 0.11 Secondary to Ground, Guard Primary at 1kV 502000 Megohms Megohms 1.32 3. Insulation Resistance Test PT-3 Serial No. D.A. Primary to Ground, Guard Secondary at 5kV NA Megohms Megohms Primary to Secondary, Guard Ground at 5kV 16600 Megohms Megohms 1.03 Secondary to Ground, Guard Primary at 1kV 211000 Megohms Megohms 1.57 Performed By: GM United Power Group, Inc. 9/30/2019 PT Tests Manufacturer: 332000 30 Seconds NA 1 Minute 61714056 617714057 61714055 17100 14500 476000 NA 16800 662000 1 Minute 30 Seconds 30 Seconds 1 Minute NA Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Rd Lenexa KS Air Temp.75F Rel. Hum.66% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd. Northampton, MA Last Inspection Report No. Equipment Location Pad E Owner Identification General Information on Each Switch Circuit Size Size Mfr.A Ph B Ph C Ph A Ph B Ph C Ph 16 DF Remarks: Submitted By GM Equipment Used DLRO Results are acceptable. Meter Cabinet #1 Metering Cabinet #1 PT Fuses 421016 G No. 7.74 7.72 Type Mfr.Cat. No. 7.81 United Power Group, Inc. LOW VOLTAGE SWITCH TEST REPORT Switch Resistance Fuse Resistance See Switch Fuse (Microhms)(MilliOhms)Remark (4) Cables United Power Group, Inc. DIELECTRIC TEST SHEET Page No. Customer Kiewet Power Constructors Date 9/26/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.70F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Transformer Pad C Owner Identification Transformer Pad C to Transformer Pad B External Equipment Included in Test none Cable Manufacturer Okonite Insulation Resistance Test Rated Voltage 15 KV One Minute @ 5 KV Operating Voltage 13.8kV Length 350 feet Phase 1 to Ground 33,500 Megohms Age New Phase 2 to Ground 41,200 Megohms No. Cond.one per phase Phase 3 to Ground 38,700 Megohms Size 1/0 Insul. Thickness 133% - 220 mils Stabilization Time 20 sec. Insul. Type EPR Installed in Conduit Type of Test Acceptance Factory Test KV Max. Test KV 65 kV DC Test Set 800PL Serial No.P0303024 Volts Leakage Current Microamp Time Volts Leakage Current Microamp KV 1 2 3 Min.KV 1 2 3 0 KV 0 0 0 0.00 65 KV 9.0 11.5 11.0 13 KV 0.20 0.30 0.35 0.25 65 KV 8.5 10.5 10.0 26 KV 0.35 0.55 0.50 0.5 65 KV 8.0 10.0 9.0 39 KV 0.80 1.05 0.90 0.75 65 KV 7.5 9.5 8.0 52 KV 1.90 2.20 2.10 1 65 KV 7.0 9.0 7.5 2 65 KV 6.0 7.5 6.5 3 65 KV 5.0 7.0 6.0 4 65 KV 4.8 6.5 6.0 5 65 KV 4.7 6.5 5.5 6 65 KV 4.7 6.5 5.5 7 65 KV 4.7 6.5 5.0 8 65 KV 4.7 6.0 5.0 9 65 KV 4.6 6.0 4.8 10 65 KV 4.6 6.0 4.8 11 65 KV 4.6 6.0 4.8 12 65 KV 4.6 6.0 4.8 13 65 KV 4.6 5.5 4.8 14 65 KV 4.5 5.5 4.8 15 65 KV 4.5 5.5 4.8 Decay Time to 5KV 16.6 sec 16.8 sec.16.9 sec. Remarks Results are acceptable Submitted by AP Equipment Used 800PL , 5kV Megger (4) Cables United Power Group, Inc. Page No. Customer Kiewet Power Constructors Date 9/26/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.70F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Transformer Pad C Owner Identification Transformer Pad C to Transformer Pad B External Equipment Included in Test none Remarks Submitted by AP Equipment Used 800PL , 5kV Megger 0 2 4 6 8 10 12 14 MICROAMPSVOLTAGE (KV)/TIME (MIN.) CURRENT VS. VOLTAGE/TIME PLOT 1 2 3 (4) Cables United Power Group, Inc. DIELECTRIC TEST SHEET Page No. Customer Kiewet Power Constructors Date 9/26/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.70F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Transformer Pad B Owner Identification Transformer Pad B to Transformer Pad A External Equipment Included in Test none Cable Manufacturer Okonite Insulation Resistance Test Rated Voltage 15 KV One Minute @ 5 KV Operating Voltage 13.8kV Length 225ft Phase 1 to Ground 98,800 Megohms Age New Phase 2 to Ground 101,000 Megohms No. Cond.one per phase Phase 3 to Ground 108,000 Megohms Size 1/0 Insul. Thickness 133% - 220 mils Stabilization Time 10 sec Insul. Type EPR Installed in Conduit Type of Test Acceptance Factory Test KV Max. Test KV 65 kV DC Test Set 800PL Serial No.P0303024 Volts Leakage Current Microamp Time Volts Leakage Current Microamp KV 1 2 3 Min.KV 1 2 3 0 KV 0 0 0 0.00 65 KV 0.9 0.95 0.9 13 KV 0.05 0.02 0.05 0.25 65 KV 0.9 0.95 0.9 26 KV 0.12 0.08 0.09 0.5 65 KV 0.9 0.95 0.9 39 KV 0.3 0.2 0.2 0.75 65 KV 0.9 0.95 0.9 52 KV 0.35 0.25 0.29 1 65 KV 0.9 0.9 0.85 2 65 KV 0.85 0.9 0.85 3 65 KV 0.85 0.9 0.8 4 65 KV 0.85 0.85 0.8 5 65 KV 0.8 0.85 0.75 6 65 KV 0.8 0.8 0.7 7 65 KV 0.75 0.8 0.7 8 65 KV 0.75 0.75 0.6 9 65 KV 0.7 0.7 0.55 10 65 KV 0.7 0.7 0.5 11 65 KV 0.7 0.7 0.5 12 65 KV 0.7 0.7 0.5 13 65 KV 0.7 0.7 0.5 14 65 KV 0.7 0.7 0.5 15 65 KV 0.7 0.7 0.5 Decay Time to 5KV 24.6 sec.24.7 sec.24.9 sec. Remarks Results are acceptable Submitted by AP Equipment Used 800PL , 5kV Megger (4) Cables United Power Group, Inc. Page No. Customer Kiewet Power Constructors Date 9/26/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.70F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Transformer Pad B Owner Identification Transformer Pad B to Transformer Pad A External Equipment Included in Test none Remarks Submitted by AP Equipment Used 800PL , 5kV Megger 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 MICROAMPSVOLTAGE (KV)/TIME (MIN.) CURRENT VS. VOLTAGE/TIME PLOT 1 2 3 (4) Cables United Power Group, Inc. DIELECTRIC TEST SHEET Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.50F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Transformer Pad A Owner Identification Transformer Pad A to Grounding Transformer External Equipment Included in Test none Cable Manufacturer Okonite 5 Insulation Resistance Test Rated Voltage 15kV One Minute @ 5 KV Operating Voltage 13.8kV Length 70ft Phase 1 to Ground 283000 Megohms Age New Phase 2 to Ground 256000 Megohms No. Cond.one per phase Phase 3 to Ground 212000 Megohms Size 4/0 Insul. Thickness 133% @ 220mils Stabilization Time 10 sec Insul. Type EPR Installed in Conduit Type of Test Hipotronics Factory Test KV Max. Test KV 65 Test Set Hipotronics Serial No. Volts Leakage Current Microamp Time Volts Leakage Current Microamp KV 1 2 3 Min.KV 1 2 3 0 KV 0 0 0 0.00 65 KV 1.60 1.30 1.80 13 KV 0.20 0.20 0.20 0.25 65 KV 1.50 1.20 1.70 26 KV 0.30 0.25 0.30 0.5 65 KV 1.40 1.10 1.60 39 KV 0.70 0.50 0.75 0.75 65 KV 1.30 1.00 1.50 52 KV 1.10 0.80 1.30 1 65 KV 1.20 0.90 1.40 2 65 KV 1.10 0.85 1.40 3 65 KV 1.05 0.85 1.35 4 65 KV 1.05 0.80 1.35 5 65 KV 1.00 0.80 1.35 6 65 KV 1.00 0.80 1.30 7 65 KV 1.00 0.75 1.30 8 65 KV 1.00 0.75 1.30 9 65 KV 0.95 0.75 1.30 10 65 KV 0.95 0.75 1.25 11 65 KV 0.95 0.75 1.25 12 65 KV 0.95 0.75 1.25 13 65 KV 0.95 0.70 1.25 14 65 KV 0.90 0.70 1.25 15 65 KV 0.90 0.70 1.25 Decay Time to 5KV 6.7 sec 6.8 sec 6.8 sec Remarks Results are acceptable Submitted by GM Equipment Used 800PL , 5kV Megger (4) Cables United Power Group, Inc. Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.50F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Transformer Pad A Owner Identification Transformer Pad A to Grounding Transformer External Equipment Included in Test none Remarks Submitted by GM Equipment Used 800PL , 5kV Megger 0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 2 MICROAMPSVOLTAGE (KV)/TIME (MIN.) CURRENT VS. VOLTAGE/TIME PLOT 1 2 3 (4) Cables United Power Group, Inc. DIELECTRIC TEST SHEET Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.50F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Metering Cabinet Owner Identification Grounding Transformer to Metering Cabinet External Equipment Included in Test none Cable Manufacturer Okonite 5 Insulation Resistance Test Rated Voltage 15kV One Minute @ 5 kV Operating Voltage 13.8kV Length 20ft Phase 1 to Ground 262000 Megohms Age New Phase 2 to Ground 303000 Megohms No. Cond.one per phase Phase 3 to Ground 315000 Megohms Size 4/0 Insul. Thickness 133% @ 220mils Stabilization Time 10 sec Insul. Type EPR Installed in Conduit Type of Test Hipotronics Factory Test kV Max. Test kV 65 Test Set Hipotronics Serial No. Volts Leakage Current Microamp Time Volts Leakage Current Microamp KV 1 2 3 Min.KV 1 2 3 0 KV 0 0 0 0.00 65 KV 0.60 0.80 0.90 13 KV 0.10 0.10 0.10 0.25 65 KV 0.55 0.70 0.85 26 KV 0.15 0.20 0.25 0.5 65 KV 0.50 0.65 0.80 39 KV 0.20 0.35 0.40 0.75 65 KV 0.50 0.60 0.75 52 KV 0.35 0.50 0.55 1 65 KV 0.45 0.55 0.70 2 65 KV 0.45 0.50 0.70 3 65 KV 0.45 0.50 0.65 4 65 KV 0.40 0.50 0.65 5 65 KV 0.40 0.50 0.65 6 65 KV 0.40 0.50 0.65 7 65 KV 0.35 0.45 0.60 8 65 KV 0.35 0.45 0.60 9 65 KV 0.35 0.45 0.60 10 65 KV 0.35 0.45 0.60 11 65 KV 0.30 0.45 0.60 12 65 KV 0.30 0.45 0.60 13 65 KV 0.30 0.40 0.60 14 65 KV 0.30 0.40 0.55 15 65 KV 0.30 0.40 0.55 Decay Time to 5KV 5.1 sec 5.1 sec 5.2 sec Remarks Results are acceptable Submitted by GM Equipment Used 800PL , 5kV Megger (4) Cables United Power Group, Inc. Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.50F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Metering Cabinet Owner Identification Grounding Transformer to Metering Cabinet External Equipment Included in Test none Remarks Submitted by GM Equipment Used 800PL , 5kV Megger 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 MICROAMPSVOLTAGE (KV)/TIME (MIN.) CURRENT VS. VOLTAGE/TIME PLOT 1 2 3 (4) Cables United Power Group, Inc. DIELECTRIC TEST SHEET Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.50F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Metering Cabinet Owner Identification Metering Cabinet to Riser Pole External Equipment Included in Test none Cable Manufacturer Okonite 5 Insulation Resistance Test Rated Voltage 15kV One Minute @ 5 kV Operating Voltage 13.8kV Length 250ft Phase 1 to Ground 75500 Megohms Age New Phase 2 to Ground 77300 Megohms No. Cond.one per phase Phase 3 to Ground 79900 Megohms Size 4/0 Insul. Thickness 133% @ 220mils Stabilization Time 10 sec Insul. Type EPR Installed in Conduit Type of Test Hipotronics Factory Test kV Max. Test kV 56 Test Set Hipotronics Serial No. Volts Leakage Current Microamp Time Volts Leakage Current Microamp KV 1 2 3 Min.KV 1 2 3 0 KV 0 0 0 0.00 65 KV 3.30 3.50 4.30 13 KV 0.40 0.40 0.40 0.25 65 KV 3.20 3.40 4.10 26 KV 0.80 0.90 1.10 0.5 65 KV 3.10 3.30 4.00 39 KV 1.20 1.40 1.70 0.75 65 KV 3.00 3.20 3.90 52 KV 1.80 2.00 2.30 1 65 KV 2.90 3.10 3.80 2 65 KV 2.80 3.00 3.70 3 65 KV 2.70 2.95 3.60 4 65 KV 2.60 2.90 3.55 5 65 KV 2.60 2.85 3.50 6 65 KV 2.55 2.80 3.45 7 65 KV 2.55 2.80 3.40 8 65 KV 2.50 2.75 3.40 9 65 KV 2.50 2.75 3.35 10 65 KV 2.50 2.75 3.35 11 65 KV 2.45 2.70 3.35 12 65 KV 2.45 2.70 3.30 13 65 KV 2.45 2.70 3.30 14 65 KV 2.40 2.70 3.30 15 65 KV 2.40 2.65 3.30 Decay Time to 5KV 13.3 sec 13.4 sec 13.6 sec Remarks Results are acceptable Submitted by GM Equipment Used 800PL , 5kV Megger (4) Cables United Power Group, Inc. Page No. Customer Kiewet Power Constructors Date 9/30/2019 Proj. No. Address 9701 Renner Blvd, Lenexa KS Air Temp.50F Rel. Hum.40% Owner Northampton Solar Date Last Inspection New Address 1010 Ryan Rd, Northampton MA Last Inspection Report No. Equipment Location Metering Cabinet Owner Identification Metering Cabinet to Riser Pole External Equipment Included in Test none Remarks Submitted by GM Equipment Used 800PL , 5kV Megger 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 MICROAMPSVOLTAGE (KV)/TIME (MIN.) CURRENT VS. VOLTAGE/TIME PLOT 1 2 3