24C-013 NORTHAMPTON_SURVIVAL_CENTERCERTIFIED TEST, ADJUST AND BALANCE REPORT
DATE:4/12/2011
PROJECT:NORTHAMPTON SURVIVAL CENTER
LOCATION:NORTHAMPTON, MASSACHUSETTS
CUSTOMER:M. J. MORAN
CONTRACTOR:LABCO Air & Water Balancing, LLC
ADDRESS:PO BOX 316
West Suffield, Connecticut 06093
PHONE 860-668-1329
FAX 860-668-7089
#TB0338407C
T.A.B.B. CERTIFICATION
EXP. 12/2011
SUPPLY FAN REPORT
PROJECT NAME
DATE 4/5/2011
UNIT DATA TEST DATA
SYSTEM #RTU 1 CFM DESIGN 4,000
AREA SERVED STORAGE AREA CFM DELIVERED 3,988
UNIT LOCATION ROOF E.S.P. DESIGN .75"
VOLTAGE 208 / 3 E.S.P. DELIVERED .51''
FAN MFR'R TRANE FAN DESIGN RPM 1,233
FAN MODEL #YHC120E3RHAOBH FAN DELIVERED RPM 4.8 VDC = 1,126
MOTOR MFR'R INACCESSABLE AMPS RATED 8.5
MOTOR HP 3.8 AMPS DELIVERED 2 / 2.4 / 2.4
MOTOR RPM INACCESSABLE S.P.C.P.NOT APPLICABLE
MOTOR S.F.INACCESSABLE V.F.D./VORTEX POS.NOT APPLICABLE
MOTOR FRAME INACCESSABLE SUCTION S.P.-.19''
DRIVE DATA DISCHARGE S.P..32''
MOTOR SHEAVE DIRECT DRIVE
FAN PULLEY DIRECT DRIVE O.A. DESIGN 620 CFM
BELTS DIRECT DRIVE O.A. ACTUAL 637 CFM
SHEAVE POSITION DIRECT DRIVE O.A. CONTROL POS.NOT APPLICABLE
CENTER TO CENTER DIRECT DRIVE
NOTES :
NORTHAMPTON SURVIVAL CENTER
4/12/2011 LAB.CO. AIR AND WATER BALANCING 2
SUPPLY FAN REPORT
PROJECT NAME
DATE 4/5/2011
UNIT DATA TEST DATA
SYSTEM #AHU 1 CFM DESIGN 1,600
AREA SERVED SEMINAR AREA CFM DELIVERED 1,531
UNIT LOCATION CEILING E.S.P. DESIGN .75"
VOLTAGE 120 / 1 E.S.P. DELIVERED .53''
FAN MFR'R TRANE FAN DESIGN RPM 973
FAN MODEL #TUHMC100ACV4 FAN DELIVERED RPM COOL MODE HIGH
MOTOR MFR'R EMERSON AMPS RATED 9.6
MOTOR HP 3/4 AMPS DELIVERED 4.8
MOTOR RPM ECM MOTOR S.P.C.P.NOT APPLICABLE
MOTOR S.F.NOT LISTED V.F.D./VORTEX POS.NOT APPLICABLE
MOTOR FRAME NOT LISTED SUCTION S.P.-.13''
DRIVE DATA DISCHARGE S.P..4''
MOTOR SHEAVE DIRECT DRIVE
FAN PULLEY DIRECT DRIVE O.A. DESIGN 600 CFM
BELTS DIRECT DRIVE O.A. ACTUAL 637 CFM
SHEAVE POSITION DIRECT DRIVE O.A. CONTROL POS.NOT APPLICABLE
CENTER TO CENTER DIRECT DRIVE
NOTES :
NORTHAMPTON SURVIVAL CENTER
4/12/2011 LAB.CO. AIR AND WATER BALANCING 3
AIR OUTLET TEST REPORT
LOCATION:GR.OUTLET AREA K (AK)% OF
NORHTAMPTON SURVIVAL CENTER NO.SIZE (ft2)CFM FPM FPM CFM DESIGN
RTU 1 SUPPLY
OFFICE CUBICAL 1 14X12 1.17 0.64 0.749 500 668 656 491
STORAGE 2 14X12 1.17 0.64 0.749 500 668 696 521
STORAGE 3 14X12 1.17 0.64 0.749 500 668 621 465
RECYCLING / TRASH 4 10X10 0.69 0.64 0.442 150 340 341 151
STAFF TOILET 5 9X9 100 99
STAFF AREA 6 9X9 100 94
VESTIBULE 7 10X10 0.69 0.64 0.442 150 340 338 149
DISTRIBUTION 8 14X12 1.17 0.64 0.749 500 668 641 480
DISTRIBUTION 9 14X12 1.17 0.64 0.749 500 668 671 502
WAITING 10 14X12 1.17 0.64 0.749 400 534 541 405
VESTIBULE 11 10X10 0.69 0.64 0.442 150 340 333 147
CONTROL 12 14X12 1.17 0.64 0.749 400 534 521 390
TOILET 13 6X6 100 93
4,050 3,988 98%
RTU 1 RETURN
PLENUM RETURN 1 34X20 4.72 1 4.72 3,430 727 710 3,351 98%
AHU 1 SUPPLY
OFFICE / INTERVIEW 1 9X9 150 134
ENTRY 2 9X9 100 93
OFFICE / INTERVIEW 3 9X9 150 155
DIRECTOR'S OFFICE 4 12X12 200 201
ZONE DAMPER FOR SEMINAR ROOM
SEMINAR WORKSHOP / CONFERENCE 5 9X9 125 126
SEMINAR WORKSHOP / CONFERENCE 6 9X9 125 134
SEMINAR WORKSHOP / CONFERENCE 7 9X9 125 126
SEMINAR WORKSHOP / CONFERENCE 8 9X9 125 123
OPEN OFFICE 9 9X9 125 111
FILE / COPY 10 9X9 125 121
OFFICE 11 9X9 125 117
TOILET 12 6X6 100 90
1,575 1,531 97%
AHU 1 RETURN
OFFICE / INTERVIEW 1 9X9 90
OFFICE / INTERVIEW 2 9X9 92
DIRECTOR'S OFFICE 3 9X9 110
SEMINAR WORKSHOP / CONFERENCE 4 22X22 249
OPEN OFFICE 5 9X9 180
FILE / COPY 6 9X9 85
OFFICE 7 9X9 88
894
NOTE: AHU1 RETURN HAS NO DESIGN CFM'S ON PRINT.
DESIGN ACTUAL
4/12/2011 LAB.CO. AIR AND WATER BALANCING 4
EXHAUST FAN REPORT
PROJECT NAME
DATE 4/5/2011
SYSTEM NO.EF 1 EF 3 EF 4 EF 5
AREA SERVED TOILET TOILET STAFF TOILET STAFF AREA
FAN LOCATION TOILET TOILET STAFF TOILET STAFF AREA
CFM DESIGN 200 200 450 250
CFM DELIVERED 184 181 182 200
T.S.P. DESIGN .25".25".25".25"
T.S.P. DELIVERED .33".32"0.64".66"
FAN DES. RPM 1,300 1,300 1,000 980
FAN DEL. RPM NOT LISTED NOT LISTED NOT LISTED NOT LISTED
VOLTAGE/PHASE 115 / 1 115 / 1 115 / 1 115 / 1
AMPS RATED 1.7 1.7 2 2
AMPS DEL. 1.7 1.7 1.8 1.8
FAN MFR'R BROAN BROAN BROAN BROAN
FAN MODEL #L200 L200 L250 L250
MOTOR MFR'R BROAN BROAN BROAN BROAN
MOTOR HP NOT LISTED NOT LISTED NOT LISTED NOT LISTED
MOTOR RPM NOT LISTED NOT LISTED NOT LISTED NOT LISTED
MOTOR S.F.NOT LISTED NOT LISTED NOT LISTED NOT LISTED
MOTOR FRAME NOT LISTED NOT LISTED NOT LISTED NOT LISTED
MOTOR SHEAVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
FAN PULLEY DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
BELTS DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
SHEAVE POS.DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
CENTER TO CENTER DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE DIRECT DRIVE
NORTHAMPTON SURVIVAL CENTER
4/12/2011 LAB.CO. AIR AND WATER BALANCING 5
EXHAUST FAN REPORT
PROJECT NAME
JOB #DATE 4/5/2011
SYSTEM NO.EF 6
AREA SERVED SERVER
FAN LOCATION SERVER
CFM DESIGN 250
CFM DELIVERED 198
T.S.P. DESIGN .25"
T.S.P. DELIVERED .35"
FAN DES. RPM 980
FAN DEL. RPM NOT LISTED
VOLTAGE/PHASE 115 / 1
AMPS RATED 1.7
AMPS DEL. 1.7
FAN MFR'R BROAN
FAN MODEL #L200
MOTOR MFR'R BROAN
MOTOR HP NOT LISTED
MOTOR RPM NOT LISTED
MOTOR S.F.NOT LISTED
MOTOR FRAME NOT LISTED
MOTOR SHEAVE DIRECT DRIVE
FAN PULLEY DIRECT DRIVE
BELTS DIRECT DRIVE
SHEAVE POS.DIRECT DRIVE
CENTER TO CENTER DIRECT DRIVE
NORTHAMPTON SURVIVAL CENTER
4/12/2011 LAB.CO. AIR AND WATER BALANCING 6
AIR OUTLET TEST REPORT
LOCATION:GR.OUTLET AREA K (AK)% OF
NORTHAMPTON SURVIVAL CENTER NO.SIZE (ft2)CFM FPM FPM CFM DESIGN
EXHAUST FAN 1
TOILET 1 CEF 200 184 92%
EXHAUST FAN 2
TOILET 1 CEF 200 DELETED
EXHAUST FAN 3
TOILET 1 CEF 200 181 91%
EXHAUST FAN 4
STAFF TOILET 1 CEF 450 182 40%
EXHAUST FAN 5
STAFF AREA 1 CEF 250 200 80%
EXHAUST FAN 6
SERVER ROOM 1 CEF 250 198 79%
DESIGN ACTUAL
NOTE: EXHAUST FAN # 4 IS THE SAME MODEL NUMBER AS EXHAUST FAN # 5. NOT RATED FOR 450 CFM
4/12/2011 LAB.CO. AIR AND WATER BALANCING 7
VELOCITY PRESSURE TRAVERSE REPORT
LOCATION:AREA STATIC % OF
NORTHAMPTON SURVIVAL CENTER WIDTH HEIGHT (ft2)CFM FPM FPM CFM PRESS.DESIGN
RTU 1 BRANCH DIFFUSER 8 - 13 18 RD 1.767 2,050 1160 1157 2,045 100%
RTU 1 BRANCH DIFFUSER 2 - 6 18 RD 1.767 1,350 764 771 1,362 101%
DESIGN ACTUALDUCT
4/12/2011 LAB.CO. AIR AND WATER BALANCING 8