BUSHEY, MATTHEW - UPDATED SOLAR PLANS 07/01/2022INSTALLATION OF NEW
ROOF MOUNTED PV SOLAR SYSTEM
984 PARK HILL ROAD
NORTHAMPTON, MA 01062
42.288522,-72.713352
PARK HILL ROAD
R2 SYSTEM SIZE INCREASE / TRENCH 6/30/2022
R1 REMOVE P METER 3/9/2022
P1 ISSUED TO TOWNSHIP FOR PERMIT 2/9/2022
NO.DESCRIPTION DATE
BUSHEY, MATTHEW-
TRINITY ACCT #: 2022-01-664504
984 PARK HILL ROAD
NORTHAMPTON, MA 01062
42.288522,-72.713352
PROPOSED PV SOLAR SYSTEM
DRAWING DATE:2/9/2022
DRAWN BY:MD
REVISED BY:DMR
DC SYSTEM SIZE:13.2kW
AC SYSTEM SIZE:10kW
MODULE COUNT:33
MODULES USED:HANWHA 400
MODULE SPEC #:Q.PEAK DUO BLK ML-G10+ 400
UTILITY COMPANY:NAT'L GRID
UTILITY ACCT #:2652151027
UTILITY METER #:23593245
DEAL TYPE:SUNNOVA
R2
R
2211 Allenwood Road
Wall, New Jersey 07719
877-786-7283
www.Trinity-Solar.com
ROOF 1 MODULES: 14 PITCH: 20 ORIENTATION: 174
ROOF 2 MODULES: 0 PITCH: 20° ORIENTATION: 354°
ROOF 3 MODULES: 19 PITCH: 20 ORIENTATION: 174
ROOF 4 MODULES: 0 PITCH: 18° ORIENTATION: 174°
ROOF 5 MODULES: 0 PITCH: 20° ORIENTATION: 354°
ROOF 6 MODULES: 0 PITCH: 20° ORIENTATION: 354°
D
DC
ep M
DC
AC NS270901352
2
5
4531542.288522,-72.713352
33 HANWHA 400 (Q.PEAK DUO BLK ML-G10+ 400)
1 SE10000H-US0SHBNC4
INSIDE OUTSIDE.
OUTSIDE (UTILITY ACCESSIBLE)OUTSIDE.
R2 SYSTEM SIZE INCREASE / TRENCH 6/30/2022
R1 REMOVE P METER 3/9/2022
P1 ISSUED TO TOWNSHIP FOR PERMIT 2/9/2022
NO.DESCRIPTION DATE
BUSHEY, MATTHEW-
TRINITY ACCT #: 2022-01-664504
984 PARK HILL ROAD
NORTHAMPTON, MA 01062
42.288522,-72.713352
PROPOSED PV SOLAR SYSTEM
DRAWING DATE:2/9/2022
DRAWN BY:MD
REVISED BY:DMR
DC SYSTEM SIZE:13.2kW
AC SYSTEM SIZE:10kW
MODULE COUNT:33
MODULES USED:HANWHA 400
MODULE SPEC #:Q.PEAK DUO BLK ML-G10+ 400
UTILITY COMPANY:NAT'L GRID
UTILITY ACCT #:2652151027
UTILITY METER #:23593245
DEAL TYPE:SUNNOVA
R2
NOTES:
1.) ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE
WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS.
2.)
3.) ALL LOCATIONS ARE APPROXIMATE AND REQUIRE FIELD VERIFICATION.
ALL OUTDOOR EQUIPMENT SHALL BE RAIN TIGHT WITH MINIMUM NEMA 3R RATING.
M
UD SP
P
DC
AC
ep
D
DC R
2211 Allenwood Road
Wall, New Jersey 07719
877-786-7283
www.Trinity-Solar.com
SD
TS
CALCULATIONS FOR CURRENT CARRYING CONDUCTORS
REQUIRED CONDUCTOR AMPACITY PER STRING
[NEC 690.8(B)(1)]: (15.00*1.25)1 = 18.75A
AWG #10, DERATED AMPACITY
AMBIENT TEMP: 33°C, TEMP DERATING FACTOR: .96
RACEWAY DERATING = 6 CCC: 0.80
(40*.96)0.80 = 30.72A
30.72A >_ 18.75A, THEREFORE WIRE SIZE IS VALID
TOTAL AC REQUIRED CONDUCTOR AMPACITY
42.00A*1.25 = 52.50A
AWG #6, DERATED AMPACITYAMBIENT TEMP: 30°C, TEMP DERATING: 1.0
RACEWAY DERATING <_ 3 CCC: N/A
75A*1.0 = 75A
75A >_ 52.50A, THEREFORE AC WIRE SIZE IS VALID
CALCULATION FOR PV OVERCURRENT PROTECTION
TOTAL INVERTER CURRENT: 42.00A
42.00A*1.25 = 52.50A
--> 60A OVERCURRENT PROTECTION IS VALID
ARRAY CIRCUIT WIRING NOTES1.) LICENSED ELECTRICIAN ASSUMES ALL RESPONSIBILITYFOR DETERMINING ONSITE CONDITIONS ANDEXECUTING INSTALLATION IN ACCORDANCE WITHNEC 2020
2.) LOWEST EXPECTED AMBIENT TEMPERATURE BASED ON
ASHRAE MINIMUM MEAN EXTREME DRY BULB
TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. LOWEST EXPECTED AMBIENT
TEMP = -16°C
3.) HIGHEST CONTINUOUS AMBIENT TEMPERATURE BASED
ON ASHRAE HIGHEST MONTH 2% DRY BULB
TEMPERATURE FOR ASHRAE LOCATION MOST SIMILAR TO
INSTALLATION LOCATION. HIGHEST CONTINUOUS TEMP =
33°C
4.) 2005 ASHRAE FUNDAMENTALS 2% DESIGN
TEMPERATURES DO NOT EXCEED 47°C IN THE UNITED
STATES (PALM SPRINGS, CA IS 44.1°C). FOR LESS THAN 9
CURRENT-CARRYING CONDUCTORS IN A ROOF-MOUNTED
SUNLIT CONDUIT AT LEAST 0.5" ABOVE ROOF AND USING
THE OUTDOOR DESIGN TEMPERATURE OF 47°C OR LESS
(ALL OF UNITED STATES)
5.) PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGSSHALL INCLUDE A RAPID SHUTDOWN FUNCTION THATCONTROLS SPECIFIC CONDUCTORS IN ACCORDANCE WITH
NEC 690.12(A) THROUGH (D)
6.) PHOTOVOLTAIC POWER SYSTEMS SHALL BE PERMITTED
TO OPERATE WITH UNGROUNDED PHOTOVOLTAIC
SOURCE AND OUTPUT CIRCUIT AS PER NEC 690.41 (A)(4)
7.) UNGROUNDED DC CIRCUIT CONDUCTORS SHALL BE
IDENTIFIED WITH THE FOLLOWING OUTER FINISH:
POSITIVE CONDUCTORS = RED
NEGATIVE CONDUCTORS = BLACK
NEC 210.5(C)(2)
8.) ARRAY AND SUB ARRAY CONDUCTORS SHALL BE #10 PV
WIRE TYPE RHW-2 OR EQUIVELANT AND SHALL BE
PROTECTED BY CONDUIT WHERE EXPOSED TO DIRECT
SUNLIGHT. SUB ARRAY CONDUIT LONGER THAN 24” SHALL
CONTAIN ≤ 20 CURRENT CARYING CONDUCTORS AND
WHERE EXPOSED TO DIRECT SUNLIGHT SHALL CONTAIN ≤
9 CURRENT CARRYING CONDUCTORS.
9.) ALL WIRE LENGTHS SHALL BE LESS THAN 100' UNLESS
OTHERWISE NOTED
10.) FLEXIBLE CONDUIT SHALL NOT BE INSTALLED ON
ROOFTOP AND SHALL BE LIMITED TO 12” IF USED
OUTDOORS
11.)OVERCURRENT PROTECTION FOR CONDUCTORS
CONNECTED TO THE SUPPLY SIDE OF A SERVICE SHALL BELOCATED WITHIN 10' OF THE POINT OF CONNECTION NEC690.9(A)(3)(2)
12.) WHERE TWO SOURCES FEED A BUSSBAR, ONE A
UTILITY AND THE OTHER AN INVERTER, PV BACKFEED
BREAKER(S) SHALL BE LOCATED OPPOSITE FROM UTILITY
NEC 705.12(B)(3)(2)
13.) ALL SOLAR SYSTEM LOAD CENTERS TO CONTAIN ONLY
GENERATION CIRCUITS AND NO UNUSED POSITIONS OR
LOADS
14.) ALL EQUIPMENT INSTALLED OUTDOORS SHALL HAVE
A NEMA 3R RATING
LOCKABLE 60A DISCONNECT
FUSED W/ 60A FUSES
SQUARE D
PN: D222NRB
ISOLATED NEUTRAL
240V 1Ø
NEUTRALEXISTING MAIN BREAKER LOAD CENTER
INSULATED LINE TAPS INSTALLED ON
MAIN FEEDERS
NEC 705.12(A)
M
2p100AMAIN240V 1Ø
100A MAIN BREAKER
100A BUSBAR
EXISTING
1Ø 120/240V
UTILITY METER
INVERTER #1 - SE10000H-US0SHBNC4
DC AC
Imp 27 Pout 10000
Vmp 400 Imax 42
Voc 480 OCPDmin 52.5
Isc 45 Vnom 240
PV MODULE SPECIFICATIONS
HANWHA 400 (Q.PEAK DUO BLK ML-G10+ 400)
Imp 10.77
Vmp 37.13
Voc 45.3
Isc 11.14
EG
NOTE:
INTERNAL REVENUE GRADE MONITORING
CONTAINED WITHIN SOLAR EDGE INVERTER
SOLAR EDGE PN. RWND-3D-240-MB
A #6 THWN-2 GEC TO EXISTING GROUND ROD G 3/4'' CONDUIT W/ 2-#6 THWN-2, 1-#6 THWN-2, 1-#8 THWN-2 GROUND
B 3/4'' CONDUIT W/ 2-#10 THWN-2, 1-#10 THWN-2 GROUND H 1" PVC W/ 2-#10 THWN-2, 1-#10 THWN-2 GROUND (TRENCHED APPROX. 15')
C 3/4'' CONDUIT W/ 6-#10 THWN-2, 1-#10 THWN-2 GROUND
D 3/4'' CONDUIT W/ 4-#10 THWN-2, 1-#10 THWN-2 GROUND
E 3/4'' CONDUIT W/ 2-#6 THWN-2, 1-#10 THWN-2, 1-#10 THWN-2 GROUND
F #10 PV WIRE (FREE AIR) W/ #6 BARE COPPER BOND TO ARRAY
NOTE: CONDUIT TYPE SHALL BE CHOSEN BY THE INSTALLATION CONTRACTOR
TO MEET OR EXCEED NEC AND LOCAL AHJD REQUIREMENTS
INVERTER #1
PV+L1 L2 N PV-C
f
f
SOLAR MODULES MOUNTED TO ROOF ON 2 ARRAYS
33 - 400W MODULES W/ 1 SOLAR EDGE P401 PER MODULE
15 ADC MAX PER STRING
[TOTAL]
1 STRING OF 10 MODULES IN SERIES - 400 Vmax
1 STRING OF 9 MODULES IN SERIES - 400 Vmax
1 STRING OF 14 MODULES IN SERIES - 400 Vmax
*3 STRINGS TO BE TERMINATED IN PARALLEL INSIDE INVERTER 1
[DWELLING]
1 STRING OF 10 MODULES IN SERIES - 400 Vmax
1 STRING OF 9 MODULES IN SERIES - 400 Vmax
[DETACHED GARAGE]
1 STRING OF 14 MODULES IN SERIES - 400 Vmax
8"x8"
JUNCTION
BOX
8"x8"
JUNCTION
BOX
DC DISCONNECT
B
D
H 6"x6"
JUNCTION
BOX
R2 SYSTEM SIZE INCREASE / TRENCH 6/30/2022
R1 REMOVE P METER 3/9/2022
P1 ISSUED TO TOWNSHIP FOR PERMIT 2/9/2022
NO.DESCRIPTION DATE
BUSHEY, MATTHEW-
TRINITY ACCT #: 2022-01-664504
984 PARK HILL ROAD
NORTHAMPTON, MA 01062
42.288522,-72.713352
PROPOSED PV SOLAR SYSTEM
DRAWING DATE:2/9/2022
DRAWN BY:MD
REVISED BY:DMR
DC SYSTEM SIZE:13.2kW
AC SYSTEM SIZE:10kW
MODULE COUNT:33
MODULES USED:HANWHA 400
MODULE SPEC #:Q.PEAK DUO BLK ML-G10+ 400
UTILITY COMPANY:NAT'L GRID
UTILITY ACCT #:2652151027
UTILITY METER #:23593245
DEAL TYPE:SUNNOVA
R2
R
2211 Allenwood Road
Wall, New Jersey 07719
877-786-7283
www.Trinity-Solar.com
JOB NAME:BUSHEY, MATTHEW-
ADDRESS:984 Park Hill Road
Northampton, MA 01062
42.288522,-72.713352
71.885 ESTIMATED PERSONNEL HOURS 3 DAYS 2.25 DAYS 1.5 DAYS
•33 HANWHA 400's (13.2KW)(CREW OF 3)(CREW OF 4)(CREW OF 6)
•2 SEPARATE ARRAYS
•18' PEAK TO GROUND
•33 PORTRAIT & 0 LANDSCAPED
•1 INVERTERS INSTALLED OUTSIDE
•15' TRENCH
ESTIMATED SENT TO JOB USED
□HANWHA 400 (Q.PEAK DUO BLK ML-G10+ 400)33 ______
□P401 SE OPTIMIZERS 33 ______
□SE10000H-US0SHBNC4 1 ______
□60A OUTDOOR FUSED DISCONNECT W/ (2) 60A FUSES 1 ______
□60A OUTDOOR NON-FUSED DISCONNECT 1 ______
□SOLADECK BOX(ES) & HAYCO CONNECTOR(S)2 ______
□PV LEAD WIRE 150'______
□INSULATED BUG BITES (LINE TAPS)2 ______
□CASE(S) OF BLACK SPRAY PAINT 1 ______
□CASE(S) OF TAR 1 ______
□ECOFASTEN 2012021 CF STD RAIL MLL AL 165.4 19 ______
□ECOFASTEN 2012013 CF RAIL SPLICE 13 ______
□ECOFASTEN 2099017 CF END CLAMP 32MM BLK 20 ______
□ECOFASTEN 2099022 CF MID CLAMP SHORT BLK 56 ______
□ECOFASTEN 4011011 MODULE JUMPER 3 ______
□GROUNDING LUG (NOT PROVIDED BY ECOFASTEN)2 ______
□ECOFASTEN 2012022 CF UNIV L-FOOT MLL 3 70 ______
□ECOFASTEN 3012020 GF-1 FLASHING GLV BLK 8 x 10 70 ______
□ECOFASTEN 2012019 CF MLPE MOUNT 33 ______
□ECOFASTEN 2012020 CF WIRE MGMT CLIP 33 ______
□ECOFASTEN 2012024 CF END CAP 20 ______
MATERIAL LIST
R(FOR INTERNAL USE ONLY)
2211 Allenwood Road
Wall, New Jersey 07719
877-786-7283
www.Trinity-Solar.com
INSTALLATION OF NEW
ROOF MOUNTED PV SOLAR SYSTEM
984 PARK HILL ROAD
BUSHEY, MATTHEW-
984 PARK HILL ROAD
NORTHAMPTON, MA 01062
42.288522,-72.713352
R
APPENDIX
CONTENTS
LABELS, STICKERS, AND PLACARDS
EQUIPMENT DATA SHEETS
2211 Allenwood Road
Wall, New Jersey 07719
877-786-7283
www.Trinity-Solar.com