Loading...
Northampton Bridge ELECTRICAL SPECNorthampton Bridge Lighting Northampton, MA ELECTRICAL - 1 SECTION 260000 – ELECTRICAL PART 1 - GENERAL 3 1.1 GENERAL PROVISIONS 3 1.2 RELATED DOCUMENTS 4 1.3 SCOPE 4 1.4 RELATED WORK SPECIFIED ELSEWHERE 5 1.5 CODES, ORDINANCES AND PERMITS 5 1.6 SUBMITTALS 6 1.7 INSTALLATION OF THE WORK 7 1.8 ENVIRONMENTAL CONDITIONS 7 1.9 PROTECTION 7 1.10 QUALIFICATIONS 8 1.11 REFERENCE TO MATERIALS BY NAME 8 1.12 DRAWINGS AND SPECIFICATIONS 8 1.13 INTERPRETATION OF THE PLANS AND SPECIFICATIONS 9 1.14 ELECTRICAL SYSTEMS IDENTIFICATION 10 1.15 IDENTIFICATION OF CONDUCTORS 11 1.16 ARC FLASH HAZARD WARNING AND ENERGY REDUCING SWITCH 11 1.17 OPERATING PROCEDURE 11 1.18 TEMPORARY LIGHT & POWER 11 1.19 EQUIPMENT CLEARANCES 11 1.20 ANCHORING EQUIPMENT 11 1.21 EQUIPMENT BOLTED CONNECTIONS 12 1.22 PRELIMINARY OPERATION 12 1.23 TESTS PRIOR TO SUBSTANTIAL COMPLETION 12 1.24 VISITING THE SITE 12 1.25 DEMOLITION 13 1.26 DESIGN INTENT 13 1.27 OUTAGES 13 1.28 OPERATING INSTRUCTIONS 13 1.29 RECORD AND AS BUILT DRAWINGS 14 1.30 GUARANTEE 14 PART 2 - PRODUCTS 15 2.1 WIREWAYS 15 2.2 RACEWAYS AND WIRING SYSTEMS 15 2.3 CONDUCTORS 16 2.4 PULL BOXES 17 2.5 BOXES AND FITTINGS 17 2.6 JUNCTION BOXES 17 2.7 SUPPORTING DEVICES 17 2.8 DISCONNECT SWITCHES 18 2.9 WIRING DEVICES AND PLATES 18 2.10 SURGE SUPPRESSION UNIT AT SERVICE ENTRANCE 19 2.11 SURGE SUPPRESSION FOR COMMUNICATIONS 22 2.12 MAIN PANELBOARD 22 2.13 LIGHT FIXTURES 22 2.14 CLIMATE CONTROLLED CABINET 25 2.15 DATA SYSTEMS 25 Northampton Bridge Lighting Northampton, MA ELECTRICAL - 2 2.16 RELAYS 26 2.17 VIBRATION ISOLATION AND SEISMIC RESTRAINTS 27 2.19 PAINTS AND COATINGS 29 2.20 COMPOSITE WOOD AND AGRIFIBER 30 2.21 ADHESIVES AND SEALANTS, 30 PART 3 - EXECUTION 31 3.1 MECHANICAL EQUIPMENT 31 3.2 WORKMANSHIP 31 3.3 GROUNDING 32 3.4 INSTALLATION OF CONDUITS AND FITTINGS 35 3.5 OUTLET AND JUNCTION BOXES 38 3.6 REQUIREMENTS GOVERNING ELECTRIC WORK IN DAMP OR WET LOCATIONS WITHIN BUILDING CONFINES 38 3.7 TESTS 39 3.8 LIGHTING FIXTURES 39 3.9 JUNCTION BOXES FEEDING LIGHT FIXTURES 40 3.10 JUNCTION BOXES FOR HOMERUNS 40 3.11 FIRESAFING AND SMOKE SEAL 40 3.12 SPLICES 41 Northampton Bridge Lighting Northampton, MA ELECTRICAL - 3 SECTION 260000 – ELECTRICAL PART 1 - GENERAL 1.1 GENERAL PROVISIONS A. The drawings and conditions of the Contract, including General and Supplementary Conditions, and all Division 1 sections, apply to the work of this Section. Work to be done under this Section is shown on the contract drawings listed at the front of the specifications. The listing of Contract drawings and Specifications shall not limit the Sub-Contractors responsibility to determine the full extent of his work as required by all Contract drawings and Specifications. B. Time, manner and requirements for bidding filed sub-bids 1. Sub-bids for work under this Section shall be for the complete work and shall be filed in a sealed envelope with the Awarding Authority at a time and place as stipulated in the “NOTICE TO CONTRACTORS” a The following shall appear on the upper left hand of the envelope: b NAME OF SUB-BIDDER: ____________________________ c NAME OF PROJECT: _______________________________ d SUB-BID FOR SECTION: 260000 – ELECTRICAL ____ 2. Each sub-bid submitted for work under this Section shall be on forms furnished by the Awarding Authority, as required by Section 44F of Chapter 149 of the General Laws, as amended. Sub-Bid forms may be obtained at the office of the Awarding Authority or Architect, or may be obtained by written request. 3. Sub-bids filed with the Awarding Authority shall be accompanied a by a BID BOND or CASH or CERTIFIED CHECK or a TREASURERS or CASHIERS CHECK issued by a responsible bank or trust company payable to the (insert Owner’s name) in the amount of 5 percent of the bid. A sub-bid accompanied by any other form of bid deposit than those specified will be rejected. C. Sub-sub-bid Requirements: 1. The Sub-Bidder shall list in Paragraph E of the FORM for SUB-BID the name and bid price of each person, firm or corporation performing each class of work or part thereof for which (the Section of the Specifications for that sub-trade) requires such listing; provided that, in the absence of a contrary provision in the Specifications, any Sub-Bidder may, without listing any bid price, list his own name in said paragraph E for any such class of work or part thereof and perform that work with persons on his own payroll, if such Sub-Bidder, after Sub-Bid openings, shows to the satisfaction of (insert Owner’s name) that he does customarily perform such class of work or the part thereof with persons on his own payroll and is qualified so to do. This Section of the Specifications requires that the following classes of work shall be listed in Paragraph E under the conditions indicated herein. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 4 1.2 RELATED DOCUMENTS A. The GENERAL DOCUMENTS, as listed on the Table of Contents, and applicable parts of Division 1, GENERAL REQUIREMENTS, shall be included in and made a part of this Section. B. If an item or material of this trade is indicated in the drawings but not specifically listed in this Section, provide such item or material at a standard of quality equal to the standard established for the balance of the Work Specified, in accordance with the Architect’s interpretation. C. In case of an inconsistency between Drawings and Specifications, or within either Document not clarified by addendum, the better quality or greater quantity of Work shall be provided, in accordance with the Architect’s interpretation. (See Article One of the general and Supplementary General Conditions.) D. The word `provide’ used elsewhere in these specifications or on the drawings shall be taken to mean furnish, move into place, install and connect (wire). Refer to ‘INTERPRETATION OF THE PLANS AND SPECIFICATIONS.’ 1.3 SCOPE A. The Contractor under this section shall furnish all labor, materials, appliances and equipment necessary to perform all electrical work, complete in strict accordance with this section of the specifications and applicable drawings and subject to the terms and conditions of the contract. All equipment and materials shall be new. B. The work referred to under this division includes all labor, materials and equipment, rigging, and transportation for the satisfactory installation and completion of all work referred to herein and/or as may be shown on the contract drawings and not specifically mentioned in this division. C. The following schedule is part, but not necessarily all-inclusive, of the items in this division of the contract: 1. Furnish and install new electric service including Secondary system conduits and conductors from the pole, main panelboard, and new grounding system. 2. The owner will pay all utility company charges. 3. Furnish and install new main panel, SPD device, meter socket, and Circuit Breakers. 4. Furnish and install new Panelboards complete with Circuit Breakers. 5. Furnish and install new feeders and branch circuits. 6. Furnish and install new junction boxes and pull boxes. 7. Furnish and install new light fixtures, power supplies, controllers, gateways, etc. 8. Furnish and install new wiring devices, wall plates and branch circuit wiring. 9. Furnishing, installation and connections of all lighting fixtures and lamps, including contactors, time switches and other required control equipment as shown on the drawings. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 5 10. Make final connections of power and/or control wiring as required by existing equipment. 11. Furnish and install new Data outlets with conduits and pull wires. 12. Furnish and install Heavy duty fused safety switches. Switches shall be Nema-1 for indoor applications and Nema-3R for outdoor applications. 13. Furnish and install a climate controlled NEMA 3R enclosure for the lighting controls. 14. Furnish and install a new NEMA 3R enclosure for the new main panel. 15. Provide all sleeves, hangers, supports, inserts, anchors, bolts, etc., required for the installation of this work 16. Calculations for lighting substitutions. Provide all required lighting calculations for review and approval by the engineer to conform with the basis of design. 17. Temporary light and power service, lighting outlets, lamps, receptacles, and wiring for construction lighting and power 18. Test of all electrically operated equipment. 19. Guarantee D. The above list is given to acquaint the contractor with the general phase of the work included, but it is not intended to cover all items which are described hereinafter. All of the work of the Contractor shall be complete and in accordance with the true intent and meaning of the drawings and specifications. 1.4 RELATED WORK SPECIFIED ELSEWHERE A. The following items of work, associated with the electrical work, will be performed in accordance with other sections of these specifications. 1. Excavation, and backfill, except as hereinafter specified. 2. All cutting, patching, preparation and painting of finish work 3. Any drilling of holes through walls, floors or structural members 4. The Mechanical Contractors shall furnish all of their equipment complete and ready for wiring by the Electrical Subcontractor, complete with wiring diagrams where applicable - Section 230000 B. The electrical contractor shall provide all work as described in the following sections: 1.5 CODES, ORDINANCES AND PERMITS A. Comply with all codes and ordinances applying to this work. Bidders shall inform themselves of Code requirements. In case of conflict between the contract documents and a governing code or ordinance, the higher standard shall govern. B. All permits and fees required shall be obtained and paid for by the Electrical Subcontractor. C. Particular attention is directed to: Northampton Bridge Lighting Northampton, MA ELECTRICAL - 6 1. State of Massachusetts 2020 Electric Code. 2. Local Electric Wiring Ordinance. 3. National Fire Protection Organization. 4. Requirements of City of Northampton. 1.6 SUBMITTALS A. Submit shop and erection drawings and descriptive and supportive literature for all work in accordance with the General Conditions. Approval by the Architect/Engineer must be obtained prior to delivery of materials to the site. B. No fabrications, ordering, delivery to the site or other steps shall be taken with respect to those items requiring shop drawings or manufacturer's detail drawings to be submitted or submittals of information for review, all to the Architect, until returned such to the submitter carrying either the notation "Approved" or "Approved as Corrected" as indicated by the Architect or his Engineer. An "Approved as Corrected" notation means that changes as indicated must be incorporated or the qualifying acceptance will be considered void. C. Corrections or comments made on the shop drawings during the review do not relieve the Contractor of his responsibility to comply with the requirements of the drawings and specifications. This review is only to check for general conformance with the design concept of the project and general compliance with the Contract Documents. The Contractor remains responsible for: Confirming and correlating all dimensions and quantities; selecting fabrication processes and techniques of construction; coordinating the work of the trades; and performing the work in a safe and satisfactory manner. D. Shop drawings listing various manufacturers to be considered subject to availability are not acceptable and will be rejected. E. Within thirty (30) days of award of contract this Subcontractor shall submit for the Architect/Engineer's approval, six (6) copies of the manufacturer's shop drawings, clearly high lighting each item with types, sizes, catalog numbers etc., detail prints, and data sheets for the following items: 1. Main panel complete with all Circuit Breakers, SPD, meter socket, rating, etc. 2. Panel boards and Circuit Breakers. 3. Conduits and conductors. 4. Light fixtures. Each fixture shall clearly indicate the load of the fixture including the driver and the led array to be installed measured in Watts. Any fixtures without this information will be rejected. 5. Heavy Duty Disconnect switches. 6. Wiring devices. 7. Lighting controls and power supplies. 8. Underground pull boxes with covers. 9. Low emitting Adhesives and Sealants. VOC levels must be indicated on the manufacturer’s literature. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 7 10. Low emitting Fire Stopping and Smoke Sealing. VOC levels must be indicated on the manufacturer’s literature. 11. Low emitting Paints and Coatings. VOC levels must be indicated on the manufacturer’s literature. 12. Low emitting Composite wood. Manufacturer’s literature must state that no added urea formaldehyde is used in the product. 1.7 INSTALLATION OF THE WORK A. Examine the site and all the drawings before proceeding with the layout and installation of this work. B. Verify all conditions and measurements in the field. C. It is not the intention of the drawings to show every item, piece of equipment, and detail to provide complete operating systems. D. Install work as closely as possible to layouts shown on drawings. Modify work as necessary to meet job conditions and to clear other equipment. Consult Architect before making changes, which affect its function or appearance of systems. E. Dimensions, elevations and locations are shown approximately. Verify measures in field. F. Architect reserves the right to order changes in layout of such items as switches, fixtures and outlets if such changes do not substantially affect costs and if affected items have not been fabricated or installed. G. In some cases, drawings are based on products of one manufacturer, as listed on the drawings and specifications. Contractors shall be responsible for modifications made necessary by substitution of products of other manufacturers. H. Coordinate work with work specified in other sections. Relocate work if required for proper installation and functioning of other systems. I. Install products in accordance with manufacturers’ instructions. Notify Architect if contract documents conflict with manufacturers’ instructions. Comply with Architect’s interpretations. J. Provide brackets, supports, anchors, and frames required for installation of work specified in this division. K. Do not install part of a system until all critical components of the system and related system have been approved. Coordinate parts of system. 1.8 ENVIRONMENTAL CONDITIONS A. Tools, Scaffolding, Etc: All necessary tools, machinery, scaffolding and transportation for completion of this contract shall be provided by the Electrical Contractor. B. Waste Material: All rubbish created by the Electrical Contractor shall be removed by the Electrical Contractor. 1.9 PROTECTION A. The Electrical Contractor shall, at all times, fully protect his work and materials from injury or loss to others. Any injury or loss, which may occur, shall be made Northampton Bridge Lighting Northampton, MA ELECTRICAL - 8 without expense to the Owner. The Electrical Contractor shall be responsible for the proper protection of his materials until the building is accepted by the Owner. 1.10 QUALIFICATIONS A. Materials and workmanship shall be the best of their respective kinds and in full accordance with the most modern construction methods. Electrical materials and equipment of types, for which there are Underwriters Laboratories Standards, shall conform to their requirements and be so labeled. 1.11 REFERENCE TO MATERIALS BY NAME A. Specific reference in the specification, or on contract drawings, to any article, device, product, material, fixture, form, or type of construction, etc., by name, make or catalog number shall be interpreted as establishing a standard of quality, and shall not be construed as limiting the competition. The Contractor may at his option use any article, device, product, material, fixture, form or type of construction which, in the judgment of the Architect/ Engineer, is equal to that named. Approval for any manufacturer's product not specifically mentioned shall be obtained as described below. B. If the Contractor intends to provide equipment, products or materials by an alternate manufacturer not listed as an equal, the alternate manufacturer must be approved by the Engineer prior to the close of bidding. An Addendum will be issued to allow all bidders the opportunity to bid using approved alternate manufacturers. Equipment cuts of "both" the specified manufacture and the alternate manufacture shall be provided to the Engineer by the Electrical Contractor. The above cuts shall be in the possession of the Engineer a minimum of ten days prior to the close of bids. The Engineer reserves the right to reject any submittals of alternate manufacturers if the above provisions are not complied with "in full". 1.12 DRAWINGS AND SPECIFICATIONS A. The Electrical Contractor shall refer to the drawings for a full comprehension of the work to be done and for conditions affecting the locations and placements of his equipment and materials. These drawings are intended to be supplementary to the specifications, and any work indicated, mentioned or implied in either is to be considered as specified by both. Should the character of the work herein sufficiently explained in the specifications or drawings, the Electrical Subcontractor may apply to the Architect/Engineer for further information and shall conform to such when given as it may be consistent with the original intent. The Architect/Engineer reserves the right to make any reasonable changes in location prior to installation at no expense to the Owner. All items are diagrammatic and exact locations are subject to the approval of the Architect/Engineer. B. It is intended that outlets shall be located symmetrical with architectural elements notwithstanding the fact the locations shown on the drawings may be distorted for clearness in representation.. C. Discrepancies between different drawings, between drawings and actual field conditions or between drawings and specifications, affecting the progress of the work, shall be promptly brought to the attention of the Owner’s representative for Northampton Bridge Lighting Northampton, MA ELECTRICAL - 9 decision, and all work on affected areas shall be stopped, subject to resolution of the conflict. 1.13 INTERPRETATION OF THE PLANS AND SPECIFICATIONS A. As used in the plans and specifications for electrical work, certain non-technical words shall be understood to have specific meanings as follows regardless of indications to the contrary in the general conditions or other documents governing the electrical work. 1. "Furnish" Purchase and deliver to the project site complete with every necessary appurtenance and support, all as part of the electrical work. Purchasing shall include payment of all sales taxes and other surcharges as may be required to assure that purchased items are free of all liens, claims or encumbrances. 2. "Install" Unload at the delivery point at the site and perform every operation necessary to establish secure mounting and correct operation at the proper location in the project, all as part of the electrical work. 3. "Provide" "Furnish" and "Install". 4. "New" Manufactured within the past two years and never before used. 5. "Area Served" The physical location in the building where the wiring device, lighting fixture or utilization equipment is located. 6. "Homerun" The run of conduit and wire between the panelboard overcurrent device and the 1st wiring device, lighting fixture or utilization equipment served by the branch circuit. B. Except where modified by a specific notation to the contrary, it shall be understood that the indication and/or description of any electrical item in the plans or specifications for electrical work carries with it the instruction to furnish, install and connect the item as part of the electrical work, regardless of whether or not this instruction is explicitly stated. C. It shall be understood that the specifications and plans for electrical work are complimentary and are to be taken together for a complete interpretation of the electrical work except those indications on the plans, which refer to an individual element of work, take precedence over the specifications where they conflict with same. D. To the extent that they govern the basic work, the specifications also govern change order work. E. The plans for electrical work utilize symbols and schematic diagrams which have no dimensional significance. The work shall, therefore, be installed to fulfill the diagrammatic intent expressed on the electrical plans, but in conformity with the dimensions indicated on the final working plans, field layouts and shop plans of all trades. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 10 F. Certain details appear on the plans for electrical work which are specific with regard to the dimensioning and positioning of the work. These are intended only for general information purposes. They do not obviate field coordination for individual items of the indicated work. G. Information as to general construction and architectural features and finishes shall be derived from the plans and specifications only. H. The use of words in the singular shall not be considered as limiting where other indications denote that more than one item is referred to. I. Ratings of devices, materials and equipment specified without reference to specific performance criteria shall be understood to be nominal or nameplate ratings established by means of industry standard procedures 1.14 ELECTRICAL SYSTEMS IDENTIFICATION A. All equipment shall be identified by means of laminated, engraved plastic nameplates, attached to equipment with screws. Lettering shall be ½” high for equipment nameplates and ¼” high for circuit nameplates. B. Voltage description of equipment labels. 120 through 240-volt gear shall have white letters on black labels; communication system equipment shall have black letters on white labels; devices connected ahead of main switch shall be so identified with white letters on red label. C. Nameplate schedule shall be submitted with all shop drawings for approval. D. Equipment nameplates shall state name and designation of equipment, voltage, phase, number of wires, and source (where project is supplied from two primary sources). E.g. Main Switchboard – IMS 120/208 volt, 3 phase, 4 wire Line A E. Switchboards and motor centers shall have each component similarly identified including meters, switches and/or breakers, and controls. Nameplate for distribution devices shall identify equipment served by name and designation. (e.g. `Toilet exhaust fan – EL’). F. Panelboards in public areas shall have nameplates inside doors. Panelboards shall have neatly typewritten schedules, indicating number and type of outlets and location for each circuit, behind clear plastic. G. Each individual transformer, switch, breaker, contactor, time switch or other separately mounted device shall be similarly identified with nameplate identifying equipment and/or equipment controlled and the source of power. H. At all fusible devices, either individually mounted or part of gear, provide a printed label (as supplied by fuse manufacturer) inside each switch cover, indicating specific type of fuse required for replacement. I. All 120/208V-3Ø-4W conduits shall be color coded. Conduits shall be color coded by taping or painting conduits every 12’ with a color band 3” wide with the color black. All junction box covers shall be painted Black. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 11 J. All data conduits shall be color coded. Conduits shall be color coded by taping or painting conduits every 12’ with a color band 3” wide with the color blue. All junction box covers shall be painted Blue. 1.15 IDENTIFICATION OF CONDUCTORS A. Provide permanent tags to all conductors at terminations, connections and splice points and intermediate pull boxes to provide identification for future use. B. All conductors # 4 AWG and larger shall be identified with colored tape. Colors are as follows: 120/208 Volts Black - Phase A Red - Phase B Blue - Phase C White – Neutral Green - Ground C. Branch circuits # 6AWG or smaller shall be identified by means of color-coded insulation. 1.16 ARC FLASH HAZARD WARNING AND ENERGY REDUCING SWITCH A. Arc Flash Hazard Warning - Provide calculations for and labeling on all new switchboards, switchgear, panelboards, industrial control panels, meter socket enclosures and motor control centers that are likely to require examination, adjustment, servicing or maintenance while energized shall be field or factory marked to warn qualified persons of potential electric arc flash hazards. The marking shall be in accordance with code. B. All circuit breakers rated 1200A or larger shall be supplied with and Energy reducing maintenance switch with local status indicator to comply with code. 1.17 OPERATING PROCEDURE A. The Electrical Subcontractor shall at all times have a foreman on the project authorized to make decisions and receive instructions exactly as of the Electrical Subcontractor himself were present. The foreman or superintendent shall not be removed or replaced without the express approval of the Architect/Engineer after construction work begins. 1.18 TEMPORARY LIGHT & POWER A. See General Conditions for description of temporary light and power. 1.19 EQUIPMENT CLEARANCES A. Deliver equipment knocked down if necessary. B. Install equipment with adequate clearances for maintenance and operation. 1.20 ANCHORING EQUIPMENT A. All floor-mounted equipment shall be securely anchored to the floor with sufficient anchors to resist a horizontal force equal to the weight of the equipment. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 12 B. All floor-mounted equipment 6 feet or more in height shall be anchored to the wall near the top of the equipment, if mounted against the wall with sufficient anchors to resist a horizontal force equal to the weight of the equipment. 1.21 EQUIPMENT BOLTED CONNECTIONS A. Before energizing switchboards, panelboards, disconnect switches etc., the Contractor shall tighten or retighten all accessible bolts in the electrical conductive paths using a torque device to the torque recommended by the manufacturer. If manufacturers torque values are not indicated, use those specified in UL 486A and UL 486B. 1.22 PRELIMINARY OPERATION A. Operate electrical systems with required supervision for at least two full days prior to substantial completion. Make necessary adjustment, and check proper operation. B. The Owner reserves the right to operate portions of the electrical system on a preliminary basis without voiding the guarantee or relieving the Contractor or his responsibility. 1.23 TESTS PRIOR TO SUBSTANTIAL COMPLETION A. All wiring and connections shall be tested for continuity, grounds and short circuits before the fixtures, devices and equipment are connected. B. Upon completion of the work, the Contractor shall make any tests necessary to satisfy the Owner and the Architect or his representative that the true intent and meaning of the drawings and specifications has been carried out. Contractor shall provide all instruments and labor necessary to make such tests. Such tests shall include voltage tests at incoming service and at every panel and switchboard. Any work showing faults under test, and any work not in accordance with the specifications shall be made good by the Contractor at his own expense. C. Tests shall be attended by representative of Electrical Subcontractor, equipped with instruments required to demonstrate proper functioning of systems, as specified. Demonstrate the following: 1. Equipment installed and operating in accordance with manufacturer’s specifications and instructions and with these specifications. 2. Safety controls operating as specified. 3. Motors equipped with proper overload protection and not operating under overload. Obtain ammeter readings. 4. Submit report in triplicate listing system tested, date, results and description of fault corrections, if any 1.24 VISITING THE SITE A. Bidder is advised to visit the site and acquaint himself with the working conditions. The Contractor shall accept conditions as they exist on Bid date. Claims for labor and material required for difficulties encountered, which could have been foreseen had an examination been made, will not be recognized. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 13 B. The contractor shall notify the Architect immediately of any existing field conditions not compensated for in the contract drawings and/or specifications. 1.25 DEMOLITION A. The contractor shall remove all equipment, outlets, wiring and devices made obsolete by the work of this contract. B. Where wiring devices are removed and outlets downstream are de-energized the contractor shall provide all conduit and wiring required to re-energize outlets de- energized by demolition. C. The contractor shall dispose of all equipment, lamps, etc… in an approved manner and in conformance with all applicable codes and standards. 1.26 DESIGN INTENT A. The project consists of 2 phases, the Rail Trail bridge work is Phase 1 and Bridges 1, 2 and 3 are Phase 2. All lighting controls gateway, controller, Pharos and POE switch shall be furnished and installed as part of Phase 1 work. B. The contractor shall provide all underground Phase 2 conduits from the new control panel and the main panel as part of Phase 2 work. C. Provide a new electrical service and a climate-controlled cabinet for the lighting controls as part of Phase 1. 1.27 OUTAGES A. All outages shall be coordinated with the owner. A written two week notice shall be given to the owner indicating what feeders and branch circuits that will be de- energized and the approximate length of the outage. All outages shall be done on premium time during the hours of 12PM and 5AM. B. All new work shall be installed to the extent possible prior to any outages to minimize the outage duration. 1.28 OPERATING INSTRUCTIONS A. At the time of final acceptance, the Electrical Subcontractor shall submit four (4) sets of operating instructions and maintenance manuals for all equipment. Major systems shall be tabbed separately into individual sections, (ie Lighting, Fire Alarm, Panelboards, etc.). The manuals shall include a copy of all system and component guarantees that exceeds one year (ie Ballast guarantee’s, light fixture emergency batteries, etc.). Manual shall include a typed parts source list for all equipment that will need to be replaced as a part of regular maintenance (ie Lamps, ballasts, fuses, etc.). A typed letter from the installing contractor of the beginning and ending date of the guarantee of the work of this project. The start date of the guarantee shall be from final acceptance of the project or when the system(s) major components have been installed, inspected, approved and are fully operational. B. The Electrical Subcontractor shall instruct Owner’s representative in the operation of all electrical systems. C. The contractor shall provide a schedule and instructions for preventative maintenance of all items requiring same. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 14 1.29 RECORD AND AS BUILT DRAWINGS A. Provide and keep up-to-date a complete as-built set of blue line prints. Correct daily to show every change from the original drawings and specifications including the size and kind of equipment, panel schedules, lighting fixture schedule, and runs of all conduits including dimensional location of all underground runs, and all addenda and/or change orders. Prints for this purpose may be obtained from the Architect. Keep this set of drawings on the work and use only as a record set. B. Submit Record drawing prints to the Engineer for review prior to submission of `As Built’ drawings. Prepare "As-built" drawings in Latest AutoCad version. The "As-built" drawings shall incorporate all corrections and comments made by the Electrical Engineer on the Record drawings and be submitted to the Electrical Engineer for final approval. After acceptance of the `As Built’ drawings the contractor shall submit 3 copies of the approved "As-built" drawings to the Architect along with the CD Rom. Provide drawings on a CD Rom in accordance with Section 01000 Basic Requirements. 1.30 GUARANTEE A. The Electrical Subcontractor shall and hereby does warrant that all work executed and all equipment furnished under this section shall be free from defects of workmanship and materials for a period of one (1) year from date of final acceptance of this work. The Electrical Subcontractor further agrees that he will, at his own expense, repair and replace all such defective work and all other work damaged thereby, which becomes defective during the term of the Guarantee Warranty. B. In addition to the guarantees called for under this specification and the requirements of the "General Conditions", and "Basic Requirements", the Contractor shall guarantee his work as follows: C. For factory-assembled equipment and devices on which the manufacturers furnish standard published guarantees as regular trade practice, the Contractor shall obtain such guarantee and/or warranty, and deliver same to the Owner, along with operating manuals required under other paragraphs of the specifications. D. LED lighting fixture drivers and lighting Arrays shall be guaranteed for a minimum of five (5) years, after final acceptance of project, for material and labor. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 15 PART 2 - PRODUCTS 2.1 WIREWAYS A. Wireways shall be made to accommodate conductors as required in accordance with applicable rules of the National Electric Code. To be of code gauge steel and supported as required by Code. B. Wireways may not be installed above a panelboard to route multiple branch circuits through down to the panelboard in larger conduits, regardless is they are 24" in length or less. 2.2 RACEWAYS AND WIRING SYSTEMS A. Electrical Metallic Tubing (EMT) may be run where exposed or where concealed in masonry. EMT shall be electro-galvanized and meet A.N.S.I. standards. Minimum size shall be ½”. Couplings and connector shall be threadless-type specifically designed for the purpose. Exposed raceway shall be run parallel to and at right angles to building features. Raceway shall be continuous from outlet to outlet. Pull or junction boxes shall be furnished and secured as required by building construction. Electrical Metallic Tubing (EMT) shall be cold rolled tubing with a zinc protective coating on the outside and a zinc enamel or equivalent corrosion resistant coating on the inside. All EMT shall meet UL-797 and shall be labeled accordingly. Fittings shall be steel and shall be either two screw set screw type or compression type. Setscrew fittings shall only be used in areas not prone to damage and areas inaccessible to general public. All Security System and Fire Alarm System raceways shall use compression type fittings. All connectors shall be provided with insulated throats. All raceway shall be run parallel to and at right angles to building features. Approved manufactures are Republic, Triangle, Allied Tube or approved equal. B. Liquid tight flexible metal raceway shall be used for final connections to operating or vibrating equipment, and for connections to equipment requiring adjustment in position. Provide green wire for bonding. Liquid-tight flexible conduit shall be interlocked zinc coated steel construction, with a sunlight and mineral oil resistant PVC jacket and shall comply with UL360. Maximum length shall be 6’. Provide a separate ground conductor in each length of flexible steel conduit regardless of length. Provide separate bond wire where integral conductor is not available. Fittings shall be steel, liquid-tight. Seal and ground conduit and comply with NEMA FB1. Use Anaconda, Electro-Flex, Flexi-Guard or approved equal. C. Rigid metal conduit shall be used in areas subject to corrosion, as required by Code, from pad mounted transformer to new switchboard and as indicated. Rigid steel conduit and conduit fittings shall be hot dipped galvanized steel with factory galvanized threads. They shall be steel and shall have a protective zinc coating applied both inside and outside by means of hot dip galvanizing. The conduit shall comply with ANSI C80.6 and UL1242 standards. The conduit shall be delivered with caps to protect threads. No running threads shall be permitted. Fittings shall be threaded steel and shall have a protective zinc coating applied both inside and outside by means of hot dip galvanizing. All fittings shall conform to UL8 and shall be labeled accordingly. Split couplings and threadless couplings shall only be used in renovation applications and shall be approved by the Engineer. Provide insulated throat bushings on all ends. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 16 D. Flexible metallic conduit shall be interlocked zinc coated steel construction and shall comply with UL1. Maximum length used shall be 6’. Install a separate ground conductor in each length of flexible steel conduit regardless of length. Fittings shall be malleable iron and shall comply with NEMA FB1, Conduit shall be manufactured by Alflex Triangle, Fourslide or approved equal. Fittings shall be manufactured by Tomic or equal. Fittings which use a screw to bind against the tubing will not be accepted. E. Intermediate metallic conduit shall be steel and shall have a protective zinc coating applied both inside and outside by means of hot dip galvanizing. The conduit shall comply with ANSI C80.6 and UL1242 standards. The conduit shall be delivered with caps to protect threads. No running threads shall be permitted. Fittings shall be threaded steel and shall have a protective zinc coating applied both inside and outside by means of hot dip galvanizing. All fittings shall conform to UL8 and shall be labeled accordingly. Split couplings and threadless couplings shall only be used in renovation applications and shall be approved by the Engineers. Provide insulated throat bushings on all ends. F. Rigid nonmetallic conduit shall be either schedule 40 or Schedule 80 PVC and shall comply with UL651. In underground installations transition rigid nonmetallic conduit to rigid steel conduit within 5’ of building including stub up. Provide a 3” wide metallic warning tape stating “Danger – Buried Electric” 12” below grade directly above all buried PVC ductbanks. Fittings shall be provided by the same manufacturer that supplies the conduit and shall be installed using manufacturer approved cement solvent. All elbows shall be long sweep PVC coated rigid steel conduit. G. A ground wire shall be provided in all conduit runs. The ground conductor shall be sized in accordance with code or larger as may be indicated on the contract documents. H. All branch circuits shall be provided with a dedicated neutral. No multi wired branch circuits shall be installed. I. Type “BX” cables shall not be allowed. J. Refer to `Installation Of Conduits And Fittings’ in part 3 of these specifications for installation requirements of all conduits. 2.3 CONDUCTORS A. All conductors shall be soft-drawn copper, and shall have a conductivity of not less than 98% of the USASI standard annealed copper, shall be smooth and true and of cylindrical form and shall be within 1% of the actual size called for. All conductors shall bear the markings of the Underwriter's Laboratories, the AWG size, the type insulation, maximum permissible voltage, the manufacturer's name and trade mark. Minimum insulation voltage rating shall be 600 VAC at 75 degrees B. For power and lighting systems, no wire smaller than #12 AWG shall be used. C. All feeder cables shall be type `THW’ or “XHHW-2” and shall be insulated for 600 volts. D. Branch circuit wiring in raceway shall be type “THHN”, “THWN”, and shall be insulated for 600 volts color-coded over its entire length. E. Conductors #12 AWG and smaller shall be solid. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 17 F. Conductors #10 AWG and larger shall be stranded. G. Lighting circuit conductors in fixture raceways shall be #12 AWG minimum, higher than minimum shall be as per plan, Type AVA, AVB, AWM, FE or equal as approved. H. Approved solderless fittings shall be used at all joints and terminals. I. All special system wiring shall be of a type and size as indicated by manufacturer for equipment. J. Wire and cable to be by General Electric, Okonite, or approved equal. 2.4 PULL BOXES A. In general, and where applicable, specifications for pull boxes shall be same as for junction boxes. Pull boxes shall be installed as indicated on the plans and wherever else as necessary to facilitate conductor installation. B. Pull boxes shall be installed in runs of more than 100 feet or runs having more than the equivalent of 3 right angle bends. C. Location of pull boxes shall be agreed with the Engineer and shall be “accessible” as defined in NEC. D. Boxes shall be supported independently of entering conduits. Pull boxes for new services shall be as indicated on the plans. 2.5 BOXES AND FITTINGS A. All boxes and fittings shall be wet location listed. B. Boxes used for supporting fixtures shall include a 3/8” fixture stud. C. Where multiple devices are located at one point, the appropriate gang box shall be used. D. Boxes used for pendant feeds to lighting fixtures shall be equipped with swivel hangers. E. All surface mounted boxes shall be “FS” or `FD’ type with appropriate covers and plates. 2.6 JUNCTION BOXES A. Where shown on plans, and where necessary to terminate tap-off or redirect multiple conduit runs, provide appropriately designed junction boxes. Boxes used with RGS Conduit and wire shall be cast boxes and shall have full access screw covers secured with corrosion-resistant screws. B. Covers shall be surface-mounted as required. C. Weatherproof junction boxes shall be of the flanged type. D. Box size shall be in accordance with N.E.C. E. All surface mounted boxes shall be “FS” or `FD’ type with appropriate covers and plates. 2.7 SUPPORTING DEVICES A. Under steel construction, use beam clamps for hangers. Under concrete construction, use inserts or expansion shields. Under wood construction, use lag Northampton Bridge Lighting Northampton, MA ELECTRICAL - 18 screws or bolts. B. Hold small conduit in place along walls or columns, where exposed, by one-hole malleable pipe clips and all metal expansion shields. C. Where parallel banks of conduit are installed, support them by means of horizontal angles below the conduit with vertical hanger rods at both ends. D. Backboards for electrical and telephone equipment shall be ¾” plywood panels painted with 2 coats of gray enamel on all sides. Provide 2” x 4” frame backing for plywood and secure to wall. Plywood shall be AC-INTERIOR-APA grade with exterior glue. 2.8 DISCONNECT SWITCHES A. Heavy-duty type, service entrance labeled where applicable. B. NEMA-1 enclosures for indoor, NEMA-3R enclosures for outdoor applications. C. Fusible types with rejection clips. D. Rain tight and lockable where indicated. E. Furnish and installed by Electrical Subcontractor. F. Fuses: Size according to motor current. G. Elevator disconnect switch shall be lockout type with interlock (power on with cover open) and shall be bonded with a # 6 green ground. Provide a pair of Form `C’ contacts, contacts to operate simultaneously when switch operates. H. Approved Manufacturer: Square D, General Electric, ITE Seimens or approved equal. 2.9 WIRING DEVICES AND PLATES A. The Electrical Subcontractor shall install devices where shown on the plans. Where two or more devices occur at one location, they shall be provided with a gang-type plate. B. Receptacles shall be NEMA WD-1 rated, meet Federal Spec. W-C-596d as verified by UL, be 2-pole, 3-wire, 20 amp, 125 volt, NEMA 5-20R, industrial specification grade or Hospital Grade as indicated below with one piece brass strap with integral ground contacts locked into back body and face, impact resistant nylon face and back body, one piece triple wipe brass power contacts. 1. Weather-Resistant /GFCI duplex receptacles for damp or wet location use shall be Specification grade, Pass and Seymour #2097TRWR-I (ivory). C. The use of the feed thru provisions of GFCI receptacles will not be allowed. All receptacles indicated as GFCI shall be individual GFCI receptacles rated 20 amps, 125VAC. D. Provide a cover plate for all devices. Cover plates shall be as follows: 1. In all finished areas install satin finish stainless steel #302 nonmagnetic stainless steel wallplates. 2. Other areas where exposed metal boxes are used Raco ½" exposed-work raised cover plates. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 19 3. Indoor receptacles labeled `weatherproof” and outdoor receptacles shall have Tay Mac #MX4280 series or #MX4380 series metal weatherproof `In Use’ cover or approved equal. Color of cover shall be as directed by the Architect. E. Wiring devices manufactured by Hubbell and Bryant and approved equal are acceptable. F. Wall plates in finished areas shall be manufactured by wiring device manufacture. 2.10 SURGE SUPPRESSION UNIT AT SERVICE ENTRANCE A. General 1. Summary: These specifications describe the electrical and mechanical requirements for a modular, high-energy, externally mounted surge protective device (SPD). Devices installed integral to the electrical panelboard do not meet the intent of this specification and shall be rejected. 2. Standards: The specified system shall be designed, manufactured, tested and installed in compliance with the following codes and standards: a. Underwriters Laboratories; UL 1449 4th Edition Revision (effective 3/26/2016) b. Institute of Electrical and Electronic Engineers (ANSI/IEEE C62.34, C62.41, C62.45) c. Institute of Electrical and Electronic Engineers 1100 Emerald Book d. Federal Information Processing Standards Publication 94 (FIPS PUB 94) e. National Fire Protection Association (NFPA 20, 70, 75 and 780) 3. Life Cycle Testing: The SPD shall be duty life cycle tested to withstand 10kA (8x20 µs), 20kV (1.2x50µs), IEEE C62.41 Category C surge current with less than 5% degradation of clamping voltage. Minimum of 15,000 Life Cycle Surges per Mode for service entrance and 6,000 Life Cycle Surges per mode for branch panels. 4. Overcurrent Protection: All suppression components shall be thermally protected and rated to allow maximum specified surge current capacity. Devices that utilize a single fuse to protect two or more suppression paths are not accepted. Overcurrent protection that limits specified surge currents is not acceptable. 5. Basis of Design: The system shall be constructed using multiple surge current diversion, thermally protected metal oxide varistors (TPMOV). The surge current circuit shall be designed and constructed in a manner that ensures surge current sharing. The listing of a manufacturer as acceptable does not imply automatic approval. Subject to compliance with requirements provide product by one of the following, no substitutions: a. ASCO Power Technologies (APT) b. Current Technologies c. LEA 6. Device Specifics and Performance Ratings (see plans and chart below): a. Service Entrance: Northampton Bridge Lighting Northampton, MA ELECTRICAL - 20 200 kA Surge Rating per Mode with disconnect] 7. Modes of Protection: The SPD shall provide protection for a WYE system in the Line to Neutral, Line to Ground and Neutral to Ground modes. For a DELTA system in the Line to Line and Line to Ground modes. Per Phase rating for a WYE system is the kA rating per mode of the Line to Neutral mode plus Line to Ground mode and for a DELTA system it is the kA rating per mode of the Line to Line mode plus Line to Ground mode. 8. UL 1449 4th Edition Voltage Protection Ratings: Shall not exceed the following: 9. UL 1449 4th Edition Inominal Discharge Current: Shall be a minimum of 20kA. 10. Short Circuit Current Rating: Equal to or greater than 200kAIC. Electrical Panel Brand/Model Surge Capacity kA Mode/Phase Minimum Circuit Breaker Required Below Notes Apply Main Service Panel(s) (MSP/MSB/MDP) ASCO 460 200/400 30 Amp / #10AWG 1,2,4,5,6,7,8 NOTES: 1. Feeder breaker required, see plans for sizing requirements 2. 10 Year Parts Warranty 3. Surge Counter required 4. Thermally Protected Metal Oxide Varsitors (TPMOV) fused at the component level 5. Audible alarm and form C dry contacts 6. Internal service disconnect required 7. Advanced Monitoring – Active Surge Monitor (ASM) with Ethernet connection and event email capability 8. Externally mounted from the electrical panelboard only. Internally mounted units shall be rejected System Voltage UL 1449 4th Edition VPR L-N N-G L-G L-L 120/240 800 v 800 v 800 v 1200 v 120/208 800 v 800 v 800 v 1200 v 240 1200 v 1800 v 277/480 1000 v 1000 v 1200 v 1800 v 480 1800 v 1800 v Northampton Bridge Lighting Northampton, MA ELECTRICAL - 21 11. Submittals a. Documentation: Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories. Copy of UL Category code VZCA certification, as a minimum, listing the tested values for VPRs, Inominal ratings, MCOVs, type designations, OCPR requirements, model numbers, system voltages and modes of protection. b. Equipment Manual: The manufacturer shall furnish an installation manual with installation, startup, and operating instructions for the specified system. c. Drawings: Electrical and mechanical drawings shall be provided by the manufacturer that show unit dimensions, weights, component and connection locations, mounting provisions, connection details and wiring diagram. 12. Quality Assurance: The manufacturer shall be ISO 9001:2000 certified. 13. Environmental Requirements Storage Temperature: -55 to +85°C (-67 to +185°F) Operating Temperature: -25 to +60°C (-15 to +140°F) Relative Humidity: 0% to 95% (non-condensing) Audible Noise: less than 45dB at 5 feet (1.5m) Operating Altitude: 0 to 18,000 feet above sea level 14. Warranty: Ten years from date of Substantial Completion. B. General SPD Requirements 1. Enclosure: The specified system shall be provided in a heavy duty NEMA 4 or better enclosure. 2. Connections: Same size as SPD leads, complying with Section 260519 "Low-Voltage Electrical Power Conductors and Cables." 3. Component Testing and Monitoring: The proposed product shall be single pulse surge current tested in all modes at the rated surge currents by an industry recognized independent test laboratory. The test shall include a surge impulse (6kV [1.2x50µs], 500 amp [8x20µs] waveform) to benchmark the unit’s suppression voltage. The applied impulse is followed by a single pulse surge of the maximum rated surge current magnitude, followed by a second 6kV [1.2x50µs], 500 amp [8x20µs] impulse as a means of measuring clamping deviation (component degradation). C. Execution 1. Installation: Conductors between suppressor and point of attachment to service equipment shall be sized in accordance with manufacturer’s Shop Drawings and conductor lengths shall be as short as possible, not to exceed 36 inches. If longer lengths are required then premium low impedance cable like ASCO AccuGuide shall be used. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 22 2. Grounding: SPD ground shall be bonded to the equipment grounding conductor and service entrance ground. Do not bond neutral and ground. 2.11 SURGE SUPPRESSION FOR COMMUNICATIONS A. The contractor shall provide surge suppression devices on all communications wiring. All SPD devices shall be 4th edition listed and type 1 unless not otherwise available. 1. Low voltage protection shall be provided using Ditek surge protections device to match voltage and wiring. 2.12 MAIN PANELBOARD A. The panel boards shall be of the dead-front type with hinged door frame in accordance with both NEMA and UL standards for use as service entrance equipment. B. Panelboards shall be for use on 120/208 volts, 3 phase 4 wire system. Panelboards shall allow for circuit breakers to be replaced without disturbing adjacent breakers. Breakers shall be rated as shown on Panel Schedule. Panels shall be equipped with ground bus welded to panel and the neutral shall be insulated from the box. Bussing shall be copper only. AIC rating shall be as per panel schedule, and shall be fully rated. C. Circuit breakers shall be listed for use one the panel voltage. Dual listed circuit breakers may not be used. D. Cabinet boxes shall be constructed of code gauge steel. Panel boxes shall be of sufficient size to provide minimum of 8” gutter space on all sides. E. Trims to be constructed of code gauge furniture steel with gray finish, ANSI 49, to be equipped with directory holder. Doors shall have concealed hinges and flush spring lock with pull-ring handle. Provide cover hinged to box type trim. F. Provide GFCI circuit breakers, switching duty breakers, ARC fault and shunt trip as indicated. Each GFCI circuit breaker requires a dedicated neutral in each branch circuit. G. Provide spare breakers as shown on Panel Schedule. H. Panelboards shall be mounted with a maximum mounting height of six feet (6’) to main breaker or top of panel board, depending on type installed. I. UL wire bending space requirements shall be met. J. Directory shall be typed, handwritten will be rejected. Directory shall identify feeder origin. K. All circuit breakers shall be bolt-on type only. L. Approved equals: Square D NQ series, ITE Siemens, General Electric, or approved equal. 2.13 LIGHT FIXTURES A. All luminaries and other lighting equipment shall be delivered to the job complete, wired and including all supporting means such as plaster frames, supports, hangers, canopies, sockets, holders, all current or voltage modifiers, such as ballasts, starters, all light control materials; specifically, diffusers, louvers, lenses, reflectors and Northampton Bridge Lighting Northampton, MA ELECTRICAL - 23 refractors. All lighting fixtures shall be constructed and installed in accordance with local building codes and directives by the National Board of Fire Underwriters and shall bear the label of approval of the Underwriters' Laboratories, Inc. All materials shall be new and of best grade of approved manufacturing standards. Workmanship shall be of the highest order to assure trouble-free operation and durability of equipment B. Specified products shall be considered the Basis of Design. Approved equals to the basis of the design fixtures listed in the Light fixture Schedule shall be accepted for review during the submittal phase with the proposed substitute fixture meeting the following minimum requirements. 1. Be of the same general size, style and shape, including but not limited to lens construction and shading. 2. Be of equal or better quality and construction. 3. Be supplied with all required accessories to match the specified fixture. 4. Be supplied with all remote drivers, power supplies and cabling lengths to meet specified performance and control. 5. Provide the same or better distribution, efficiency, source lumen output, and L70 lumen depreciation metric or greater to equal the specified fixtures. C. Fixtures shall meet the requirements of utility incentive programs for energy efficiency. Contact utility company for information. Cooperate and coordinate with utility for incentive program. Incentives shall go to the owner. Provide information and fill out forms as requested. D. Assume all responsibility for checking Architectural Drawings, prior to ordering fixtures, and provide the specified fixtures with proper mounting arrangement to be compatible with the type ceiling construction in which the fixture is to be mounted. Submit letter indicating verification was done. E. Manufacturer’s submittals for all lighting fixtures shall be submitted for review and acceptance prior to purchase. F. Submittals for LED fixtures shall indicate complete details of fixtures, including Manufacturer’s catalog number, number of lighting boards, number of drivers, CRI of LED lamps, Lumens per watt, Color temperature, projected life of fixture at percentage of lumen output, DLC or energy star listing, Light Loss factor (LLF), IES LM-79, LM-80 and IES TM-21 adherence, LEDs from the same batch, inrush current, surge protection, RFI, THD, power factor, light shields, switches, metal gauges, type of wiring, finish color and texture. G. LED fixture manufacturers shall have a minimum of 5 years’ experience in the manufacturer of LED systems. H. Where pertinent to proper installation or operation, submittals shall indicate relationship between fixtures and adjacent elements of structure (walls, columns, ducts, openings, ceiling grid, etc.) I. Submit verification of meeting utility incentive program requirements. J. Submit letter indicating that the latest Architectural Drawings have been reviewed for ceiling types and the fixtures being submitted have the proper mounting accessories. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 24 K. Submit photometric information. L. Submit point-by-point calculations for substituted fixtures where requested. M. Fixtures shall be free of light leaks. No crossbars are permitted over light shields. Fixtures shall provide for sufficient ventilation of lamps and ballasts. Size and location of vent holes shall be indicated on Manufacturer’s Drawings. Outdoor fixtures shall have mesh screens in vent holes. N. Assume all responsibility for the safe handling of all light fixtures, accessories, and lamps until the final inspection has been made by the Architect and the installation accepted by the owner. O. Special fittings and materials that may be required to support fixtures shall be supplied as well as supports, spacers, or grounds required to secure surface or pendant mounted fixtures on suspended ceilings. P. Fixtures, part or parts thereof (including LED’s) determined to be defective shall be replaced. Q. Recessed fixtures shall be supplied with trim gaskets as required to prevent light leaks on ceiling. Provide mounting support bars for all recessed fixtures, where required. R. All LED arrays, shall have the same bin rating for consistency of color. S. LED drivers shall be specifically listed for use with the fixture. The driver shall be encased and have overload, short circuit protection, thermal regulation to protect against overheating and a sound rating of `A’. Drivers shall have a minimum starting temperature of -20ºC. The drivers shall have a five-year written warranty from date of shipment against mechanical or electrical defects under normal conditions of use. The warranty shall include a per-driver replacement labor allowance. T. Fixtures to be located outdoors or indoors in ambients that may be below 60-degree F (-18 degree C), shall have outdoor ballasts and lamps suitable for operation at 0 degree (-16 degree C). U. Provide manpower and tools for final adjusting of all adjustable fixtures. This operation shall take place immediately before the building is turned over to the owner after regular working hours where required. V. Provide individually fused fixtures for emergency lighting fixtures. Indicate fusing in submittals. Provide ten percent spare fuses of each type supplied (minimum one). Mount in cabinet in Electric Room. Obtain signed receipt from owner. W. All fixtures to be independently supported from building structure. X. Provide 10% spare lamps for all types specified. Y. All pendant fixtures shall be mounted from “hang-strait” devices. Z. Provide end caps on all industrial LED fixtures. AA. Exact colors shall be selected by Architect from manufacturer’s standard color charts. BB. All LED and exterior lighting fixtures shall be fused. CC. All tamperproof fasteners shall be Tork head (center pin reject) type. Provide three Northampton Bridge Lighting Northampton, MA ELECTRICAL - 25 (3) screwdrivers for such to Owner. 2.14 CLIMATE CONTROLLED CABINET A. The contractor shall provide a climate-controlled cabinet which shall house the lighting control equipment. The cabinet shall consist of a cooling unit, heater and thermostat and enclosure. The contractor shall mount cabinet on Unistrut channels in accordance with manufactures requirements. B. The cabinet shall provide a maximum temperature of 85F degrees in the summer and a minimum temperature between 45-50F degrees in the winter. The assumed maximum ambient temperature shall be 110F and the minimum ambient temperature shall be 0F. The cabinet shall consist of an A/C cooling unit, heater and thermostat and hinged cover junction box with a mounting backboard. C. The cabinet to house the lighting control panel shall be a Carbon Steel Nema 4 enclosure, hinged door, IP 66 rated with a hinged door field adjustable for right or left hinge. The cabinet shall be 42”H x 60”W x 16”D with quarter turn lock cover. The housing and door thickness shall be 2mm and the mounting plate shall be 2.5mm minimum. The mounting plate shall be 40”H x 58”W. Cabinet shall be UL listed and factory cut on the side to mate with the cooling unit mounted to the cabinet. Install all components and mounting equipment required. Provide Rittal wall mounted enclosure or approved equal. D. The cooling cabinet shall be a Rittal Top Therm Blue e stainless steel wall-mounted cooling unit. The cabinet shall be Nema 4X. The cabinet shall include nano-coated condenser, integral electric condensate evaporation, wired ready for connection (plug in terminal strip), drilling template and fasteners. The unit operating voltage shall be of 120V, 60 Hz.. Cabinet shall be provided with a circuit breaker sized as required. The cooling unit shall be stainless steel and UL listed. Cooling unit shall be manufactured by Rittal or approved equal. The contractor shall provide all power to the cooling unit as required. E. The heater and thermostat shall be installed in the cabinet. The heater shall consist of a PTC heater with fan, quick connection terminal and fasteners. The heater shall be rated for use at 120V. The heater shall come with a circuit breaker/fuse.. Heater shall be UL listed. Heater shall be manufactured by Rittal or approved equal and thermostat shall be Rittal #3110.00 or approved equal. F. The contractor shall provide all wiring required for a complete and fully operational system both within the cabinet between components as well as external circuiting. The system shall be provided with a minimum of a 1 year warranty on all parts and components. The contractor shall have the manufacturer provide start up/commissioning of the climate controlled cabinet. G. The contractor may contact Jim Hockenberry at Dittman & Greer, Inc. Mobile 413- 207-2851 and email:jim.hockenberry@dittman-greer.com for climate controlled cabinet. 2.15 DATA SYSTEMS A. Furnish and install Data raceways, male connectors, Category 6 cables and make all connections/testing each end of cable. B. The Electrical contractor shall provide a 3/4” conduit (EMT) with pull line from each outlet box to an accessible location. Provide metal bushings on the ends of all conduits. (Accessible location shall be defined as the hung ceiling space). All Northampton Bridge Lighting Northampton, MA ELECTRICAL - 26 raceways shall be routed concealed in all “finished spaces”. C. Minimum size outlet box shall be 4-11/16” square by 2-1/8” deep junction box and 1-1/2” extension ring on box with single gang ring. D. The Electrical contractor is responsible for identifying any sources of EMI/RFI and providing adequate protection for the cable plant. Maintain a minimum of .9m (3 feet) of clearance between any EMI/RFI source, including electrical wire runs. E. Sources of EMI include, but are not limited to: 1. Motors/Generators 2. Lighting 3. Air Conditioner units 4. Batteries 5. Power Tools 6. Kitchen Appliances 7. Power Panels, boxes 8. Copiers 9. Power panels F. Sources of RFI include, but are not limited to: 1. Radio Transmitters 2. Televisions 3. Wireless phones 4. Satellite Transmitters 5. Alarm Systems 6. Surveillance equipment 7. Microwave units G. The complete installation shall comply with the latest edition of EIA/TIA-568, Commercial Building Telecommunications Wiring Standard and the latest edition of EIA/TIA 569, Commercial Building Standard for Telecommunications Pathways and Spaces. H. The entire installation shall be coordinated with the lighting fixture manufacture. I. The cable shall be blue Cat 6, 4 pair, UTP, 24-gauge low smoke cable. Cable shall be manufactured by Commscope or approved equal. J. The contractor shall make all connections to the network switch, gateway, Pharos and all data enabler Pro’s. Refer to wiring diagram on the contract documents. 2.16 RELAYS A. Furnish and install relays as shown and detailed on the plans. Relays to be in a steel housing with a hinged cover as detailed on the plans. Relay contacts to be 20 amp., 120 or 277 volt as required. Coil voltage shall be as indicated on the plans or as field required. Relays shall be mechanically held. B. Elevator relays shall be as required by elevator manufacturer. There are 4 relays shown on the plans. They are for main level elevator recall, alternate level elevator recall, elevator shaft venting and flashing hat. Coordinate the requirements with the State Elevator Code and the Elevator installer in the field. C. Approved Manufacturers: Asco, Square D, G.E., Siemens or Allen Bradley. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 27 2.17 VIBRATION ISOLATION AND SEISMIC RESTRAINTS A. Vibration Isolation 1. All electrical equipment, conduits and gears as noted on the Drawings or in the Specification shall be mounted on vibration isolators to prevent the transmission of vibration and mechanically transmitted sound to the building structure. Vibration isolators shall be selected in accordance with the weight distribution to produce reasonably uniform deflections. 2. All isolators and isolation materials shall be of the same manufacturer and shall be certified by the manufacturer. B. Seismic Restraints 1. It is the intent of the seismic portion of this specification to keep all electrical building system components in place during a seismic event. 2. All such systems must be installed in strict accordance with seismic codes, component manufacturer's and building construction standards. Whenever a conflict occurs between the manufacturer's and construction standards, the most stringent shall apply. 3. This specification is considered to be minimum requirements for seismic consideration and is not intended as a substitute for legislated, more stringent, national, state or local construction requirements. C. The contractor shall correct any variance or non-compliance with these specification requirements in an approved manner. 1. The work in this section includes, but is not limited to the following: a. Vibration isolation for piping, ductwork and equipment b. Flexible piping connections c. Equipment isolation bases d. Seismic restraints for isolated equipment. e. Seismic restraints for non-isolated equipment f. Certification of seismic restraint designs and installation supervision g. Certification of seismic attachment of housekeeping pads h. Equipment buried underground is excluded but entry of services through the foundation wall is included. D. Definitions 1. Positive Attachment: a. A positive attachment is defined as a cast-in anchor, a drill-in wedge anchor, a double-sided beam clamp loaded perpendicular to a beam, or a welded or bolted connection to structure. b. Single sided "C" type beam clamps for support rods of overhead piping, ductwork or equipment are not acceptable on this project. 2. Transverse Bracing: a. Restraint(s) applied to limit motion perpendicular to the centerline of the Northampton Bridge Lighting Northampton, MA ELECTRICAL - 28 pipe, or conduit. 3. Longitudinal Bracing: a. Restraint(s) applied to limit motion parallel to the centerline of the pipe, or conduit. E. Submittal Data Requirements 1. The manufacturer of vibration isolation and seismic restraints shall provide submittals for products as follows: a. Descriptive Data: 1. Catalog cuts or data sheets on vibration isolators and specific restraints detailing compliance with the specification. 2. Detailed schedules of flexible and rigidly mounted equipment, showing vibration isolators and seismic restraints by referencing numbered descriptive drawings. b. Shop Drawings: 1. Submit fabrication details for equipment bases including dimensions, structural member sizes and support point locations. 2. Provide all details of suspension and support for ceiling hung equipment. 3. Where walls, floors, slabs or supplementary steel work are used for seismic restraint locations, details of acceptable attachment methods for ducts, conduit and pipe must be included and approved before the condition is accepted for installation. Restraint manufacturers' submittals must include spacing, static loads and seismic loads at all attachment and support points. 4. Provide specific details of seismic restraints and anchors; include number, size and locations for each piece of equipment. c. Seismic Certification and Analysis: 1. Seismic restraint calculations must be provided for all connections of equipment to the structure. 2. Calculations (including the combining of tensile and shear loadings) to support seismic restraint designs must be stamped by a registered professional engineer with at least five years of seismic design experience and licensed in the state of the job location. Testing and calculations must include both shear and tensile loads as well as one test or analysis at 45° to the weakest mode. 3. Analysis must indicate calculated dead loads, static seismic loads and capacity of materials utilized for connections to equipment and structure. Analysis must detail anchoring methods, bolt diameter, embedment and/or welded length. All seismic restraint devices shall be designed to accept, without failure, the forces detailed in this Section acting through the equipment center of gravity. Overturning moments may exceed forces at ground level. F. Code and Standards Requirements 1. Applicable codes and Standards Northampton Bridge Lighting Northampton, MA ELECTRICAL - 29 2. The Massachusetts State Building Code G. Manufacturer's Responsibility 1. Manufacturer of vibration isolation and seismic control equipment shall have the following responsibilities: a. Determine vibration isolation and seismic restraint sizes and locations b. Provide vibration isolation and seismic restraints as scheduled or specified c. Provide calculations and materials if required for restraint of non-isolated equipment d. Provide installation instructions, drawings and trained field supervision to insure proper installation and performance. H. Related Work 1. Housekeeping Pads a. Housekeeping pad reinforcement and monolithic pad attachment to the structure details and design shall be prepared by the restraint vendor if not already indicated on the drawings. b. Housekeeping pads shall be coordinated with restraint vendor and sized to provide a minimum edge distance of ten (10) bolt diameters all around the outermost anchor bolt to allow development of full drill-in wedge anchor ratings. If cast-in anchors are to be used, the housekeeping pads shall be sized to accommodate the ACI requirements for bolt coverage and embedment. 2. Supplementary Support Steel a. Contractor shall supply supplementary support steel for all equipment, piping, ductwork, etc. including roof-mounted equipment, as required or specified. 3. Attachments a. Contractor shall supply restraint attachment plates cast into housekeeping pads, concrete inserts, double-sided beam clamps, etc. in accordance with the requirements of the vibration vendor's calculations. 2.18 Seismic Force Levels - The following force levels will be used on this project. Building Code "G" Forces for All Pipe, Duct & Conduit "G" Forces for Rigidly Mounted Equipment "G" Forces for Flexibly Mounted Equipment "G" Forces for Life Safety Equipment either Rigidly or Flexibly Mounted 2.19 PAINTS AND COATINGS A. All paints and coating used on the interior of the building (defined as inside of the weatherproofing system and applied on site) shall comply with the Leed Northampton Bridge Lighting Northampton, MA ELECTRICAL - 30 Requirements. B. Paints shall not exceed VOC content limits established in Green Seal Standard GS- 11, Paints, First Edition, May 20, 1993. Primers must meet the VOC limit for non- flat paint. 1. Flats: 50g/L 2. Non-Flats: 150g/L C. Anti Rust and Anti corrosive paints: 250g/L Per Green Seal Standard GS-03, Anti Corrosive Paints, Second Edition, Jan. 7, 1997 D. Paints shall be Benjamin Moore, Eco Spec series, ICI Paints Lifemaster series with Devflex 4020PF or Prep and Prime Gripper 3210 or equal 2.20 COMPOSITE WOOD AND AGRIFIBER A. All composite wood and agrifiber used on the interior of the building (defined as inside of the weatherproofing system and applied on site) shall contain no added urea formaldehyde resins. Laminating adhesives used to fabricate on site and shop applied composite wood and agrifiber assemblies shall contain no added urea formaldehyde. B. Composite wood and agrifiber products are defined as: particleboard, medium density fiberboard (MDF), plywood, wheatboard, strawboard, panel substrates and door cores. C. Plywood shall be manufactured by Certified Wood Products Inc. of Minnesota or equal 2.21 ADHESIVES AND SEALANTS, A. All adhesives and sealants used on the interior of the building (defined as inside of the weatherproofing system and applied on site) shall comply with the current Leed Requirements. 1. PVC welding 510g/L less water 2. CPVC welding 490g/L less water 3. ABS welding 325g/L less water 4. Plastic cement welding 250g/L less water 5. Adhesive primer for plastic 550g/L less water 6. Special Purpose contact Adhesive 250g/L less water 7. Contact Adhesive 80g/L less water B. If the contractor intends to use any other type of adhesive or sealant that is not listed it will be incumbent upon him to provide products that comply with the South Coast Air Quality Management District 9SCAQMD) Rule #1168. VOC limits are listed in New Construction and Major Renovations version 4.1 Reference Guide page 339, table 1. C. Aerosol Adhesives shall comply with Green Seal Standard for Commercial Adhesives GS-36 dated October 19, 2000. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 31 PART 3 - EXECUTION 3.1 MECHANICAL EQUIPMENT A. Electrical Subcontractor shall furnish and install all disconnect switches, thermal protection and starters for all heating and cooling and plumbing equipment except where such are an integral part of the equipment. B. Provide required electrical connections for the building mechanical equipment. Wiring shall be as necessary to provide proper operation of the equipment including power and temperature control and as indicated on the plans. C. The Electrical Subcontractor shall, before energizing any motor or other piece of mechanical equipment, verify that it is proper voltage, properly lubricated, aligned and/or ready for proper and safe operation. Motor rotation shall be checked and corrected, if necessary. D. Make connections to other building equipment as required. Data on the drawings of equipment actually purchased before starting this work of its rough-in. Each piece of equipment and each motor shall be provided with an approved disconnect and over-current protection as required by Code. 3.2 WORKMANSHIP A. This Contractor shall endeavor to layout and perform his work in such a manner as to cause no delay in the construction work by other trades. B. This Contractor shall verify all measurements and shall be responsible for the correctness of same. No allowance will be made for differences between actual measurements and those shown on the plans. C. If, in laying out his work, this Contractor finds that the work of other trades might interfere with him, the Architect/Engineer shall be notified at once. The right is hereby reserved by the Architect/Engineer to make reasonable changes in arrangement of equipment, piping, etc., prior to roughing-in, if interference is found, without additional cost to the Owner. D. All work shall be installed in such a manner as to be readily accessible for maintenance, repair and operation. Deviations from the plans must be approved by the Architect/Engineer without additional cost to the Owner. E. The locations of outlets, apparatus and equipment are approximate only and the runs of feeders, mains and branches are not necessarily to be made exactly as shown on the plans. The exact locations of such work shall be determined after full consideration has been given to work of other trades and without changes in the design of the systems. The entire installation shall conform to the latest issue of the National Electric Code and local inspection authorities. F. Verify exact circuit breaker, feeder and outlet requirements and locations for mechanical equipment in accordance with manufacturer’s wiring diagrams. Incorporate any changes necessary in design to accommodate such. G. In areas where finish may be of a different color, the Architect will advise on finish. H. Electrical equipment, such as junction and pull boxes, controls and apparatus, shall be made accessible. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 32 I. There shall be no splices in new wire except where circuits are branched. J. Make splices for #10 or smaller conductors with U.L. approved solderless connectors based on MMM Co.”Scotchlock” Type S, M, or L, Buchanan, or T&B “Stakon”. Make splices, cable taps and terminals for #8 or larger conductors with U.L. approved bolted pressure conductors of bronze or copper construction equal to those manufactured by T&B or Burndy. 3.3 GROUNDING A. The Electrical Subcontractor shall furnish and install all material required for the grounding and/or bonding in the building of all equipment, metal piping systems, power and lighting systems. B. The Electrical Subcontractor shall make tight and proper all metallic components and equipment to one another and to ground, using a positive foolproof system of connections. Provide and install bonding and grounding conductors with approved termination where required, conforming with latest National Electric Code, M.E.C.O. and other applicable specification standards. C. A #12 AWG insulated equipment ground conductor shall be installed in each length of flexible metallic conduit connecting to motors, recessed lighting fixtures and other equipment components for continuity. Positive ground connections with ground wire shall be made at each outlet box, lighting fixture, motor and other equipment components by means of positively secured ground clamp in each. D. A ground wire shall be provided in all conduit runs. The ground conductor shall be sized in accordance with code or larger as may be indicated on the contract documents E. Size ground connections according to Code. Ground connections shall be copper, connected with code-approved brass or copper clamp fittings. Do not use soldered connections in grounding connection. F. Make ground connection and taps from equipment with as few connections as possible. Make connections with approved type solderless connectors, protect from mechanical injury and support rigidity. G. Clean contact surfaces thoroughly before connection is made, so as to insure a good metal-to-metal contact. Ground connections shall be readily accessible for inspection at all times. H. Ground all systems and equipment in accordance with best industry practice and the following: I. Establish a ground bonding connection from structural building steel to each cold-water mains entering the building. Each bonding connection shall consist of green insulated conductors run in threaded steel conduit, and sized as indicated hereinafter for grounding electrode conductors. J. The grounding stud of each secondary voltage to secondary voltage dry type 3 phase transformer for light and power shall be connected separately to the grounding electrode for such transformers specified below. Connection shall be by means of a green insulated conductor, run in threaded steel conduit, sized in accordance with the following: Northampton Bridge Lighting Northampton, MA ELECTRICAL - 33 Transformer KVA Grounding Conductor Conduit Size 0 - 45 1 # 6 ¾"C 46 – 75 1 # 2 ¾"C 76 - 150 1 # 3/0 1”C 151 and larger 1 # 250MCM 1 1/4"C K. The grounding electrode for each secondary voltage to secondary voltage dry type transformer shall consist of a cadweld connection to adjacent structural steel at a point where only fireproofing and not structural concrete is applied to it. L. Provide grounding bonds between all metallic conduits of the light and power system which enter and leave cable chambers or other non-metallic cable pulling and splicing boxes. Accomplish this by equipping the conduit with bushings of the grounding type individually cross connected. M. Bond metallic conduits containing grounding electrode conductors and main bonding conductors to the ground bus service enclosure and/or grounding electrode at both ends of each run utilizing grounding bushings and jumpers. N. Provide grounding bonds for all metallic conduits of the light and power system, which terminate in pits below equipment for which a ground bus is specified. Accomplish this by equipping the conduits with bushings of the grounding type connected individually to the ground bus. O. Provide supplementary ground bonding where metallic conduits terminate at metal clad equipment (or at the metal pull box of equipment) for which a ground bus is specified. Accomplish this by equipping the conduits with bushings of the grounding type connected individually by means of jumpers to the ground bus. P. Each grounding type bushing shall have the maximum ground wire accommodation available in standard manufacture for the particular conduit size. Connection to bushing shall be with wire of this maximum size. Q. Provide a #6 AWG in ¾" minimum conduit green insulated copper ground wire connection to cold water pipe or other main building service grounding electrode for the main telephone equipment room/backboard and main data equipment room/backboard.. R. The central equipment for the fire protection alarm system shall have its grounding terminal connected to the nearest metallic cold water main by means of a #6 green coded insulated conductor, run in ¾" threaded metallic conduit. Utilize a ground clamp of a type specifically manufactured for the purpose. S. Conductors utilized for grounding and bonding shall have Type "TW" or better insulation, color coded green. T. Bonding conductors on the load side of the service device and equipment grounding conductors shall be sized in relation to the fuse or trip size of the overcurrent device supplying the circuit in accordance with the following table: U. SIZING OF EQUIPMENT AND RACEWAY GROUNDING CONDUCTORS AND LOAD SIDE OF SERVICE BONDING JUMPERS Northampton Bridge Lighting Northampton, MA ELECTRICAL - 34 OVERCURRENT DEVI CE GROUNDING CONDUCTOR OR BONDING CONDUCTOR FUSE OR TRIP SIZE SIZE -- CU SIZE AL (AMPS)** 15 - 20 #12 #10 25 - 60 #10 #8 70 - 100 # 8 # 6 110 - 200 # 4 # 4 225 - 400 # 2 1/0 500, 600 * 2 x #1 2 x 2/0 700, 800 * 2 x 1/0 2 x 3/0 1000 * 3 x 2/0 3 x 4/0 1200 * 4 x 3/0 4 x 250 MCM 1600 * 5 x 4/0 5 x 350 MCM 2000 * 6 x 250 MCM ( x 400 MCM *Adjust quantity (if needed) to match number of conduits in run. **Where phase leg conductor ampacity exceeds over-current device, increase grounding conductor as if the overcurrent device size matched the phase leg ampacity. V. Grounding electrode conductor and conductors used for bonding on the supply side of the service device shall be sized in accordance with the following table: Northampton Bridge Lighting Northampton, MA ELECTRICAL - 35 SIZING OF GROUNDING ELECTRODE CONDUCTORS AND MAIN (AND SUPPLY SIDE OF SERVICE) BONDING JUMPERS SERVICE CONDUCTOR SIZE GROUNDING ELEC-TRODE CONDUCTOR BONDING JUMPER CONDUCTOR CABLE BUS CU AL CU AL CU AL #2 1/0 100 # 8 #6 # 8 #6 3/0 250MCM Max 200 # 4 #2 # 4 #2 500 MCM. 700MCM Max 400 # 1/0 3/0 # 1/0 3/0 2x350 MCM. 2X500 MCM Max 600 # 2/0 4/0 # 2/0 4/0 2x500 MCM 2X700 MCM Max 800 # 2/0 4/0 #2/0 4/0 4x350 MCM 4X500 MCM Max 1200 3/0 250 MCM 250 MCM 350 MCM 5x400 MCM 5X600 MCM Max 1600 3/0 250 MCM 400 MCM 600MC M 6x500 MCM 6X750 MCM Max 2000 3/0 250 MCM 500 MCM 2X250 MCM 8x500 MCM 8X750 MCM Max 3000 3/0 250 MCM 2x500 MCM 2X250 MCM 11x500 MCM 11X750 MCM Max 4000 3/0 250 MCM 2x500 MCM 2X750 MCM 14x500 MCM 14X750 MCM max5000 3/0 250 MCM 3x400 MCM 3X600 MCM W. Connections of ground wires shall be in accordance with the following: LOCATION GROUND WIRE CONNECTION Main Switchboard Switchboard ground bus Junction box at which non-metallic conduits terminate Metal body of junction box Secondary voltage to secondary voltage Transformer Transformer ground stud 3.4 INSTALLATION OF CONDUITS AND FITTINGS A. All conduits shall be installed so as to provide the straightest possible run with not more than the equivalent of three 90-degree bends in a single run. Where Northampton Bridge Lighting Northampton, MA ELECTRICAL - 36 more bends are necessary, the Electrical Subcontractor shall provide suitable pull boxes. B. All feeders and homeruns shall be installed in conduit or duct. Raceways underground shall be rigid steel galvanized, non-metallic duct encased in concrete or plastic conduit encased in concrete. Conduits in concrete slabs on grade or where exposed to weather shall be rigid steel galvanized. Conduits in concrete slabs or walls above grade shall be galvanized intermediate metal conduit (IMC) where allowed by code or rigid steel galvanized. Conduits in masonry walls, in steel stud walls or in furred spaces 10’ in length or greater, shall be EMT for 2 inch and smaller size and shall be EMT, rigid steel galvanized or galvanized intermediate metal conduit (IMC) where allowed by code, for larger than 2 inch size. Conduits in metal or wood stud walls, in furred spaces less than 10’ in length or for final connections to recessed fixtures or to motors or moving or vibrating equipment shall be flexible conduit in dry locations and liquid-tight flexible conduit in damp locations or where exposed to weather. C. All homeruns, if not shown on the drawings, shall originate from the first outlet, wiring device or light fixture of the circuit back to the panel. D. Run all conduits unless specifically noted on the drawings by note or symbol, concealed. Install all conduit runs parallel to, or at right angles to structural members, walls or lines of the building. DO NOT COMBINE CONDUIT RUNS WITHOUT APPROVAL. E. Conduits which are suspended on rods more than 2 feet long shall be rigidly braced to prevent horizontal motion or swaying. F. Conduits shall be supported at intervals called out in `spacing of conduit supports’ table of NECA Standard of Installation, or as required by code, whichever is more restrictive. G. Conduits which are installed at this time and left empty for future use including intercommunications system conduits shall have a 3/16 inch polyrope pull line left in place for future use. H. Where conduit passes from one type of construction to another, or where there is a possibility of dissimilar movements, a minimum of 36 inches of flexible conduit shall be installed in furred spaces or where exposed. Use O.Z. type `DX’ expansion fittings in concrete. Conduits entering refrigerated areas shall have an approved sealing fitting filled with compound, installed in an accessible location, on warmer side of wall. I. Electric metallic tubing with approved fittings will be accepted in lieu of heavy wall conduit where so approved by the National Electrical Code if note otherwise on the drawings. J. Conduit shall be fished and cleaned and dry before pulling wires and shall be suitably protected against entrance of dirt and moisture during construction. K. Ends of all conduits shall be reamed and all joints made waterproof. Connections to junction boxes shall be double locknut and bushing, using insulated bushings on all conduit 1-1/4” or larger. Grounding busing shall be provided at all panel connections. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 37 L. Conduit connections to motor frames shall have a minimum of 18” of greenfield to eliminate vibrations and noise being transferred to other parts of the building, with cable jumper across greenfield and fittings. M. Run conduit to avoid low pockets which might collect water. During installation, cap open ends. N. Maintain conduits in position during the pouring of concrete. O. Electric metallic tubing will not be installed below grade in areas subject to severe corrosion conditions or embedded in concrete. Approved conduit no larger than 1-1/4” & 2” may be installed on the centerline of concrete slabs on grade, respectively. Conduit larger than the above may be embedded in the slab, provided the slab on grade is thickened accordingly. Where conduit is run below slab on grade, conduit will be corrosion protected. P. Support exposed conduit in a firm and substantial manner by means of adjustable malleable hangers of approved design. Q. All elbows 1 inch and larger shall be factory made. Conduits shall be kept at least 16 inches from the coverings on hot water and steam pipes, and 18 inches from the covering on flues and breechings. The open ends of all conduits shall be kept closed with approved conduit seals during the construction of the building. Use approved conduit unions or O.Z. type `SSP’ split couplings (except in hazardous locations) where union joints are necessary. Running threads will not be permitted. R. Conduits above de-mountable ceilings shall be installed as high as possible against the structure above. S. Route all exposed raceways as directed by the Engineer. T. When installing flexible metallic cable concealed, tape cable together in bundles and tie to structure or supports at 5' intervals. U. Type “MC” cables shall be allowed for lighting fixture whips and branch circuits fished into existing walls only. All homeruns to panel board(s) shall be conduit and wire only. See paragraph C above. V. In finished areas where raceways cannot be routed concealed because of building construction, the Architect will advise on how to route these raceways in a low profile wiremold type surface metal raceway system. W. In finished areas where feeder conduits cannot be routed concealed because of building construction or approved by the Architect or the engineer, the electrical contractor shall paint the conduits and supports to match the surrounding surfaces. The contractor shall clean all conduits and supports to insure the paint adheres to the conduit and supports. X. Permanent electrical power shall be scheduled for availability for use to make tests of mechanical equipment prior to the installation completion date. Y. All penetrations through fire rated walls shall be sealed with 3-hour fire-rated caulk or putty “3M” or equal. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 38 3.5 OUTLET AND JUNCTION BOXES A. Verify mounting heights of switches and receptacles with Architect before installation. The Electrical Subcontractor shall check with Architectural and Structural Plans for interference. B. Junction and outlet boxes, where exposed to weather and wet locations, shall be of the threaded hub type and provided with watertight screw-on cover and gasket. C. Pull boxes shall be adequate size to accommodate the conductors installed therein without excessive bending of the conductors, which would damage the conductor insulation. D. All outlets installed in masonry shall be so set that their outer edges are ¼” in back of finished surface. E. Outlet boxes shall not be supported by the conduit. Suitable means shall be provided to support the outlet box to take the weight of the fixture. F. Fixture outlet boxes used as junction boxes or outlets not used, shall be provided with cover. G. All outlet boxes surface mounted on walls or columns shall be equal to Crouse Hinds FS2 Series ½” or ¾” conduit entry. Covers and device plates shall be designed for FS boxes. 3.6 REQUIREMENTS GOVERNING ELECTRIC WORK IN DAMP OR WET LOCATIONS WITHIN BUILDING CONFINES A. Abide by the requirements specified for normal electric work conditions except: 1. Exclude armored cable. 2. Utilize watertight compression gland type fittings only on elect. metallic tubing. 3. The finish for threaded steel conduit shall be galvanized only. 4. Outlet size boxes and fittings shall be of galvanized cast ferrous metal only. 5. Conductors for pulling into raceways for lighting and appliance branch circuitry purposes shall have permissible insulation types limited to “XHHW”, “TW”, “THW” and “THWN”. 6. Conductors for pulling into raceways for main feeders, submain feeders and branch feeders shall have permissible insulation types limited to “XHHW”, “THW”, and “THWN”. 7. Apply one layer of half lapped plastic electric insulating tape over wire nuts used for joining the conductors of wires. 8. Exclude split insulating casings for insulating joints and taps in conductors of wires and cables. 9. Wiring device plates shall be galvanized sheet steel or cast ferrous metal except that in finished spaces, they shall be of type 302 non-magnetic stainless steel. 10. Plates for toggle switches and receptacles shall have gasketed snap-shut covers. 11. Final connections of flexible conduit shall be of the neoprene sheathed type. 12. Enclosures, junction boxes, pull boxes, cabinets, cabinet trims, wiring troughs and the like, shall be fabricated of galvanized sheet metal, shall conform to the Northampton Bridge Lighting Northampton, MA ELECTRICAL - 39 following. a. They shall be constructed with continuously welded joints and seams. b. Their edges and weld spots shall be factory treated with cold galvanized compound. c. Their connection to circuitry shall be by means of watertight hub connectors with sealing rings. d. Enclosures for individually mounted switching and over current devices shall be NEMA-4. 13. The covers, doors, plates and trims used in conjunction with all enclosures, pull boxes, outlet boxes, junction boxes, cabinets and the like, shall be equipped with gaskets. 14. All enclosures, cabinets, junction and pull boxes (larger than outlet box size) and the like, shall be equipped with breather and drain fittings. 15. The following shall be treated as damp or wet locations within building confines, regardless of whether or not a high ambient moisture level is found to exist: a. Spaces where any designations indicated weather-proof (WP) or vaporproof (VP) appear on the drawings. b. Outside of waterproofing in foundation walls in contact with grade. c. Electric work in slabs, walls or suspended ceilings which bound on a space defined as a damp or wet location shall meet the damp or wet location requirements if it enters into, or opens into the damp or wet location in any way. 3.7 TESTS A. All wiring and connections shall be tested for continuity, grounds and short circuits before the fixtures, devices and equipment are connected. B. Upon completion of the work, the Contractor shall make any tests necessary to satisfy the Owner and the Architect or his representative that the true intent and meaning of the drawings and specifications has been carried out. Contractor shall provide all instruments and labor necessary to make such tests. Such tests shall include voltage tests at incoming service and at every panel and switchboard. Any work showing faults under test, and any work not in accordance with the specifications, shall be made good by the Contractor at his own expense. C. All tests shall be typed to include page number and number of pages in report. Handwritten reports will be rejected. 3.8 LIGHTING FIXTURES A. Installation of all lighting fixtures shall be done by experienced mechanics. Lighting fixtures shall not be installed where finished coat of paint has been applied to ceiling and walls until paint is thoroughly dry. B. Lighting fixtures in equipment rooms shall not be installed until after all piping and ductwork is in place. Lighting fixture layout shown on the drawings is typical layout but may be modified to provide adequate lighting of the equipment Northampton Bridge Lighting Northampton, MA ELECTRICAL - 40 space according to final construction conditions. Any relocation of fixtures due to duct or piping interference shall be as directed by the Architect/Engineer, at no expense to the Owner. C. Fixtures shall be rigidly mounted to fixture stud in outlet boxes. Malleable iron hickies or extension pieces shall be provided where required. D. Provide and install suitable cover plate or canopy for each fixture outlet box where the fixture does not provide a suitable cover. E. Pendant type fixtures in the same room shall be installed at a uniform height from the floor and hang plumb. F. Each fixture shall be completely prewired in Code approved manner with #12 AWG copper conductors with an insulation rating approved by Code. G. Circuit wiring running through the fixtures shall be No. 12 AWG with type THMN insulation. There shall be no joints in the wires other than those absolutely required. The fixture wires shall be of sufficient length for making approved connections at the fixture outlets and at the lamp-holders or ballasts. H. Joints and splices within fixtures to be either secured by wire nuts or indent type lug fasteners. 3.9 JUNCTION BOXES FEEDING LIGHT FIXTURES A. For light fixtures installed in or on dropped accessible ceilings the contractor shall provide a junction box on the structure above light fixtures and provide a fixture whip from the junction box down to the light fixture. A maximum of 4 fixtures will be allowed to be fed from a single junction box. The contractor shall size junction box in accordance with code. Looping wiring from fixture to fixture will not be allowed. 3.10 JUNCTION BOXES FOR HOMERUNS A. The contractor shall provide a junction on the ceiling above the light fixture or wiring device which has a homerun indicated. The homerun conduit shall be terminated in this box and MC Cable may be run from this junction box down to the light fixture or wiring device. The minimum size junction box shall be 6” square x 4”D, larger as required by code. 3.11 FIRESAFING AND SMOKE SEAL A. Firesafing and smoke seal is required where pipes, ducts and conduit leave or enter any vertical pipe/duct shaft way at all floors and through all walls above or below any Class “A” acoustical tile ceiling or any space without any type of finished ceiling. B. Firesafing and smoke seal is required for all pipes, ducts or conduit penetrations through rated walls or partitions and at positions separating smoke zones from each other—if smoke zones or plenums are employed in the building. Each of the principle trades—plumbing, sprinklers, HVAC and electrical—are to provide their own pipe and duct sleeves and to do their own Firesafing and smoke seal work. Northampton Bridge Lighting Northampton, MA ELECTRICAL - 41 C. Firesafing and smoke seal of pipe and duct penetrations through non-rated secondary walls within a rated larger area need not require Firesafing and smoke seal until they penetrate the rated walls. D. All Firesafing and smoke seal sealants used on the interior of the building (defined as inside of the weatherproofing system and applied on site) shall comply with the requirements of the following reference standards to comply with the LEED Certified Building Credit 4.1 Low Emitting Materials: Adhesives and Sealants. Adhesives, sealants and sealant primers: South Coast Air Quality Management District (SCAQMD) Rule #1168. E. Firesafing and smoke seal materials are as follows: 1. Fire Stop sealant shall be FS One High Performance Intumescent Fire Stop sealant by Hilti 2. Self-leveling fire stop shall be CP 604 sealant by Hilti. 3. All Firesafing materials must be Low Emitting and be at or below LEED maximum VOC levels. 4. All Firesafing material must be non-combustible as defined by NFPA standard 220 when tested in accordance with ASTM E136; melt point - 200ºF; when in contact with metal, be non-corrosive meeting FS-HH-1-558 B; “k” value of 0.25 or less per ASTM C 518; the material shall be moisture-resistant, mildew, vermin-proof and non-deteriorating. The Firesafing insulation shall be fire containment tests per ASTM E119. 3.12 SPLICES A. Make splices for #10 or smaller conductors with UL approved solderless connectors based on 3M Co. “Scotch-lock” Type Y, R, G or B, Buchanan, or T&B “Stakon”. Make splices, cable taps, and terminals for #8 or larger conductors with UL approved bolted pressure conductors of bronze or copper construction equal to those manufactured by T&B or Burndy. END OF SECTION