Information required pursuant to the Massachusetts State Building Code 780 CMR,
1301.8.4.1.
Owner: Northampton Co-Op Bank
Designers of Record: Lindgren& Sharples, P.C.
Consulting Engineers
Date of Submittal: November 22, 2004
1. Design Intent
• This project consists of a new branch bank building and retail building. This
project will include the installation of new gas fired furnaces and air
conditioning for both buildings.
• The Project is located at 8 Main Street. The Building Use Group for the Bank
Building is Business B with construction type 3B unprotected. The retail
building is mercantile construction 3B as defined by the Massachusetts State
Building Code.
• The building consists of approximately 2,400 square feet of floor space on one
level for the Bank, and 2,600 square feet of floor space for the Retail
Building.
• Both buildings are new construction with exposed standing seam metal roof
and exposures on north, south, east and west elevations. The operating
schedule is 12 hours/day six days per week...
L&S 1081 Page 1
• Heating will be supplied from two gas-fired high efficiency furnaces per
building, each sized and controlled to achieve operating flexibility and
efficient operation.
• Lighting and power systems have been designed to provide proper ambient
light, accent lighting as well as operating flexibility and efficient operation.
• The designer of record will verify that the systems have been installed in
substantial accordance with the approved construction documents, in
conformance with 780 CMR 1301.8.4.4.
2. Basis of Design
• The following are the assumptions used to calculate the capacities and
parameters for the building components.
HVAC
Interior temperature set points:
• 70 deg. F. heating when occupied; 55 deg. F. heating when unoccupied.
• 74 deg. F. cooling when occupied; 90 deg. F. cooling when unoccupied.
Outdoor ambient design temperatures:
• 0 deg. F. winter
• 87 deg. F. db, 73 deg. F. wb summer
Occupancy
• 24 - Bank
• 45 - Retail
Envelope
• 3035 sf gross wall area - Bank
• 381 sf gross glass area - Bank
• 3081 sf gross wall area - Retail
• 372 sf gross glass area - Retail
• 14'-0"envelop wall height
• All walls are masonry with furred-out metal studs.
• Glass is double-glazed, low-E, insulating glass.
• Glass and walls have a north, south, east, and west exposure.
L&S 1081 Page 2
• Mechanical outside ventilation air is provided at 15 cfm/occupant.
Lighting
• 50 foot candles ambient lighting provided offices—Bank.
• 5 foot candles general lighting for Retail Building—(temporary).
• 1.2 watts per gross square foot for ambien�lighting.
• 30 foot candles general lighting for all corridor, storage areas.
3. Sequence of Operations and Interactions
HVAC
• Heating will be provided by two gas-fired furnaces (per building). Each unit
will be controlled buy local programmable thermostat allowing for variable
space set points and occupancy schedules.
• Fresh air motorized dampers will be open during all occupied periods
providing code-compliant ventilations. Fresh air damper will be closed during
off-hour unoccupied periods.
Lighting
• Emergency lighting and exit sign lighting will be fed from self contained
battery packs.
• All lighting will be controlled by local switches.
4. Systems and Equipment Capacities
HVAC
• The new furnaces and cooling coils will be a �onstant volume air system. The
furnaces are hi efficiency 92% conder . style. Each unit is rated for
t� Y ( ) g Y
93,000 Btuh heating, 48,000 Btuh cooling, and will provide 400 cfm of
outside ventilation air.
Lighting
• The ambient lighting system will be accomplished with a combination of
direct and indirect fluorescent fixtures. The lighting controls will be located
locally and operated with ease.
L&S 1081 Page 3
5. Testing
• The following tests and inspections shall be performed by the General
Contractor with the Owner and the Owners representative present. The test
and inspections must comply with the criteria stated for the work to be
accepted.
HVAC
• Inspect new furnaces, coils and fans for any physical damage. There shall be
no dents or distortion of the metal.
• Inspect new furnaces, coils and fans for any unusual noise or vibration. There
shall be no unusual noise or vibration when the unit is operating.
• Inspect new piping and equipment for leaks.
• The HVAC system shall be tested to verify that the final TAB report is
correct. Readings within 10% of those listed on the final TAB report shall be
considered acceptable. If the readings are not acceptable, then all systems in
the space must be balanced and a new final TAB report prepared. After the
new final TAB report is issued, all HVAC systems in that space will be tested
to verify that the new final report is correct.
• Verify that the HVAC system is functioning correctly. The control valves
shall operate when the space sensor calls for heat and the air conditioner must
function when the space sensor calls for cooling. The outside air damper shall
open when the temperature control system is in the occupied mode and shall
remain closed when the temperature control system is in the unoccupied
mode.
Lighting
• Demonstrate that the time clocks controlling the lighting system automatically
turn the lights off and on at the prescribed times.
• Inspect that all lamps in all the fixtures are functioning.
6. Operation Manuals and Maintenance Manuals
When the buildings are completed and ready for occupancy, the General Contractor
shall provide the following items before the review and final testing will begin.
L&S 1081 Page 4
HVAC
• Two complete sets of operating manuals.
• Two complete sets of maintenance manuals. The manuals shall cover all new
HVAC equipment.
Electrical
• Two complete sets of operating manuals. The manuals shall cover occupancy
sensors,time clock controls, and light fixtures
7. Record Drawings and Control Documents
When the both buildings are complete and ready for occupancy, the General
Contractor shall provide the following items before the review and final testing will
begin.
• As-Built Drawings for the HVAC, electrical, and lighting systems.
• Copy of the final test, adjust and balance (TAB)report.
***END OF NARRATIVE***
REPORT BY: Marvin Blakley
ers/1256/admin
L&S 1081 Page 5
" gal
19AA I<
Envelope Compliance Report
Massachusetts Commercial Code rn2
C UMc beck-EZ Sofiu are Version 2.4 Release 1 !
Data filename:1\1:\04019-NCR-FLorence\Uocumenv',Com Chcck energy analysis bank cck.cck
Li l NOLV ,21 200Section l: Project Information 4Project Name: Nunhampton Cooperative Bank-Banl:fiuilding OEPTOr fHSP ,JR Main Street � 9� �CT10ryS
1060
Florence. M A 01060
Dc5igner/Contractor: Kuhn Riddle Architect;
7 North Pleasanst Street
Amhcrnt.MA 01002
Document Author: Erica Gccs AIA
Section 2: General Information
Building Location: Northamptcn.Massachusetts
Climate 7one: 14a
Heating Uegrce (ba,c 65 dcgrce.s F): 6894
Cooling Dcercc Da%s(base 65 degrees F): .i-)7
Building Use Method of Compliance: Whoic Building Method
Building 7 ire _-, Floor Arta
Office 2401
Project De:criprton(check unc):
•_ New C'onstructton —Addition Alteration _Unconditioned Shell(File Affidavit)
Section 3: Requirements Checklist
Air Lcakake.Component Certif5catinn,and Vapor Retarder Requirements
Inspection Approved Initial
Date (Y/N)
All joint~and penetrations are caulked.gasketed,
weather-stnpped,or uthcntisc sealed _
Window,,doors,and>kylighu certified
as meeting leakage requirement:
Component R-value:&U-factors labeled as certified
Vapor retarder inaulied
Climate-Specific Requirements
Gross Caviry Cont. Proposed Budget
Component Namt,'Dcscription Area R-Value R-Value U-Factor U-Factor
Rool'l: All-Wood Joi::VRafter/Trua 2401 38.0 0.0 0.028 0.054
Exterior Wall 1: Solid Concrete or Masonry=8'•
rtlrring: Metal 2731 16.2 0.0 0.120 0.079
Windov. l: Wood Frame. Double Pane with Low-E
Clear.;hgc 0.28 21R --- --- 0.430 0.547
Window 2:
Metal Frame with Thermal Break.Triple Pane N."ith Low-E
Tinted.shvc US 31 --- --- 0.630(b) 0.547
Door 1: Solid 21 - --- 0.180 0.127
EXLcrior Wall 2: Mctal Frame. 16" O.C. 254 0.0 19.0 0.047 0.079
Window 3:
Metal f=rame with Themial Break. Double Pane with Low-E
Clear.shgc 0.28 70 --- --- 0.280 0.547
Door 4. Air Lock Entry 62 — -- 0.630(b) 0.127
Interior Will 2: Nfetal Frame. 16" o.c. 1036 5.0 5.0 0.094 0.127
Floor l: Unheated Slab-Un-Grade, Depth 4 R.ie) 220 — 10.0 -- —
(a) Budget l!-launr..arc u,vd for 3ul'a.are baseline calculations ONLY,and arc not code requirements.
(b)Claimed perfonnancc dim not cxcaed dcfaulrc in Tahlcs 1301.9.: 1.No manufacturer certification required.
(c)Ccrtain building uac qTc-require crnrinuous under-:Irh in-•uLiiirn(,cam Massachusetts Code Section 1304.2.7 and 1304.2.S).
Envelope PASSES: Design 2R°ln boner than code
Section 4: Compliance Statement
The proposed envelope design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this permit application. The proposed envelope system has been designed to meet
the Massachusetts C otnmcrcial Code requirements in COMcheck-EZ Version 2.4 Release 1.
09-ICs} 2&;6
Principal Envelope Designer-Name Signature Date
11LJV`! 1JLJ lllal 'f1V LV J1 vt1 a�vua• • �✓✓...... •�.•..-� v �
Lighting Compliance Certificate
Massachusetts Commercial Code
CONlcheck-L•Z Sollmurc Venion 2.4 Rcicasc 1
Data filename: M:\0401 A -NCB -FLorencecDocumenta\Com Check energy analysis bank:cckcck
Section l: Project Information
Project Name: North=pton Cooperative Bank-Bank Building
R Main Street
Florence. MA 01000
Designer'C'ontractor. Kuhn {fiddle A.rchi ects
7 North Pleasarst Street
Amherst.MA 01002
Docwnent .kuthor: Erica Gees AIA
Section 2: General Information
Building Location: Northampton,Massachuscru
Climate Zonc: 14a
Heating Degree Days(base 65 degrees F): 0894
Cooling Degree Days(base 65 degree:F): 507
Building Use Method of Compliance: Whole Building Method
Building Type _ _ __ __ __ Floor Area
Office ?401
Project Description(check:one):
New Construction Addition _Alteration _Unconditioned Shell(File Aifida,-it)
Section 3: Requirements Checklist
Inspection Approved Initial
Date (Y/N)
Controls, SA itching.and Wiring
lndcpcndcnt controls for each space(switclvoccupancy sensor)
Exceprinns Securiry lighting,building lobby/retail store/mall
Master switch at entry to hoteUmotel guest room
Two s vuchc>. dimmer. or occupancy sensor in each space providing
a uniform illumination pattern
Exceplium:
Only one luminaire in space;
Aii occupant-:encin„, device controls the area:
The area is a corridor.starage.restroom.or lobby
Photocelllwtmnomical time,witch on exterior lichts
Exccpriat.c.
i.arge covered irzi.,requiring lighting during daylight hours
Tandem wind one-lamp and duce-lamp ballasted luminaires _
E•xceprinns:
Electronic high-frrqucncy ballasted luminaires not on same.witch
Interior Lighting
11' r v yv ry •.�.- .-v-vv-v-r ------ ----
TSA%1
Lighting Application Worksheet
Massachusetts Commercial Code
CONIcht�ck-FZ Software Ver.ion 2.4 Release l
Section 1: Allowed Lighting Power Calculation
A B C D
Total
Floor Allowed Allowed
Area Watts Wats
Buildin!T\pc _ (Q) (watts./ft2) (B x C)-
Office
)_Offce 2401 1.3 3121
Total Allowed Watts= 3121
Section 2: Actual Lighting Power Calculation
A B C D C F
FLUUre fixture Dc,criptiun/ Lamps/ it of Fixture
ID Lamp Description;WauaKe Per Lamp/Ballast Fixture Fixtures Watt. D( x F)
A C'FILING RECESSED 124"TR 17W/Electronic 2 17 34 578
B CFTT TNC'r RF.CESSM/ 24"TRU 32W!Flectronic 2 6 64 384
D ('L•ILNG RL•CL•SSL•D/48" f8 32W/Electronic 2 8 64 512
E CEILNG RECESSED/48" TR 32W/Electronic 1 2 34 68
F CF.U..NG RFCESSFT)/Other/F..lectronic 2 2 64 128
G CUL1NG RECESSED/Other/ L•'lectronic 2 6 52 312
H CEILING RECESSED/Other/ Electronic 1 7 32 224
i PF.ND-,,NT /Incandescent 6OW 3 1 180 180
L RECC'ESSD SOFFIT 148"T8 32W/Electronic 2 4 64 256
N SURl'ACE PLNDANT 148" T8 32W/Electronic 2 ? 64 128
P CEILNC'r PENDANT/Incandescent 60W 3 1 180 180
Q WAT.I. Si RFACF/24" TR 17W/Electronic 2 1 34 34
R WM l 12r-CI'SSF0 /OTher/Electronic 1 2 32 64
U UNDLIL COUNTER LIGHT/24" 'r8 17W/Llectronic 1 2 17 34
Total Actual Watts= 3082
Section 3: Compliance Calculation
If the Tourl.411an•cal [Fairs minus the Toral,lcrua/Warts is greater than or equal to zero.the building complies.
Total Allowed Watts= 3121
Total Actual Watts= 3082
Project Compliancc= 39
Lighting PASSES: Dc>ign 1^/4 better than code
ii. rv. vi sv.ry • u. Fav rv..s..r� ..�.+.. ..�........ ....�.. � ..
Total actual watt.: must he less than or equal to total allowed watts
Allowed Wan; Actual WAILS Complies(Y'N)
3131 3092 YES
Exterior Lighting
Typc(a)of cxtcnor lighting sources:
fluorescent Metal Halide _ High-Pr. Sodium _
Excepl ul1!':
Specialized signal.directional. and marker lighting. lighting highlighting exterior features of historic buildings:
advertising signage:safcty or security lighting: lout-voltage landscape lighting.
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans,bpecifications and
other calculations submitted With thi;permit application. The proposed lighting system has been designed to meet
the Massachusetts Commercial Code requirements in COMcbecl:-EZ Vcrsion 2.4 Release 1.
t I 2.)4+-f ,
Principal Lighting Da!zigner-Name Signature Date
-- - - - — - - - -- krGTAIL,
Envelope Compliance Report
Massachusetts Commercial Code
COMchc-cd-EZ Software Version 2.4 Release 1
Data filen:unc: M:'04018 -NCB -FT.orence\Documentt\Com Check energy analysis retail.eck
Section 1: Project Information
Project Nan-tc: Northampton Cooperative Bank-Retail Building
R Main Street
Florence, MA 01060
Dc,igncr/Contractor: Kuhn Riddle Architects
7 North Plcasanst Street
Anihergt_MA 01002
Documcnt.Author: Erica Gees AIA
Section 2: General Information
Building Location: Northampton,Massachusetts
Climate Zone: l4a
1 leating Degree Days(bane 65 degrees F): 6894
Cooling Degree Days(base 65 degrees F): 507
Building U:ie Method of Compliance: Whole Building Method
Building TyRc door Area
Retail 2660
Protect Decription (check one):
New Ccn-,trUCLIon Additien Alteration Unconditioned Shell(File Affidavit)
Section 3: Requirements Checklist
Air Leakage, Component Certification, and Vapor Retarder Requirements
Inspection Approved Initial
Date (Y/1)
All joints and penetration:are caulked,gasketed.
weather-stripped. or otherwise sealed
Windows.doors.and skylights certified
as meeting leakage requirements
Component R-value.&U-factors labeled as certified
Vapor retarder installed
e-
Climate-Specific Requirements
Gros Cavity Con(. Proposed Budget
Component N3me/Oz.:crip6on Area R-Value R-Value U-Factor U-Factor
Roof 1: .411-Wnod.lni:t/Rafter/Truss 2660 38.0 0.0 0.028 0.054
L`Merior Wall 1: Solid Concrete or lviasonry>8"
Furring: Meral 3081 16.2 0.0 0.120 0.079
Window 1: Wood I-rame,Double Pane with I-ow-E
Clcar.:hgc 0'F 270 --- -- 0.430 0.547
Door l: Solid 42 — -- 0.179 0.127
Door 4; Glass,Clear, 4)gc 0.54 102 — -- 0.430 0.547
Floor 1: Unheated Slahb-On-Grade, Depth 4 ft.th1 216 — 10.0 -- --
(:11 BudFut l)-hicu�n arc used For suftware ha.�clme calculations ONLY.and are not code requirements.
(b)Cmain builtdine use typrs require continuous under-slab insulation(sc c Massachusens Code Section 13(43 2.7 and 13(4 .2.8).
Envelope PASSES: Design 29"4 better than code
Section 4: Compliance Statement
The proposal (mvelope deign represented in this document is consistent with the building plans, specifications and
other calculations submitted with(his permit application. The proposed envelope system has been designed to meet
the NfissachuFetuz Commercial Code requirements in COlvicheck-EZ Version 2.4 Release 1.
Wo 04
Principal Em clupe Designer-Name Signature Date
Lighting Compliance Certificate
Massachusetts Commercial Code
COMcheck--EZ Softu-are Version 2.4 Rclease 1
Daft filename:W04018 -NCB-FLorencc''Docum nts\Com Check energy analysis retail.cck
Section 1: Project Information
Project Name: Northampton Cooperative Bank-Retail Building
8 Main Street
Florence,MA 01060
Designer/Contractor: Kuhn Riddle Architects
7 North Pleasanst Street
Amherst.MA 01002
Document Author: Erica Gees AIA
Section 2: General Information
Building Location: Northampton,Massachnaems
Climate 'Lone: 14a
Heating Dcgrec Day.(b3-.;c 65 degrees F): 6894
Cooling Degree Days(base 65 degrees F): 507
Building Use Method of Compliance: Whole Building Method
Building Type Floor Arca
Rctail 2660
Project Dezzcription (check one):
Ncw Cunstructiun Addition Alteration Unconditioned Shell(File Affidavit)
Section 3: Requirements Checklist
inspection Approved Initial
Date (YIN)
Controls.$,-i itching. and Wiring
Independent controls for each space(switch/occupancy sensor)
Excepliuns: Security lighting.building lobby/retail store/mall
Master switch at entry to hotel/motel guest room
Two switches, dinuner,or occupancy sensor in each space providing
I a uniform illum I narion pattem
Exceptions:
Only one luminaire in space:
An occupant-scmiing dt-\•icc controls the arca:
The area is a corridor, storage.restroom, or lobby
PhotocclUastronomical time switch on cxtcrior lights
l;xceprin ns:
Large cuN,crcd areas requiring lighting during daylight hours
Tandem wired one-lamp and three-lamp ballasted luminaires
Exceptions:
Electronic hich-frcquency ballasted luminaires not on same switch
Interior Lighting
Total actual watts must be less than or equal to total allowed watts
Allowed Watts Acmal Watts Complies(Y,N)
5054 2892 YES
Exterior Lighting
Type(s) of cxtcrior lighting sources:
_Fluorescent _Metal Halide —High-Pr. Sodium
Exceptinns:
Specialized signal. directional,and marker lighting; lighting highlighting cxtcrior features of historic buildings,
advertising signage: Safety or Security lighting: low-voltage landscape lighting.
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans,specifications and
other calculations submitted with this pemtit application. Tlie proposed lighting system ha_s been designed to meet
the Mascachusemq Commercial Code requirements in COMcheck-L•Z Version 2.4 Rckwe 1.
Principal Lighting Dciigner-Name Signature Date
R ZTAIL.
Lighting Application Worksheet
Massachusetts Commercial Code
COMcheck-E7-Sofnvarc Version 2.4 Rcicasc 1
Section 1: Allowed Lighting Power Calculation
A B C D
Total
Floor Allowed Allowed
Area Wath Wats
Building Tjre , _ (ft—')) (warts/fr2) (B x C)
Retail 2660 1.9 5054
Total Allowed Watt-= 5054
Section 2: Actual Lighting Power Calculation
A B C D E F
Fixture Fixture Description i Lamps/ R of Fixture
ID lamp Description i Wattage I'er Iam»! Halla-t Fixn,re Fixtures Watt. (D x E)
1 Tcmproary Cagc Light/Incandescent 100W 1 27 100 2700
E Ceilina Recessed/48" T8 32W!Electronic 1 2 32 64
N Surface mounted/48" T8 32W/F,lectronic 2 2 64 128
Total Actual Watt-= 2892
Section 3: Compliance Calculation
!f the Total:l//aired 11*aus minus the Total.4crual Warts i.-greater than or equal to zero,the building complies.
Total Allowed Wats= 5054
Total Actual Watt,= 2892
Project Compliance= 2162
Lighting PASSES: Design 43%better than code
I
NORTHAMPTON CO-OP BANK
f C',�
ENERGY SYSTEMS
B SIS OF DESIGN FLORENCE,MA
AItRATIVE
pEN�F gar�vSGN, 010
Information required pursuant to the Massachusetts State Building Code 780 CMR,
1301.8.4.1.
Owner: Northampton Co-Op Bank
Designers of Record: Lindgren & Sharples, P.C.
Consulting Engineers
Date of Submittal: November 22, 2004
1. Design Intent
• This project consists of a new branch bank building and retail building. This
project will include the installation of new gas fired furnaces and air
conditioning for both buildings.
• The Project is located at 8 Main Street. The Building Use Group for the Bank
Building is Business B with construction type 3B unprotected. The retail
building is mercantile construction 3B as defined by the Massachusetts State
Building Code.
• The building consists of approximately 2,400 square feet of floor space on one
level for the Bank, and 2,600 square feet of floor space for the Retail
Building.
• Both buildings are new construction with exposed standing seam metal roof
and exposures on north, south, east and west elevations. The operating
schedule is 12 hours/day six days per week...
L&S 1081 Page 1
• Heating will be supplied from two gas-fired high efficiency furnaces per
building, each sized and controlled to achieve operating flexibility and
efficient operation.
• Lighting and power systems have been designed to provide proper ambient
light, accent lighting as well as operating flexibility and efficient operation.
• The designer of record will verify that the systems have been installed in
substantial accordance with the approved construction documents, in
conformance with 780 CMR 1301.8.4.4.
2. Basis of Design
• The following are the assumptions used to calculate the capacities and
parameters for the building components.
HVAC
Interior temperature set points:
• 70 deg. F. heating when occupied; 55 deg. F. heating when unoccupied.
• 74 deg. F. cooling when occupied; 90 deg. F. cooling when unoccupied.
Outdoor ambient design temperatures:
• 0 deg. F. winter
• 87 deg. F. db, 73 deg. F. wb summer
Occupancy
• 24 - Bank
• 45 - Retail
Envelope
• 3035 sf gross wall area - Bank
• 381 sf gross glass area - Bank
• 3081 sf gross wall area - Retail
• 372 sf gross glass area - Retail
• 14'-0" envelop wall height
• All walls are masonry with furred-out metal studs.
• Glass is double-glazed, low-E, insulating glass.
• Glass and walls have a north, south, east, and west exposure.
L&S 1081 Page 2
• Mechanical outside ventilation air is provided at 15 cfin/occupant.
Lighting
• 50 foot candles ambient lighting provided offices—Bank.
• 5 foot candles general lighting for Retail Building—(temporary).
• 1.2 watts per gross square foot for ambient lighting.
• 30 foot candles general lighting for all corridor, storage areas.
3. Sequence of Operations and Interactions
HVAC
• Heating will be provided by two gas-fired furnaces (per building). Each unit
will be controlled buy local programmable thermostat allowing for variable
space set points and occupancy schedules.
• Fresh air motorized dampers will be open during all occupied periods
providing code-compliant ventilations. Fresh air damper will be closed during
off-hour unoccupied periods.
Lighting
• Emergency lighting and exit sign lighting will be fed from self contained
battery packs.
• All lighting will be controlled by local switches.
4. Systems and Equipment Capacities
HVAC
• The new furnaces and cooling coils will be a constant volume air system. The
furnaces are high efficiency (92%) condensing style. Each unit is rated for
93,000 Btuh heating, 48,000 Btuh cooling, and will provide 400 cfm of
outside ventilation air.
Lighting
• The ambient lighting system will be accomplished with a combination of
direct and indirect fluorescent fixtures. The lighting controls will be located
locally and operated with ease.
L&S 1081 Page 3
5. Testing
• The following tests and inspections shall be performed by the General
Contractor with the Owner and the Owners representative present. The test
and inspections must comply with the criteria stated for the work to be
accepted.
HVAC
• Inspect new furnaces, coils and fans for any physical damage. There shall be
no dents or distortion of the metal.
• Inspect new furnaces, coils and fans for any unusual noise or vibration. There
shall be no unusual noise or vibration when the unit is operating.
• Inspect new piping and equipment for leaks.
• The HVAC system shall be tested to verify that the final TAB report is
correct. Readings within 10%of those listed on the final TAB report shall be
considered acceptable. If the readings are not acceptable, then all systems in
the space must be balanced and a new final TAB report prepared. After the
new final TAB report is issued, all HVAC systems in that space will be tested
to verify that the new final report is correct.
• Verify that the HVAC system is functioning correctly. The control valves
shall operate when the space sensor calls for heat and the air conditioner must
function when the space sensor calls for cooling. The outside air damper shall
open when the temperature control system is in the occupied mode and shall
remain closed when the temperature control system is in the unoccupied
mode.
Lighting
• Demonstrate that the time clocks controlling the lighting system automatically
turn the lights off and on at the prescribed times.
• Inspect that all lamps in all the fixtures are functioning.
6. Operation Manuals and Maintenance Manuals
When the buildings are completed and ready for occupancy, the General Contractor
shall provide the following items before the review and final testing will begin.
L&S 1081 Page 4
HVAC
• Two complete sets of operating manuals.
• Two complete sets of maintenance manuals. The manuals shall cover all new
HVAC equipment.
Electrical
• Two complete sets of operating manuals. The manuals shall cover occupancy
sensors,time clock controls, and light fixtures.
7. Record Drawings and Control Documents
When the both buildings are complete and ready for occupancy, the General
Contractor shall provide the following items before the review and final testing will
begin.
• As-Built Drawings for the HVAC, electrical, and lighting systems.
• Copy of the final test, adjust and balance (TAB)report.
***END OF NARRATIVE***
REPORT BY: Marvin Blakley
ers/1256/admin
L&S 1081 Page 5
Envelope Compliance Report
Massachusetts Commercial Code u (j i
CONIchecA-EZSofivare Version 2.4 Release 1 �aV [U Fq
Data filename:M:'�0401 A-NCR-FLorence`d)ocumenb,Com Chcck energy analysis bank cck.cck
L �VEFT_OTr 11 SS ECTIONS
R'HAat,�JON,M,A
Section l: Project Information 01060
Project Name: Northampton Cooperative Bank-Bank Building
F Main Street
Florence, MA 01060
Dcoigncr/Contractor. Kuhn Kiddle Architect.;
7 North Plcasanyt Street
Arnher.,i.MA 01002
Document Author. Erica Gccs Ain
Section 2: General Information
Buildine Location: Northampton.Massachusetts
Climate lone: 14a
Heating Degree Day,(base 65 dcgreex F): 6894
Coolinc Dcercc Days(base 65 decrees F): .i07
Building Use Method of Compliance: NVhoic Building Method
Ruildine'l,me Floor Arra
Office 2401
Project ne:cripnon(check onc):
Ne1v Construction Addition Alteration Unconditioned Shell(File Affidavit)
Section 3: Requirements Checklist
Air Leakage,Component Certification,and Vapor Retarder Requirements
Inspection Approved Initial
Date (Y/N)
All points and penetrations are caulked,ga•keted,
weather-stnpped.orothcrulsc sealed _
Window,,doors,and skylights certified
as meeting leakage requirement;
Component R-value.&U-factors labeled as certified _
Vapor retarder inaolled
-- - - - 1wel.
Climate-Specific Requiremenca
Gross Cavity Cont. Proposed Budget
Component Name/Description Area R-Value R-Value U-Factor U-Factor
Roof l: All-wood Joist/Raftel-/Truss 2401 38.0 0.0 0.028 0.054
Exterior Wall I: Solid Concrete or Masonry=8-
Furring: Metal 2731 16.2 0.0 0.120 0.079
Windom. 1: \Vood 1•rame, Double Pane with Low-E
Clcar.shgc 0.28 218 --- --- 0.430 0.547
Window 2:
Metal Frame with Thermal Break.Triplc Panc with Low-E
Tinted.shoe 0,28 31 --- --- 0.630(b) 0.547
Door 1: Sulid 21 --- --- 0.180 0.127
Exterior Wall?: Mctal Frame. 16" o.c. 254 0.0 19.0 0.047 0.079
Window 3:
Metal game with Themial Break_ Doublc Pane with Low-E
Clear.shgc 02 70 --- --- 0?80 0.547
Door 4: Air Lock Entry 62 — -- 0.630(b) 0.127
Interior W-60i 2: 1`tetal Frame. 16" o.c. 1036 5.0 5.0 0.094 0.127
Floor l: Unheated Slab-On-Gude, Depth 4 fuc) 220 — 10.0 — —
(s'I l3udEct I1-lactim are ua,:d for 3ufo%are ba whnc i:alculations ONLY,and arc not code requirements.
(b)Claimed pcif nnancc docs nor exceed dcfatiltc in Tahlcs 1301 A' 1.No rn.,inufacturcr certification required.
(.e)Certain building use rypt.-require crnrinuow.under-Imb in�ulaiictn(see M3e\u.:huSewo Code Section 1304.2.7 and 1304.2.5).
Envelope PASSES: Design 28°'n bencr than code
Section 4: Compliance Statement
The proposed envelope design represented in this document is consistent with the building plans,specifications and
other calculanons submirred with this permit application. The proposed envelope system has been designed to meet
the Massachusetts C ommcrcial Code requirements in CONIcheck-E[Version 2.4 Release 1.
619-l.0-+ G6a6SIR' til M/041-
Principal Envelope Designer-Name Signature Datc
ISM
Lighting Compliance Certificate
Massachusetts Commercial Code
CONlcheek-EZ Soll urc Version 2.4 Release 1
Data filename:M:10401 R -NCB -FLorencelDocuments\Cam Check energy analysis basil:cck.cck
Section l: Project Information
Project Name: Northampton Cooperative Bank-Bank Building
R Main Srreet
Florence.MA 01060
Design er'C'ontnctor: Kuhn Riddle Architects
7 North Pleasant Street
Amherst.MA 01002
Docwnant Author: Erica Gees AIA
Section 2: General Information
Building Location: Northampton,:Massachuacru
Climate Zone: 14a
Heating.Degree Days(base 65 degrees F): 6994
Cooling Degree Day,(base 65 degrees F): 507
Building Use Method of Compliance: Whole Building:Method
Building Type _ _ __ __ ,_ __ Floor Area
Office 2401
Project De.4cription(check one):
New Construction Addition _Alteration _Unconditioned Shcll(File Affidavit)
Section 3: Requirements Checklist
Inspection Approved Initial
Date (YIN)
Controls,Switching.and Wiring
Independent controls for each space(switclvoccupancy sensor)
Exceptions: Security lighting,building lobby/reran store/mall
blaster�wirch at entry to hotel/motel guest room
Two suitchcs. dimmer. or occupancy sensor in each space providing
a uniform illumination pattern
£xcepriuns:
Only one luminaire in spaec;
A,t occupant-aenzmg device controls the area:
The area is a corridor.storage.re:atroom.or lobby
PhoLuce I11w mnomical time switch on exterior lieltits
Exceprion.N.
Large covered areas requiring lighting during daylight hour,
Tandem wired one-lamp and three-lamp ballasted luminaires _
Lxceprinns:
Electronic high-frrqucncy ballasted luminaires not on same.witch
Interior Lighting
15�•�1 K
Lighting Application Worksheet
Massachusetts Commercial Code
CONIcheck-EZ Software Version 2.4 Release I
Section 1: Allowed Lighting Power Calculation
A B C D
Total
Floor Allowed Allowed
Area Watts Watts
Buildinp-TNpr (ft2) (watts/ft2) (B x C)
Office 2401 1.3 312)
Total Allowed Watts= 3121
Section 2: Actual Lighting Power Calculation
A B C D E F
Fixture I'ixturc Dc,cription/ Lamps/ a of Fixture
ID Lamp Description/W;itlxkc Pcr Lamp/Ballast_ Fixture Fixtures WattD( x Fl
A CFILING RECESSED/24"TR 17W/Electronic 2 17 34 578
B CFTT ING RF.CFSSFD/24" TRU 32W!Electronic 2 6 64 384
D CLILNG KL•CLSSLU/48" 178 32W/Electronic 2 8 64 512
E CEILNG RECESSED/49" TR 32W/Electronic 1 2 34 68
F MING RFCFSSF.D/Other/F..lectronic 2 2 64 128
G CUL1NG RECESSED/Other/ L•'lectranic 2 6 52 312
H CEILING RECESSED/Other! Electronic 1 7 32 224
! PENDANT/Incandescent 60W 3 1 180 180
L RECCESSD SOFFIT 148"T8 32W/Electronic 2 4 64 256
N SURFAC L•' PLNDANT/48" T8 32W/'Electronic 2 2 64 128
P CEII NG PFNDANT/' Incandescent 60W 3 1 180 180
Q WAT.T.1;17RFACF./24" TR 17W !Electronic 2 1 34 34
R W-\I 1. IZFCI'SSFD/OTher/Flectronic 1 2 32 64
U UNDLR COUNTER L1GH'1'%24" '1'8 17W/Mectronic 1 2 17 34
Total Actual Wath= 3082
Section 3: Compliance Calculation
If the Tautl.4/1oired If'WIN minus the Toral,1 crux/ I'Varts is greater than or equal to zero.the building complies.
Total Allowed Watts= 3121
Total Actual Watts= 3082
Project Compliance= 39
Lighting PASSES: Deign 1"/„better than code
Total actual watt.: muet he less than or equal to total allowed watts
Allowed Watts Actual Watts Complies(YN)
3121 3(1R2 YES
Exterior Lighting
Type(;)of cxtcnor lighting sources:
_rluortscent Metal Halide _ High-Pr. Sodium _
facepliuns:
Specialized signal.dircctional. and marker lighting: lighting highlighting exterior features of histone buildings:
advertising:ignagc:safety or security lighting: low-voltage landscape lighting.
Section 4: Compliance Statement
The propoxed lighting design represented in this document i.�consistent with the building plats,specifications and
other calculations submitted with thk permit application. The proposed lighting system has been designed to meet
the Ma«achutetts Commercial Code requircmcnt�in COMcheck-EZ Vcrsion 3.4 Release 1.
f-K1i est- ()c5 A - ti I 2,J a'-f -
Principal Lighting Designer-Name Signature Date
i
Envelope Compliance Report
Massachusetts Commercial Code
COMchrc 6-EZ Software Version 2.4 Release I
Data filename: M:`•0401 S -NCS -FT.orence0ocuments\Com Check energy analysis retail_cck
Section 1: Project Information
Project Namc: Northampton Cooperative Bank-Retail Building
R Main Street
Florence,MA 01060
Dc.igncr/C'omractur: Kuhn Riddle Arclutects
7 North Plcasanst Street
Anther,L MA 01002
Document Author: Erica Gees AIA
Section 2: General Information
Building Location: Northampton,Massachusetts
Climate Zone: l4a
I leating Degree Days (baae 65 degrees F): 6894
Cooling Degree lays(base 65 degrees F): 507
Building Uie Method of Compliance: Whole Building Method
Building Type Floor Area
Retail 2660
Protect Dez-cription (check one):
New Construction Addition Alteration Unconditioned Shell(File Affidavit)
Section 3: Requirements Checklist
Air Leakage, Component Certification, and Vapor Retarder Requirements
Inspection Approved Initial
Date (Y/?)
All joints and penetration: are caulked.gasketed.
weather-stripped. or otherwise sealed
Window,,,doors.and :kyligltts certified
as meeting lc3kagc requirLmLnui ___... .
Component R-value.&U-factors labeled as certified
Vapor retarder installed
2�T�L
Climate-Specific Requirements
Gross Cavity Cont. Proposed Budget
Component Name0e,:erintion Area R-Value R-Value U-Factor U-Factor
Roof 1: .411-Wnnd.loi:dRafter/Trus, 2660 38.0 0.0 0.028 0.054
Exterior Wall 1: Solid Concrete or Masonry>8"
Furring: Meral 3081 16.2 0.0 0.120 0.079
Window l; Wood I-rame.Double Pane with I-ow-E
Clear.shgc U.'F 270 -- -- 0.430 0.547
Door l: Solid 42 — -- 0.179 0.127
Door 4; Glass,Clear,rhgc 0.54 102 — -- 0.430 0.547
Floor 1: Unhcated Slab-On-Grade,Deptlt 4 ft.ih) 216 — 10.0 -- --
(al BuctFct U-rii�u,r�arc u>ed for solmarc ha:zc1ine calculations ONLY.and are not code requirements.
(b)Cu-nain huildine use i\pes require conrinuous under-slab insulation(sa:Massachuscns Code Section 1304?.7 and 1304.2.8).
Envelope P.xSSES: Deign_R"w better than code
Section 4: Compliance Statement
The proposed envelope de iun represartted in this document is consistent with the building plant.;. specifications and
other calculations,ubmittcd Ntith(his permit application. The proposed envelope system has been designed to meet
the Massachusem; Commercial Code requirements in COlvicheck-EZ Version 2.4 Release 1.
hick 61�% tlA d&aar� -- IfIILI 04
Principal En N clupe Designer-Natne Signature Date
Lighting Compliance Certificate
Massachusetts Commercial Code
COMchcck-EZ Soiiu-are Version 2.4 Release 1
Data filename:M:\04018 -NCB -FLorencc'Oocum nts\Com Check energy analysis retail.cck
Section 1: Project Information
Project Name: Northampton Cooperative Bank-Retail Building
R Main Street
Florence,MA 01060
Designer/Contractor: Kuhn Riddle Architects
7 North Pleasanst Street
Amherst-MA 01002
Document Author: Erica Gees AIA
Section 2: General Information
Building Location: Northampton,Massachusetts
Climate 'Lone: 14a
Heating Degree Days(bast 65 degrees F): 6894
Cooling Degree Days(base 65 degrees F): 507
Building Usc Method of Compliance: Whole Building Method
I Building Type Floor Arca
Rctail 2660
Proiect Dezzcripuon (cheek one):
New Cun-,tructiun Addition Alreration Unconditioned Shell(bile Affidavit)
Section 3: Requirements Checklist
Tnspection Approved Initial
Date (YrN)
Controls.Sri itching. and Wiring
Independent control,for each space(switch/occupancy sensor)
Excepliuns: Security lighting.building lobby/retail store/mall
Master:Witch ar entry to hoteUmorel guest room
Two switches, dinuner,or occupancy sensor in each space providing
I a uniform illum narion pattern
Exceprion.�:
Only one luminaire in space:
An occupant-scmiing dt\•icc control; the area:
The area is a corridor, stnrage.restroom,or lobby
Photocell/a.;tronomical time switch on exterior lights
EYceprin n c:
Large cu\,crcd areas rcyuiring lighting during daylight huurs
Tandem wired one-lamp and three-lamp ballasted luminaires
Exceptions:
Electronic hich-frequency ballasted luminaires not on same switch
Interior Lighting
Total actual waus must be less than or equal to total allowed watts
Allowed Watts Actual Watts Contplies(Y,N)
5054 2892 YES
Exterior Lighting
Type(s) of cxlcrior lighting sources:
Fluorescent _Metal Halide —High-Pr. Sodium
Exceptions:
Specialized signal, directional, and marker lighting; lighting highlighting ruerior features of historic buildings:
advertising signage: safety or security lighting: low-voltage landscape lighting.
Section 4: Compliance Statement
The proposed lighting design represented in this document is consistent with the building plans,specification-,and
other calculations submitted with this permir application. The proposed lighting system has been designed to meet
the Massachusetts Commercial Code requirements in COMcheck-L•Z Version 2.4 Rcic&-e 1.
Principal Lighting Dc:�igncr-Name Signature Date
R ZTA i ..
Lighting Application Worksheet
Massachusetts Commercial Code
COMcheck-E7_Softiearc Version 2.4 Rcicasc 1
Section 1: Allowed Lighting Power Calculation
A B C D
Total
Floor Allowed Allowed
Area Watts Watts
Buildine Tire _ (ft2) (warts/fr2) (B x C)
Retail 2660 1.9 5054
Total Allowed Watts= 5054
Section 2: Actual Lighting Power Calculation
A B C D E F
Fixture Fixture Description/ Lamps/ 9 of Fixturc
Lamp Description/ Watraee I'er limn! hlallaci Fixn,re Fixtures Watt. D( x E)
I Tcmproary Caec Light/Incandescent 100W 1 27 100 2700
E Ceiling Recessed/48" T8 32W/Electronic 1 2 32 64
N Curface mounted/49" T8 32W/F,lectronic 2 2 64 128
Total Actual Wath= 2892
Section 3: Compliance Calculation
If the Total Allowed Watts minus the Total Actual Warts is greater than or equal to zero,the building complies.
Total Allowed Warts= 5054
Total Actual Watb= 2892
Project Compliance= 2162
Lighting PASSES: Design 43%better than code
I
TRANSMITTAL
No. 00058
AQUADRO & C,E.RRI-�l l
PO Box 656•Notthatnpton M A 09060 •P 413 5844022-F413 5840011
PROJECT: NCB - Florence Branch DATE: 11/24/2004
TO: Northampton Building Department REF: Energy Compliance
212 Main Street
Northampton , MA 01 T6LL
E C k u-`Yl—-FAX#PAGES
i NOV 2 4 2004
ATTN: Ton Patillo �" -
y I nF�nr PI III N&Ir,IksoECTIONS�
..
WE ARE SENDING: SUBMITTED FOR: ACTION TAKEN:
Shop Drawings V Approval Approved as Submitted
Letter Your Use Approved as Noted
❑ Prints ❑ As Requested ❑ Returned After Loan
❑ Change Order ❑ Review and Comment ❑ Resubmit
❑ Plans ❑ Submit
❑ Samples SENT VIA: R Returned
❑ Specifications ❑Attached ❑ Returned for Corrections
❑ Other: ❑Separate Cover Via: ❑ Due Date:
ITEM NO. COPIES DATE ITEM NUMBER REV.NO. DESCRIPTION STATUS
2 11/24/200, Envelope Compliance Report
2 11/24/200, Energy System Narrative
Remarks:
✓7 I
CC: Signed:
Bryan Gleason
Expedition 10