31A-076 Hurley & David - 264 Elm St Phase 2 Submittal (1)
Prepared For:
Hurley & David
Attn: Jessica Smith
Date: September 17, 2013
Customer P.O. Number:
825911
Sold To:
Hurley & David Job Name:
Hurley & David - 264 Elm St Phase 2
Trane U.S. Inc. dba Trane is pleased to provide the enclosed submittal for your review and approval.
Product Summary
Qty Product
1 Packaged Gas/Electric Rooftop Units
1 Split System Air Conditioning Units (Small)
Daniel Lavoie - Trane
90 Carando Drive
Springfield, MA 01104
Phone: (413) 746-3090
Fax: (413) 746-0537
The attached information describes the equipment we propose to
furnish for this project, and is submitted for your approval.
Submittal
J:\JOBS\3\106347\2\Sub.doc
Table Of Contents
Product Summary .......................................................................................................................... 1
Packaged Gas/Electric Rooftop Units (Item A1) ......................................................................... 3
Tag Data ................................................................................................................................................... 3
Product Data ............................................................................................................................................ 3
Performance Data .................................................................................................................................... 3
Mechanical Specifications ........................................................................................................................ 5
Unit Dimensions ....................................................................................................................................... 8
Weight, Clearance & Rigging Diagram ................................................................................................... 10
Accessory ............................................................................................................................................... 12
Split System Air Conditioning Units (Small) (Item B1)............................................................. 13
Tag Data ................................................................................................................................................. 13
Product Data .......................................................................................................................................... 13
Performance Data .................................................................................................................................. 13
Mechanical Specifications ...................................................................................................................... 14
Unit Dimensions ..................................................................................................................................... 16
Weight, Clearance & Rigging Diagram ................................................................................................... 19
Accessory ............................................................................................................................................... 20
Field Installed Options - Part/Order Number Summary ........................................................... 21
Packaged Gas/Electric Rooftop Units ..................................................................................................... 21
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 3 of 21
Tag Data - Packaged Gas/Electric Rooftop Units (Qty: 1)
Item Tag(s) Qty Description Model Number
A1 RTU-2 1 15 Ton Packaged Unitary
Gas/Elec
YHD180F3RLA--H00000000000000000000000
000
Product Data - Packaged Gas/Electric Rooftop Units
Item: A1 Qty: 1 Tag(s): RTU-2
Gas/Electric
High efficiency
Downflow
15 Ton
Major design sequence
208-230/60/3
Reliatel
Gas Heat - Low
Economizer Comparative Enthaply 0-100% with Barometric Relief
3H/2C Touchscreen, programmable, remote temperature, remote humidity (Fld)
10 year heat exchanger warranty
Performance Data - Packaged Gas/Electric Rooftop Units
Tags RTU-2
Design Airflow (cfm) 6000
Cooling Entering Dry Bulb (F) 80.00
Cooling Entering Wet Bulb (F) 67.00
Ent Air Rel Humidity (%) 51.08
Ambient Temp (F) 95.00
Cooling Leaving Unit DB (F) 60.09
Cooling Leaving Unit WB (F) 57.78
Gross Total Capacity (MBh) 181.49
Gross Sensible Capacity (MBh) 138.01
Gross Latent Capacity (MBh) 43.48
Net Total Capacity (MBh) 174.58
Net Sensible Capacity (MBh) 131.10
Net Sensible Heat Ratio (Number) 0.75
Heating LAT (F) 31.18
Heating Temp Rise (F) 31.18
Output Htg Capacity (MBh) 203.00
Output Htg Capacity w/Fan (MBh) 209.91
Design ESP (in H2O) 0.500
Component SP Add (in H2O) 0.200
Field Supplied Drive Kit Required None
Indoor Mtr. Operating Power (bhp) 2.19
Indoor RPM (rpm) 587
Indoor Motor Power (kW) 1.64
Outdoor Motor Power (kW) 0.98
Compressor Power (kW) 12.16
System Power (kW) 14.78
IPLV @ AHRI (IPLV) 13.3
MCA (A) 72.00
MOP (A) 90.00
Compressor 1 RLA (A) 27.60
Compressor 2 RLA (A) 20.50
Condenser Fan FLA (A) 3.20
Evaporator Fan FLA (A) 10.60
Evaporator Face Area (sq ft) 31.42
Evaporator Face Velocity (ft/min) 191
Evaporator Fin Spacing (Per Foot) 180
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 4 of 21
Tags RTU-2
Evaporator Rows ( ) 3
Min. Unit Operating Weight (lb) 1944.0
Max Unit Operating Weight (lb) 2366.0
Fan Motor Heat (MBh) 6.91
Evap Coil Leav Air Temp (DB) (F) 58.70
Evap Coil Leav Air Temp (WB) (F) 57.25
Dew Point Temp (F) 56.32
Rated capacity (AHRI) (MBh) 172.00
Exhaust fan power (kW) 0.56
Refrig charge (HFC-410A) - ckt 1 (lb) 11.9
Refrig charge (HFC-410A) - ckt 2 (lb) 7.2
ASHRAE 90.1 Yes
Saturated Suction Temp Circuit 1 (F) 50.53
Saturated Discharge Temp Circuit 1 (F)
115.36
Saturated Suction Temp Circuit 2 (F) 52.20
Saturated Discharge Temp Circuit 2 (F)
118.67
IEER Rating ( ) 13.30
EER @ AHRI Conditions (EER) 12.0
Total Static Pressure (in H2O) 0.700
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 5 of 21
Mechanical Specifications - Packaged Gas/Electric Rooftop Units
Item: A1 Qty: 1 Tag(s): RTU-2
General
The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 115°F and 0°F in
cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with AHRI testing
procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested
to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to
the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in
accordance to UL 1995/C 22.2, 236-05 3rd Edition.
Casing
Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned,
phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a
salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the
unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than three screws
to remove. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch, 1 pound
density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be
insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material. The downflow unit's base pan shall have no
penetrations within the perimeter of the curb other than the raised 11/8 inch high supply/return openings to provide an
added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift
and crane lifting.
Unit Top
The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage.
Filters
Two inch standard filters shall be factory supplied on all units. Optional two inch pleated media filters shall be available.
Compressors
All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction
gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal
overloads shall be provided with the scroll compressors. All models shall have crankcase heaters, phase monitors and
low and high pressure control as standard.
Crankcase Heaters
These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or
low ambient conditions. These are standard on all Voyager models.
Refrigerant Circuits
Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices, service pressure ports,
and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line
driers.
Evaporator and Condenser Coils
Microchannel coils will be burst tested by the manufacturer. Internally finned, 5/16¿ copper tubes
mechanically bonded to a configured aluminum plate fin shall be standard for evaporator coils.
Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the
pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 psig and
pressure tested to 450 psig. Sloped condensate drain pans are standard.
Gas Heating Section
The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A
forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system.
In order to provide reliable operation, a negative pressure gas valve shall be used on standard furnaces and a pressure
switch on furnaces with modulating heat that requires blower operation to initiate gas flow. On an initial call for heat, the
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 6 of 21
combustion blower shall purge the heat exchanger 45 seconds before ignition. After three unsuccessful ignition
attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for
use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NOx
emissions. The 12½- 25 tons shall have two stage heating (Gas/Electric Only).
Outdoor Fans
The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge
position. The fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection.
Indoor Fan
Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall
have an adjustable idler-arm assembly for quick-adjustment of fan belts and motor sheaves. All motors shall be
thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S.
Energy Policy Act of 1992 (EPACT).
Controls
Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power
wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be
provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling, and/or
ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The
control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building
comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a
higher level of machine protection.
High Pressure Cutout
This option is offered for units that do not have High Pressure cutout as standard.
Economizer - Downflow
The assembly includes fully modulating 0-100 percent motor and dampers, barometric relief, minimum position setting,
preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator. The barometric relief damper shall be
standard with the downflow economizer and shall provide a pressure operated damper that shall be gravity closing and
shall prohibit entrance of outside air during the equipment "off" cycle. Solid state enthalpy and differential enthalpy
control shall be field-installed.
Discharge Line Thermostat
A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system.
This standard option provides extra protection to the compressors against high discharge temperatures in case of loss
of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge
line thermostat is wired in series with high pressure control. When the discharge temperature rises above the protection
limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 VAC circuit. When the temperature
on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor.
When the thermostat opens the fourth time, the ReliaTel control must be manually reset to resume operation on that
stage.
Reference or Comparative Enthalpy
Reference Enthalpy is used to measure and communicate outdoor humidity. The unit receives and uses this information
to provide improved comfort cooling while using the economizer. Comparative Enthalpy measures and communicates
humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this
information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or
Comparative Enthalpy option shall be available when a factory or field installed Downflow Economizer is ordered. This
option is available on all downflow models.
Comparative Enthalpy-Factory Installed
This option will be factory installed to measure and communicate humidity for both outdoor and return air conditions, and
return air temperature. The unit will receive and use this information to maximize use of economizer cooling, and to
provide maximum occupant comfort control.
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 7 of 21
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 8 of 21
Unit Dimensions - Packaged Gas/Electric Rooftop Units
Item: A1 Qty: 1 Tag(s): RTU-2
1. GAS CONNECTION PIPE SIZE 1/2"
121 11/16"
64 1/8"
26 3/4"
84 3/16"
8 15/16"
1"
33 3/16"
2 11/16"
64 11/16"
6"
26 7/16"
68 11/16"76 5/16"
4 1/4"
4 1/4"
28 3/4"19 15/16"
RETURN SUPPLY
GAS CONNECTION (SEE NOTE 1)
NOTES:
PACKAGED GAS/ELECTRIC - DOWNFLOW
7/8" DIA. HOLE
(UNIT CONTROL WIRE)
3" DIA. HOLE
(UNIT POWER WIRE)
DOWNFLOW CONDENSATE
DRAIN CONN 1" NPT
ISOMETRIC DRAWING
PACKAGED GAS/ELECTRIC - DOWNFLOW
PLAN VIEW DRAWING
2. THRU -THE -BASE GAS AND ELECTRICAL IS NOT STANDARD
ON ALL UNITS. (SELECTED OPTION: SEE ACCESSORY SHEET)
3. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 9 of 21
Unit Dimensions - Packaged Gas/Electric Rooftop Units
Item: A1 Qty: 1 Tag(s): RTU-2
N/A
N/A
N/A
N/A
N/A
0.1
3500/2800
1
0.8
2.00
12.0
YHD180F (15.0)
187-253
208
230
60
3
72.0
90.0
90.0
Low
250,000 / 175,000
203,000 / 142,000
2.5 / 14.0
1/2"
2
7.5/4.75
3
27.6/20.5
203.0/155.0
1
3.0
1,740
3
10.6
81.0
2
0.5
1,100
1
3.2
8.8
Throwaway
Yes
8 / 4
20"x20"x2" / 20"x16"x2"
R-410
11.9 lb / 7.2 lb
COMPRESSOR
ELECTRICAL / GENERAL DATA
OUTDOOR MOTOR
(Gas-Fired Heating only)
REFRIGERANT
INDOOR MOTOR
(Field Installed Power Exhaust)
POWER EXHAUST
NOTES:
FILTER
GENERAL PERFORMANCE
GAS HEATING
EER:
Model (Ton):
Circuit #1 / 2
Circuit #1 / 2
COMBUSTION BLOWER
MOTOR
Unit Operating Voltage Range:
Unit Primary Voltage:
Unit Secondary Voltage:
Unit Hertz:
Unit Phase:
Minimum Circuit Ampacity:
Maximum Fuse Size:
Maximum (HACR) Circuit Breaker:
Heating Models:
Heating and 1 Stage Input (Btu/h)
Heating and 1 Stage Output (Btu/h):
Min./Max. Gas Input -
Pressure Natural or LP (in w.c):
Gas Connection Pipe Size:
Number:
Horsepower:
Phase:
Rated Load Amps:
Locked Rotor Amps:
Number:
Horsepower:
Motor Speed (RPM):
Phase:
Full Load Amps:
Locked Rotor Amps:
Number:
Horsepower:
Motor Speed (RPM):
Phase:
Full Load Amps:
Locked Rotor Amps:
Number:
Horsepower:
Motor speed (RPM):
Phase:
Full Load Amps:
Locked Rotor Amps:
Horsepower:
Motor Speed (RPM):
Phase:
Full Load Amps:
Locked Rotor Amps:
Horsepower:
Motor Speed (RPM):
Phase:
Full Load Amps:
Locked Rotor Amps:
Type:
Furnished:
Number:
Recommended Size:
Type:
Factory Charge
Circuit #1 / 2:
Accessory Oversized Motor
(2)
Standard Oversized Motor
(7)
(6)
(8)
(6)Standard Motor
Standard Motor (1) (3) (4)
(6) (4)Standard Oversized Motor Accessory Oversized Motor (6) (4)
Minimum Circuit Ampacity:
Maximum Fuse Size:
Maximum (HACR) Circuit Breaker:
Minimum Circuit Ampacity:
Maximum Fuse Size:
Maximum (HACR) Circuit Breaker:
Number:
Horsepower:
Motor Speed (RPM):
Phase:
Full Load Amps:
Locked Rotor Amps:
1. Maximum (HACR) Circuit Breaker sizing is for installations in the United States only.
2. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
3. Value does not include Power Exhaust Accessory.
4. Value does not include Heater.
5. Value include Standard Motor.
6. Value include Oversized Motor
7. EER is rated at AHRI conditions and in accordance with DOE test procedures.
8. For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.
9. HP for each compressor.
10. TXV/Face-Split Option (Downflow Only) YCD211E3,4,W (EER):12; (System Power kW): 17.33; (Refrigerant Control): Expansion Valve;
11. TXV/Face-Split Option (Downflow Only) YCD241E3,4,W (EER):11; (System Power kW): 22; (Refrigerant Control): Expansion Valve;
12. TXV/Face-Split Option (Downflow Only) YCD301E3,4,W (EER):11; (System Power kW): 25.45; (Refrigerant Control): Expansion Valve;
13. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270 or 370.
14. AFUE is rated in accordance with DOE test procedures.
(10)(11)(12)(13)(14)
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 10 of 21
Weight, Clearance & Rigging Diagram - Packaged Gas/Electric Rooftop Units
Item: A1 Qty: 1 Tag(s): RTU-2
81"
ROOF OPENING
CLEARANCE FROM THE
TOP OF UNIT 72"
(1828.8mm)
UNIT OUTLINE
CLEARANCE 68"
(1727.2mm)
CLEARANCE 60"
(1524mm)
76 1/2"
CLEARANCE 36"
(914.4mm)
CLEARANCE 48"
(1219.2mm)
DOWNFLOW-PACKAGED GAS/ELECTRIC ROOF OPENING CLEARANCE
DOWNFLOW-PACKAGED GAS/ELECTRIC CLEARANCE
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 11 of 21
Weight, Clearance & Rigging Diagram - Packaged Gas/Electric Rooftop Units
Item: A1 Qty: 1 Tag(s): RTU-2
80.0 lb
2613"2129.0 lb 677.0 lb 556.0 lb 407.0 lb 488.0 lb 57"36"
F
E
CORNER WEIGHT
B
C
A
D
RIGGING AND CENTER OF GRAVITY
LPG Conversion Kit
Oversized Motor
Power Exhaust
High Static Drive
Motorized Outside Air Damper
Manual Outside air Damper
Thru the Base Electrical
Unit Mounted Circuit Breaker
Unit Mounted Disconnect
Powered Convenience Outlet
Economizer
Roof Curb
Hinged Doors
Zone Sensor
Accessory
BASE UNIT WEIGHTS
SHIPPING
CENTER OF GRAVITYCORNER WEIGHTS
NET A B C D E
NOTE:
1. CORNER WEIGHTS ARE GIVEN FOR INFORMATION ONLY.
2. TO ESTIMATE SHIPPING WEIGHT OF OPTION/ACCESSORIES ADD 5 LBS TO NET WEIGHT.
3. NET WEIGHT OF OPTIONAL ACCESSORIES SHOULD BE ADD TO UNIT WEIGHT WHEN
ORDERING FACTORY INSTALLED ACCESSORIES.
4. WEIGHTS FOR OPTIONS NOT LISTED ARE < 5 LBS.
5. WEIGHT ARE OF BASE UNIT ONLY. FOR TOTAL WEIGHT, 10 DIGIT FACTORY INSTALLED
OPTION (ECONOMIZER AND/OR OVERSIZED MOTOR OR FIOP/ACCESSORY WEIGHT
MUST BE ADDED.
F
INSTALLED OPTIONS NET WEIGHT DATA
Accessory
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 12 of 21
Accessory - Packaged Gas/Electric Rooftop Units
Item: A1 Qty: 1 Tag(s): RTU-2 78"19 1/2"ECONOMIZER HOODEND PANELACCESS PANELDOWNFLOW ACCESSORY- ECONOMIZER
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 13 of 21
Tag Data - Split System Air Conditioning Units (Small) (Qty: 1)
Item Tag(s) Qty Description Model Number
B1 AH-1, CU-1 1 4 Ton Unitary Split Systems ( SSC
)
4TTR5024E1000-GAM5A0A04M-1S-0----000-
0--0
Product Data - Split System Air Conditioning Units (Small)
Item: B1 Qty: 1 Tag(s): AH-1, CU-1
Split System Cooling Outdoor Unit
2 Ton Nominal Cooling Capacity
200 - 230 Volt 1 Phase 60 Hertz
Air handler
2 Ton Nominal Cooling Capacity
Multi-poise 4-way
Major designs sequence
17.5" wide x 21.5" deep
Multi-speed ECM
Performance Data - Split System Air Conditioning Units (Small)
Tags AH-1, CU-1
Design clg outdoor DB (F) 95.00
Cooling EDB (F) 80.00
Cooling EWB (F) 67.00
Rated gross capacity (AHRI) (Btuh) 21600.00
Clg net total capacity (Btuh) 21800.00
Clg net sensible capacity (Btuh) 17400.00
Clg net latent capacity (Btuh) 4400.00
Calc clg LDB (F) 59.50
Calc clg LWB (F) 58.20
SEER @ AHRI (btuh/watt) 16.25
EER @ AHRI (EER) 13.5
Cooling airflow (cfm) 800
Min system airflow clg (cfm) 700
Max system airflow clg (cfm) 900
AHRI airflow (cfm) 760
AHRI reference number ( ) 4150905
Compressor power @ (specific Ambient) (W) 1357.0
Condenser fan power @ (specific SP) (W) 128.0
Supply fan power @ (specified SP) (W) 115.0
ASHRAE 90.1 S6.4.1 compliant Yes
Blower capability 2.0 ton to
2.5 ton
airflow
80 to 90 second blower off delay Not
Required
OD AHRI Model (Each) -1.00
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 14 of 21
Mechanical Specifications - Split System Air Conditioning Units (Small)
Item: B1 Qty: 1 Tag(s): AH-1, CU-1
GAM5
Air-Tite II cabinet
2% or less air leakage
Precision applied - durable door seals
Specially designed air seal around refrigerant,
Condensate and conduit connections
Double wall foamed cabinet system
R-4.2 insulating value
No loose fiber design
Smooth cleanable interior design
Sweat eliminating design
Composite foamed cabinet doors
Water proof cabinet design
Integrated horizontal drain pans
Modular cabinet with " allen wrench "quick latch" design
Multi-position up/down flow horizontal left/right
Side return option
Control board protection pocket built into cabinet wall
Alert port to view control board codes without door removal
10 alert codes
Low voltage terminal connection point
Quarter turn phillips head door fasteners
Vortica blower with polarized plug connections and integrated slide deck for easy removal
Patented enhanced coil fin
Dual refrigerant compatible as shipped
Slide in electric heaters with polarized plug connections (sold as accessory)
UVC light kit with safety switch and polarized plug connections (sold as accessory)
Labeled panels and connections
Molded in 1" standard filter rail
High efficiency ECM motor
Soft start fan motor operation
Built in fan delay modes
Maximum width of 23 1/2"
Compact 20 13/16" depth with doors removed
Two tone color
Fused 24v power
Safety door switch
1-year warranty
10-year warranty registered
Optional extended warranty available
General - 4TTR5
The 4TTR5 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor
ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and
furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application.
Casing - 4TTR5
Unit casing is constructed of heavy gauge, G90 galvanized steel and painted with a weather-resistant powder painton all
louvers, panels, prepaint on all other panels. Corrosion and weather-proof CMBP-G30 DuraTuff base.
Refrigerant Controls - 4TTR5
Refrigeration system controls include condenser fan and compressor contac-tor. High and low pressure controls are
inherent to the compressor. A factory installed liquid line drier is standard.
Compressor - 4TTR5
The Climatuff compressor features internal over temperature and pressure protection and total dipped hermetic motor.
Other features include: centrifugal oil pump and low vibration and noise.
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 15 of 21
Condenser Coil - 4TTR5
The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by
louvered panels.
Low Ambient Cooling - 4TTR5
As manufactured, this unit has a cool-ing capability to 55 F. The addition of an evaporator defrost control with TXV
permits low ambient cooling to 30 F.
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 16 of 21
Unit Dimensions - Split System Air Conditioning Units (Small)
Item: B1 Qty: 1 Tag(s): AH-1, CU-1
49 7/8"
21 13/16"
1 1/2"
14 1/2"
1 1/2"1 1/2"
17 1/8"
3 3/16"
17 1/2"
1 1/2"
14 1/2"
1 1/2"
39 5/8"
24 3/8"
1 1/2"
21 3/4"
14 3/8"5 15/16"
3"7 5/16"
GAM5A0A18 & 24 AIR HANDLER- COOLING
UNIT DIMENSION DRAWING
3/4" GAS LINE
3/8" LIQUID LINE
CONDENSATE DRAIN
CONDENSATE DRAIN
CONDENSATE DRAIN
NOTES:
1. BADGE ROTATION WILL KEEP BRAND IN CORRECT POSITION.
2. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION.
3. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
4. GAM5 AIR HANDLERS ARE ALL TWO PIECE CABINETS.
5. SEE WEIGHT AND RIGGING PAGE FOR CONDENSATE DRAIN
CONFIGURATION
SEE NOTE 1
CONDENSATE DRAIN
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 17 of 21
Unit Dimensions - Split System Air Conditioning Units (Small)
Item: B1 Qty: 1 Tag(s): AH-1, CU-1
GAM5A0A24M21SA
208
230
60
1
4.0/4.0
15.0/15.0
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1
0.33
1050
1
2.8
-
R410
Brazed
3/4"
3/8"
Throwaway
No
1
16"x20"x1"
120.0 lb
126.0 lb
1. These air handlers are a.r.i. certified with various split system air conditioners and heat pumps
(ari standard 210/240). refer tothesplit system outdoor unit product data guides for performance data.
2. 3/4" male plastic pipe (ref.: astm 1785-76)
3. Minimum filter size for horizontal applications will be based on airflow selection
and will be calculated as follows:
low velocity filter: face area (sq. ft.) = cfm / 300
high velocity filter: face area (sq. ft.) = cfm / 500
4. For customer ease of filter maintenance, it is recommended that a properly sized, remote filter and grille be
installed for horizontal applications. airflow should not exceed the face value of the filter being used
5. Standard mca and mop without electric heat.
NOTES:
REFRIGERANT
Number:
Horsepower:
Motor Speed (RPM):
Phase:
Full Load Amps:
Locked Rotor Amps:
Type:
Furnished:
Number:
Recommended:
FILTERS INDOOR MOTOR
Model:
Unit Primary Voltage:
Unit Secondary Voltage:
Unit Hertz:
Unit Phase:
GENERAL (1)(2)(4)
ELECTRIC HEAT
230 Volt / 208 Volt
ELECTRICAL / GENERAL DATA
STANDARD
Minimum Circuit Ampacity:
Maximum Overload Protection:
230 Volt / 208 Volt
(1)(3)
Capacity Circuit #1:
Capacity Circuit #2:
Capacity Circuit #3:
# of Circuit:
Phase:
Heater Amps Per Circuit Circuit #1:
Heater Amps Per Circuit Circuit #2:
Heater Amps Per Circuit Circuit #3:
Minimum Circuit Ampacity Circuit #1:
Minimum Circuit Ampacity Circuit #2:
Minimum Circuit Ampacity Circuit #3:
Maximum Overload Protection Circuit #1:
Maximum Overload Protection Circuit #2:
Maximum Overload Protection Circuit #3:
(5)Weights
Net:
Shipping:
Type:
REF. Line Connections
Coupling or Conn. Size - Gas:
Coupling or Conn. Size - Liq.:
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 18 of 21
Unit Dimensions - Split System Air Conditioning Units (Small)
Item: B1 Qty: 1 Tag(s): AH-1, CU-1
GAS LINE 1/4" TURN BALL
SERVICE VALVE, 3/4" I.D. FEMALE
BRAZED CONNECTION WITH 1/4" SAE
FLARE PRESSURE TAP FITTING.
LIQUID LINE SERVICE VALVE,
3/8" I.D. FEMALE BRAZE
CONNECTION WITH 1/4" SAE
FLARE PRESSURE TAP FITTING.
7/8" DIA. HOLE
LOW VOLTAGE
1 1/8" DIA. K.O. WITH
7/8" DIA. HOLE IN CONTROL
BOX BOTTOM FOR
ELECTRICAL POWER SUPPLY
32 5/8"
29 3/4"
28 3/4"
20"
1"
7 3/4"5"
2 1/4"
3"
ELECTRICAL
SERVICE PANEL
SERVICE PANEL
SEE NOTE 2
SEE NOTE 1"
AIRHANDLER - 4TTR5024
OUTLINE DRAWING
NOTES
1. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 60"
ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT
POUR DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 12" FROM WALL AND
ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED.
2. ELECTRICAL AND REFRIGERANT COMPONENT CLEARANCES PER PREVAILING CODES.
3. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS
BEFORE INSTALLATION
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 19 of 21
Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Small)
Item: B1 Qty: 1 Tag(s): AH-1, CU-1
NOTES
1. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION.
2. BADGE ROTATION WILL BRAND IN CORRECT POSITION.
VERTICAL DOWNFLOW
FRONT
SIDE
BACK
INLET DUCT
OUTLET DUCT
TO COMBUSTIBLE
MATERIALS (REQUIRED)
SERVICE CLEARANCE
(RECOMMENDED)
0
0
0
0
0
2"
21"
0
0
0
MINIMUM UNIT CLEARANCE TABLE
CLEARANCE NOTES:
* 1" FOR THE FIRST 3 FT. OF OUTLET DUCT
WHEN ELECTRIC HEATERS ARE INSTALED EXCEPT
MODELS BAYHTR1405, 1408, AND 1410 ARE APPROVED FOR
0" PLEMUM AND DUCT CLEARANCE IN THE UPFLOW
CONFIGURATION ONLY ON TWE-P MODELS.
VERTICAL UPFLOW
HORIZONTAL RIGHT FLOW
HORIZONTAL LEFT FLOW
REFRIGERANT CONNECTION
DOWNFLOW CONDENSATE DRAIN
REFRIGERANT
CONNECTION
DOWNFLOW
CONDENSATE
DRAIN
REFRIGERANT CONNECTION
DOWNFLOW CONDENSATE DRAIN
DOWNFLOW CONDENSATE DRAIN
REFRIGERANT CONNECTION
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 20 of 21
Accessory - Split System Air Conditioning Units (Small)
Item: B1 Qty: 1 Tag(s): AH-1, CU-1
W
G
Y
R
B
O
WHITE
GREEN
YELLOW
RED
BLUE
ORANGE
W 3
W 2
W 1
G
YI
O
R
B
YO
COMFORT CONTROL
AIR HANDLER
AIR CONDITIONER
WHITE
GREEN
YELLOW
RED
BLUE
B - BLUE
Y - YELLOW
BLUE
YELLOW
NOTES:
1. * FOR MULTIPLE STAGES OF ELECTRIC HEAT, JUMPER W1, W2, AND W3 TOGETHER IF COMFORT CONTROL HAS
ONLY ONE STAGE OF HEAT.
2. ** R TO ••O JUMPER MUST BE IN PLACE AS SHOWN FOR COOLING ONLY, NON-HEAT PUMP SYSTEMS FOR
PROPER OPERATION.
3. YI AND YO CONNECTIONS MUST BE MADE AS SHOWN FOR FREEZE PROTECTION AND INTERNALLY MOUNTED
CONDENSATE OVER FLOW CIRCUITS TO WORK PROPERLY.
4. INTERNALLY MOUNTED CONDENSATE SWITCH IS OPTIONAL AND MUST BE ORDERED SEPARATELY.
5. IF 3RD PARTY CONDENSATE OVERFLOW SWITCHES ARE INSTALLED, THEY SHOULD BE WIRED IN SERIES
BETWEEN YO AND Y TO THE OUTDOOR UNIT.
6. MAKE CONNECTIONS PER HOOKUP DIAGRAMS.
7. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES
8. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE.
AIR HANDLER HOOK-UP - COOLING
FIELD WIRING DIAGRAM
Hurley & David - 264 Elm St Phase 2 September 17, 2013
FLD = Furnished by Trane U.S. Inc. dba Trane /
Installed by Others
Equipment Submittal Page 21 of 21
Field Installed Options - Part/Order Number Summary
This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order
numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of
material for the job.
Product Family - Packaged Gas/Electric Rooftop Units
Item Tag(s) Qty
Description Model Number
A1 RTU-2 1 15 Ton Packaged Unitary Gas/Elec YHD180F3RLA--H
000000000000000
00000000000
Field Installed Option Description Part/Ordering Number
3H/2C Touchscreen, programmable, remote temperature, remote humidity BAYSTAT152A