Loading...
18C-042 Attic Girder CalcsCS Structure™ 2.14.50 [Build 4] kmBeamEngine 4.13.4.1 Materials Database 1530 ContemporaryConservatoryRobert 9-25-15 7:16am 1 of 3 All product names are trademarks of their respective owners Copyright (C) 2015 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications. Doug Hodgins rk Miles Inc. 21 West St. West Hatfield Ma. Member Data Description: CalcG1 Member Type: Girder Application: Floor Comments:Top Lateral Bracing: Continuous Bottom Lateral Bracing: Continuous Standard Load: Moisture Condition: Dry Building Code: IBC/IRC Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.6 PLF Filename: C:\KMW\JOBS\ Other Loads Type (Description) Side Begin End Trib. Width Other Start End Dead Start End Category Replacement Uniform (PLF) Top 0' 0.00" 10' 6.00" 75 25 Live 1 2 10 6 0 10 6 0 Bearings and Reactions Input Min Gravity Gravity Location Type Material Length Required Reaction Uplift 1 0' 0.000" Girder SPF Plate (425psi) N/A N/A 526# -- 2 10' 6.000" Girder SPF Plate (425psi) N/A N/A 526# -- Maximum Load Case Reactions Used for applying point loads (or line loads) to carrying members Live Dead 1 373# 152# 2 373# 152# Design spans 10' 0.000" Product: Spruce-Pine-Fir #2 2 x 10 2 ply PASSES DESIGN CHECKS Design assumes continuous lateral bracing along the top chord. Design assumes continuous lateral bracing along the bottom chord. Allowable Stress Design Actual Allowable Capacity Location Loading Positive Moment 1315.# 3431.# 38% 5.25' Total Load D+L Shear 445.# 2498.# 17% 0.26' Total Load D+L LL Deflection 0.0607" 0.3333" L/999+ 5.25' Total Load L TL Deflection 0.0854" 0.5000" L/999+ 5.25' Total Load D+L Control: Positive Moment DOLs: Live=100% Snow=115% Roof=125% Wind=160% This member has been designed in accordance with NDS 2005 Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design. CS Structure™ 2.14.50 [Build 4] kmBeamEngine 4.13.4.1 Materials Database 1530 ContemporaryConservatoryRobert 9-25-15 7:16am 2 of 3 All product names are trademarks of their respective owners Copyright (C) 2015 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications. Doug Hodgins rk Miles Inc. 21 West St. West Hatfield Ma. Member Data Description: CalcG2 Member Type: Girder Application: Floor Comments:Top Lateral Bracing: Continuous Bottom Lateral Bracing: Continuous Standard Load: Moisture Condition: Dry Building Code: IBC/IRC Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 8.4 PLF Filename: C:\KMW\JOBS\ Other Loads Type (Description) Side Begin End Trib. Width Other Start End Dead Start End Category Replacement Uniform (PLF) Top 0' 0.00" 5' 2.50" -53 -13 Live Replacement Uniform (PLF) Top 0' 0.00" 5' 2.50" 27 7 Live Replacement Uniform (PLF) Top 0' 0.00" 5' 2.50" 40 13 Live Replacement Uniform (PLF) Top 0' 0.00" 12' 5.50" 27 7 Live Replacement Uniform (PLF) Top 5' 2.50" 12' 5.50" -53 -13 Live Replacement Uniform (PLF) Top 5' 2.50" 12' 5.50" 27 7 Live Replacement Uniform (PLF) Top 5' 2.50" 12' 5.50" 40 13 Live Point (LBS) Top 5' 1.00" 373 194 Live Point (LBS) Top 12' 0.88" 89 27 Snow 1 2 12 5 8 12 5 8 Bearings and Reactions Input Min Gravity Gravity Location Type Material Length Required Reaction Uplift 1 0' 0.000" Wall SPF Plate (425psi) N/A 1.500" 1091# -339# 2 12' 5.500" Wall SPF Plate (425psi) N/A 1.500" 1006# -312# Maximum Load Case Reactions Used for applying point loads (or line loads) to carrying members Live Snow Dead 1 769# 0# 322# 2 696# 89# 311# Design spans 11' 8.250" Product: Spruce-Pine-Fir #2 2 x 10 3 ply PASSES DESIGN CHECKS NOTE: Pass-thru framing is required at point loads over bearings. Design assumes continuous lateral bracing along the top chord. Design assumes continuous lateral bracing along the bottom chord. Review gravity uplift reaction force of 339lbs at bearing 1 and ensure that the structure can resist appropriately. Review gravity uplift reaction force of 312lbs at bearing 2 and ensure that the structure can resist appropriately. Allowable Stress Design Actual Allowable Capacity Location Loading Positive Moment 3705.# 5919.# 62% 5.08' Total Load D+L Negative Moment 993.# 5919.# 16% 6.23' Total Load D+L Shear 992.# 3746.# 26% 0.4' Total Load D+L LL Deflection 0.1432" 0.3896" L/979 6.23' Total Load L TL Deflection 0.2041" 0.5844" L/687 6.23' Total Load D+L Control: Positive Moment DOLs: Live=100% Snow=115% Roof=125% Wind=160% Design assumes a repetitive member use increase in bending stress: 15 % This member has been designed in accordance with NDS 2005 Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table CS Structure™ 2.14.50 [Build 4] kmBeamEngine 4.13.4.1 Materials Database 1530 ContemporaryConservatoryRobert 9-25-15 7:16am 3 of 3 All product names are trademarks of their respective owners Copyright (C) 2015 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications. Doug Hodgins rk Miles Inc. 21 West St. West Hatfield Ma. Member Data Description: CalcG3 Member Type: Girder Application: Floor Comments:Top Lateral Bracing: Continuous Bottom Lateral Bracing: Continuous Standard Load: Moisture Condition: Dry Building Code: IBC/IRC Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 8.4 PLF Filename: C:\KMW\JOBS\ Other Loads Type (Description) Side Begin End Trib. Width Other Start End Dead Start End Category Replacement Uniform (PLF) Top 0' 0.00" 7' 3.00" 27 7 Live Replacement Uniform (PLF) Top 0' 0.00" 12' 5.50" -53 -13 Live Replacement Uniform (PLF) Top 0' 0.00" 12' 5.50" 27 7 Live Replacement Uniform (PLF) Top 0' 0.00" 12' 5.50" 27 13 Live Replacement Uniform (PLF) Top 7' 3.00" 12' 5.50" 27 7 Live Point (LBS) Top 0' 4.63" 89 27 Snow Point (LBS) Top 7' 4.50" 373 194 Live 1 2 12 5 8 12 5 8 Bearings and Reactions Input Min Gravity Gravity Location Type Material Length Required Reaction Uplift 1 0' 0.000" Wall SPF Plate (425psi) N/A 1.500" 928# -312# 2 12' 5.500" Wall SPF Plate (425psi) N/A 1.500" 1013# -339# Maximum Load Case Reactions Used for applying point loads (or line loads) to carrying members Live Snow Dead 1 618# 89# 311# 2 691# 0# 322# Design spans 11' 8.250" Product: Spruce-Pine-Fir #2 2 x 10 3 ply PASSES DESIGN CHECKS NOTE: Pass-thru framing is required at point loads over bearings. Design assumes continuous lateral bracing along the top chord. Design assumes continuous lateral bracing along the bottom chord. Review gravity uplift reaction force of 312lbs at bearing 1 and ensure that the structure can resist appropriately. Review gravity uplift reaction force of 339lbs at bearing 2 and ensure that the structure can resist appropriately. Allowable Stress Design Actual Allowable Capacity Location Loading Positive Moment 3486.# 5919.# 58% 7.37' Total Load D+L Negative Moment 993.# 5919.# 16% 6.23' Total Load D+L Shear 924.# 3746.# 24% 11.49' Total Load D+L LL Deflection 0.1297" 0.3896" L/999+ 6.23' Total Load L TL Deflection 0.1907" 0.5844" L/735 6.23' Total Load D+L Control: Positive Moment DOLs: Live=100% Snow=115% Roof=125% Wind=160% Design assumes a repetitive member use increase in bending stress: 15 % This member has been designed in accordance with NDS 2005 Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table