22B-043 FD 296 Nonotuck St 2010-07-30Northampton Fire Department
Memorandum
To: Louis Hasbrouck
From: Duane Nichols
Date: July 29, 2010
CC: Larry Therrien
Re: 296 Nonotuck St
Secondary to a review of the plans submitted to me for review, I concur with the issuance of a building permit subject to the following conditions:
Fire alarm and fire suppression work permits shall be obtained for the project. The C/O inspection fee needs to be paid prior approval of any permit. As built plans are fine for this
project.
A graphic representation of the structure must be installed at the Fire Alarm Control Panel (FACP) and/or Fire Alarm Annunciator and/or Communicator. This must be current with on-going
renovations
5 lb ABC Fire extinguishers are needed located at exits. This shall be in compliance with NFPA relative to maximum travel distance. Appropriate signage in compliance with ADA should
be located above
Pull stations and horn/strobes shall be installed in renovated area by exits.
Pull Stations shall be double action type.