Loading...
31A-076 Hurley & David - 264 Elm St Phase 2 Submittal (1) Prepared For: Hurley & David Attn: Jessica Smith Date: September 17, 2013 Customer P.O. Number: 825911 Sold To: Hurley & David Job Name: Hurley & David - 264 Elm St Phase 2 Trane U.S. Inc. dba Trane is pleased to provide the enclosed submittal for your review and approval. Product Summary Qty Product 1 Packaged Gas/Electric Rooftop Units 1 Split System Air Conditioning Units (Small) Daniel Lavoie - Trane 90 Carando Drive Springfield, MA 01104 Phone: (413) 746-3090 Fax: (413) 746-0537 The attached information describes the equipment we propose to furnish for this project, and is submitted for your approval. Submittal J:\JOBS\3\106347\2\Sub.doc Table Of Contents Product Summary .......................................................................................................................... 1 Packaged Gas/Electric Rooftop Units (Item A1) ......................................................................... 3 Tag Data ................................................................................................................................................... 3 Product Data ............................................................................................................................................ 3 Performance Data .................................................................................................................................... 3 Mechanical Specifications ........................................................................................................................ 5 Unit Dimensions ....................................................................................................................................... 8 Weight, Clearance & Rigging Diagram ................................................................................................... 10 Accessory ............................................................................................................................................... 12 Split System Air Conditioning Units (Small) (Item B1)............................................................. 13 Tag Data ................................................................................................................................................. 13 Product Data .......................................................................................................................................... 13 Performance Data .................................................................................................................................. 13 Mechanical Specifications ...................................................................................................................... 14 Unit Dimensions ..................................................................................................................................... 16 Weight, Clearance & Rigging Diagram ................................................................................................... 19 Accessory ............................................................................................................................................... 20 Field Installed Options - Part/Order Number Summary ........................................................... 21 Packaged Gas/Electric Rooftop Units ..................................................................................................... 21 Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 3 of 21 Tag Data - Packaged Gas/Electric Rooftop Units (Qty: 1) Item Tag(s) Qty Description Model Number A1 RTU-2 1 15 Ton Packaged Unitary Gas/Elec YHD180F3RLA--H00000000000000000000000 000 Product Data - Packaged Gas/Electric Rooftop Units Item: A1 Qty: 1 Tag(s): RTU-2 Gas/Electric High efficiency Downflow 15 Ton Major design sequence 208-230/60/3 Reliatel Gas Heat - Low Economizer Comparative Enthaply 0-100% with Barometric Relief 3H/2C Touchscreen, programmable, remote temperature, remote humidity (Fld) 10 year heat exchanger warranty Performance Data - Packaged Gas/Electric Rooftop Units Tags RTU-2 Design Airflow (cfm) 6000 Cooling Entering Dry Bulb (F) 80.00 Cooling Entering Wet Bulb (F) 67.00 Ent Air Rel Humidity (%) 51.08 Ambient Temp (F) 95.00 Cooling Leaving Unit DB (F) 60.09 Cooling Leaving Unit WB (F) 57.78 Gross Total Capacity (MBh) 181.49 Gross Sensible Capacity (MBh) 138.01 Gross Latent Capacity (MBh) 43.48 Net Total Capacity (MBh) 174.58 Net Sensible Capacity (MBh) 131.10 Net Sensible Heat Ratio (Number) 0.75 Heating LAT (F) 31.18 Heating Temp Rise (F) 31.18 Output Htg Capacity (MBh) 203.00 Output Htg Capacity w/Fan (MBh) 209.91 Design ESP (in H2O) 0.500 Component SP Add (in H2O) 0.200 Field Supplied Drive Kit Required None Indoor Mtr. Operating Power (bhp) 2.19 Indoor RPM (rpm) 587 Indoor Motor Power (kW) 1.64 Outdoor Motor Power (kW) 0.98 Compressor Power (kW) 12.16 System Power (kW) 14.78 IPLV @ AHRI (IPLV) 13.3 MCA (A) 72.00 MOP (A) 90.00 Compressor 1 RLA (A) 27.60 Compressor 2 RLA (A) 20.50 Condenser Fan FLA (A) 3.20 Evaporator Fan FLA (A) 10.60 Evaporator Face Area (sq ft) 31.42 Evaporator Face Velocity (ft/min) 191 Evaporator Fin Spacing (Per Foot) 180 Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 4 of 21 Tags RTU-2 Evaporator Rows ( ) 3 Min. Unit Operating Weight (lb) 1944.0 Max Unit Operating Weight (lb) 2366.0 Fan Motor Heat (MBh) 6.91 Evap Coil Leav Air Temp (DB) (F) 58.70 Evap Coil Leav Air Temp (WB) (F) 57.25 Dew Point Temp (F) 56.32 Rated capacity (AHRI) (MBh) 172.00 Exhaust fan power (kW) 0.56 Refrig charge (HFC-410A) - ckt 1 (lb) 11.9 Refrig charge (HFC-410A) - ckt 2 (lb) 7.2 ASHRAE 90.1 Yes Saturated Suction Temp Circuit 1 (F) 50.53 Saturated Discharge Temp Circuit 1 (F) 115.36 Saturated Suction Temp Circuit 2 (F) 52.20 Saturated Discharge Temp Circuit 2 (F) 118.67 IEER Rating ( ) 13.30 EER @ AHRI Conditions (EER) 12.0 Total Static Pressure (in H2O) 0.700 Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 5 of 21 Mechanical Specifications - Packaged Gas/Electric Rooftop Units Item: A1 Qty: 1 Tag(s): RTU-2 General The units shall be dedicated downflow or horizontal airflow. The operating range shall be between 115°F and 0°F in cooling as standard from the factory for all units. Cooling performance shall be rated in accordance with AHRI testing procedures. All units shall be factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check cooling operation, fan and blower rotation and control sequence, before leaving the factory. Wiring internal to the unit shall be colored and numbered for simplified identification. Units shall be UL listed and labeled, classified in accordance to UL 1995/C 22.2, 236-05 3rd Edition. Casing Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Unit's surface shall be tested 672 hours in a salt spray test in compliance with ASTM B117. Cabinet construction shall allow for all maintenance on one side of the unit. In order to ensure a water and air tight seal, service panels shall have lifting handles and no more than three screws to remove. All exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2 inch, 1 pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material. The base of the downflow unit shall be insulated with 1/2 inch, 1 pound density foil-faced, closed-cell material. The downflow unit's base pan shall have no penetrations within the perimeter of the curb other than the raised 11/8 inch high supply/return openings to provide an added water integrity precaution, if the condensate drain backs up. The base of the unit shall have provisions for forklift and crane lifting. Unit Top The top cover shall be one piece, or where seams exist, double hemmed and gasket sealed to prevent water leakage. Filters Two inch standard filters shall be factory supplied on all units. Optional two inch pleated media filters shall be available. Compressors All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of nameplate voltage. Internal overloads shall be provided with the scroll compressors. All models shall have crankcase heaters, phase monitors and low and high pressure control as standard. Crankcase Heaters These band heaters provide improved compressor reliability by warming the oil to prevent migration during off-cycles or low ambient conditions. These are standard on all Voyager models. Refrigerant Circuits Each refrigerant circuit shall have independent fixed orifice or thermostatic expansion devices, service pressure ports, and refrigerant line filter driers factory installed as standard. An area shall be provided for replacement suction line driers. Evaporator and Condenser Coils Microchannel coils will be burst tested by the manufacturer. Internally finned, 5/16¿ copper tubes mechanically bonded to a configured aluminum plate fin shall be standard for evaporator coils. Microchannel condenser coils shall be standard on all units. Coils shall be leak tested to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 225 psig and pressure tested to 450 psig. Sloped condensate drain pans are standard. Gas Heating Section The heating section shall have a drum and tube heat exchanger design using corrosion resistant steel components. A forced combustion blower shall supply premixed fuel to a single burner ignited by a pilotless hot surface ignition system. In order to provide reliable operation, a negative pressure gas valve shall be used on standard furnaces and a pressure switch on furnaces with modulating heat that requires blower operation to initiate gas flow. On an initial call for heat, the Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 6 of 21 combustion blower shall purge the heat exchanger 45 seconds before ignition. After three unsuccessful ignition attempts, the entire heating system shall be locked out until manually reset at the thermostat. Units shall be suitable for use with natural gas or propane (field installed kit) and shall also comply with California requirements for low NOx emissions. The 12½- 25 tons shall have two stage heating (Gas/Electric Only). Outdoor Fans The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection. Indoor Fan Units above shall have belt driven, FC centrifugal fans with adjustable motor sheaves. Units with standard motors shall have an adjustable idler-arm assembly for quick-adjustment of fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static application. All indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT). Controls Unit shall be completely factory wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Unit shall provide an external location for mounting a fused disconnect device. ReliaTel controls shall be provided for all 24 volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized control shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection. High Pressure Cutout This option is offered for units that do not have High Pressure cutout as standard. Economizer - Downflow The assembly includes fully modulating 0-100 percent motor and dampers, barometric relief, minimum position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator. The barometric relief damper shall be standard with the downflow economizer and shall provide a pressure operated damper that shall be gravity closing and shall prohibit entrance of outside air during the equipment "off" cycle. Solid state enthalpy and differential enthalpy control shall be field-installed. Discharge Line Thermostat A bi-metal element discharge line thermostat is installed as a standard option on the discharge line of each system. This standard option provides extra protection to the compressors against high discharge temperatures in case of loss of charge, extremely high ambient and other conditions which could drive the discharge temperature higher. Discharge line thermostat is wired in series with high pressure control. When the discharge temperature rises above the protection limit, the bi-metal disc in the thermostat switches to the off position, opening the 24 VAC circuit. When the temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit, providing power to the compressor. When the thermostat opens the fourth time, the ReliaTel control must be manually reset to resume operation on that stage. Reference or Comparative Enthalpy Reference Enthalpy is used to measure and communicate outdoor humidity. The unit receives and uses this information to provide improved comfort cooling while using the economizer. Comparative Enthalpy measures and communicates humidity for both outdoor and return air conditions, and return air temperature. The unit receives and uses this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Reference or Comparative Enthalpy option shall be available when a factory or field installed Downflow Economizer is ordered. This option is available on all downflow models. Comparative Enthalpy-Factory Installed This option will be factory installed to measure and communicate humidity for both outdoor and return air conditions, and return air temperature. The unit will receive and use this information to maximize use of economizer cooling, and to provide maximum occupant comfort control. Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 7 of 21 Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 8 of 21 Unit Dimensions - Packaged Gas/Electric Rooftop Units Item: A1 Qty: 1 Tag(s): RTU-2 1. GAS CONNECTION PIPE SIZE 1/2" 121 11/16" 64 1/8" 26 3/4" 84 3/16" 8 15/16" 1" 33 3/16" 2 11/16" 64 11/16" 6" 26 7/16" 68 11/16"76 5/16" 4 1/4" 4 1/4" 28 3/4"19 15/16" RETURN SUPPLY GAS CONNECTION (SEE NOTE 1) NOTES: PACKAGED GAS/ELECTRIC - DOWNFLOW 7/8" DIA. HOLE (UNIT CONTROL WIRE) 3" DIA. HOLE (UNIT POWER WIRE) DOWNFLOW CONDENSATE DRAIN CONN 1" NPT ISOMETRIC DRAWING PACKAGED GAS/ELECTRIC - DOWNFLOW PLAN VIEW DRAWING 2. THRU -THE -BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS. (SELECTED OPTION: SEE ACCESSORY SHEET) 3. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 9 of 21 Unit Dimensions - Packaged Gas/Electric Rooftop Units Item: A1 Qty: 1 Tag(s): RTU-2 N/A N/A N/A N/A N/A 0.1 3500/2800 1 0.8 2.00 12.0 YHD180F (15.0) 187-253 208 230 60 3 72.0 90.0 90.0 Low 250,000 / 175,000 203,000 / 142,000 2.5 / 14.0 1/2" 2 7.5/4.75 3 27.6/20.5 203.0/155.0 1 3.0 1,740 3 10.6 81.0 2 0.5 1,100 1 3.2 8.8 Throwaway Yes 8 / 4 20"x20"x2" / 20"x16"x2" R-410 11.9 lb / 7.2 lb COMPRESSOR ELECTRICAL / GENERAL DATA OUTDOOR MOTOR (Gas-Fired Heating only) REFRIGERANT INDOOR MOTOR (Field Installed Power Exhaust) POWER EXHAUST NOTES: FILTER GENERAL PERFORMANCE GAS HEATING EER: Model (Ton): Circuit #1 / 2 Circuit #1 / 2 COMBUSTION BLOWER MOTOR Unit Operating Voltage Range: Unit Primary Voltage: Unit Secondary Voltage: Unit Hertz: Unit Phase: Minimum Circuit Ampacity: Maximum Fuse Size: Maximum (HACR) Circuit Breaker: Heating Models: Heating and 1 Stage Input (Btu/h) Heating and 1 Stage Output (Btu/h): Min./Max. Gas Input - Pressure Natural or LP (in w.c): Gas Connection Pipe Size: Number: Horsepower: Phase: Rated Load Amps: Locked Rotor Amps: Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps: Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps: Number: Horsepower: Motor speed (RPM): Phase: Full Load Amps: Locked Rotor Amps: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps: Type: Furnished: Number: Recommended Size: Type: Factory Charge Circuit #1 / 2: Accessory Oversized Motor (2) Standard Oversized Motor (7) (6) (8) (6)Standard Motor Standard Motor (1) (3) (4) (6) (4)Standard Oversized Motor Accessory Oversized Motor (6) (4) Minimum Circuit Ampacity: Maximum Fuse Size: Maximum (HACR) Circuit Breaker: Minimum Circuit Ampacity: Maximum Fuse Size: Maximum (HACR) Circuit Breaker: Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps: 1. Maximum (HACR) Circuit Breaker sizing is for installations in the United States only. 2. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions. 3. Value does not include Power Exhaust Accessory. 4. Value does not include Heater. 5. Value include Standard Motor. 6. Value include Oversized Motor 7. EER is rated at AHRI conditions and in accordance with DOE test procedures. 8. For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps. 9. HP for each compressor. 10. TXV/Face-Split Option (Downflow Only) YCD211E3,4,W (EER):12; (System Power kW): 17.33; (Refrigerant Control): Expansion Valve; 11. TXV/Face-Split Option (Downflow Only) YCD241E3,4,W (EER):11; (System Power kW): 22; (Refrigerant Control): Expansion Valve; 12. TXV/Face-Split Option (Downflow Only) YCD301E3,4,W (EER):11; (System Power kW): 25.45; (Refrigerant Control): Expansion Valve; 13. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270 or 370. 14. AFUE is rated in accordance with DOE test procedures. (10)(11)(12)(13)(14) Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 10 of 21 Weight, Clearance & Rigging Diagram - Packaged Gas/Electric Rooftop Units Item: A1 Qty: 1 Tag(s): RTU-2 81" ROOF OPENING CLEARANCE FROM THE TOP OF UNIT 72" (1828.8mm) UNIT OUTLINE CLEARANCE 68" (1727.2mm) CLEARANCE 60" (1524mm) 76 1/2" CLEARANCE 36" (914.4mm) CLEARANCE 48" (1219.2mm) DOWNFLOW-PACKAGED GAS/ELECTRIC ROOF OPENING CLEARANCE DOWNFLOW-PACKAGED GAS/ELECTRIC CLEARANCE Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 11 of 21 Weight, Clearance & Rigging Diagram - Packaged Gas/Electric Rooftop Units Item: A1 Qty: 1 Tag(s): RTU-2 80.0 lb 2613"2129.0 lb 677.0 lb 556.0 lb 407.0 lb 488.0 lb 57"36" F E CORNER WEIGHT B C A D RIGGING AND CENTER OF GRAVITY LPG Conversion Kit Oversized Motor Power Exhaust High Static Drive Motorized Outside Air Damper Manual Outside air Damper Thru the Base Electrical Unit Mounted Circuit Breaker Unit Mounted Disconnect Powered Convenience Outlet Economizer Roof Curb Hinged Doors Zone Sensor Accessory BASE UNIT WEIGHTS SHIPPING CENTER OF GRAVITYCORNER WEIGHTS NET A B C D E NOTE: 1. CORNER WEIGHTS ARE GIVEN FOR INFORMATION ONLY. 2. TO ESTIMATE SHIPPING WEIGHT OF OPTION/ACCESSORIES ADD 5 LBS TO NET WEIGHT. 3. NET WEIGHT OF OPTIONAL ACCESSORIES SHOULD BE ADD TO UNIT WEIGHT WHEN ORDERING FACTORY INSTALLED ACCESSORIES. 4. WEIGHTS FOR OPTIONS NOT LISTED ARE < 5 LBS. 5. WEIGHT ARE OF BASE UNIT ONLY. FOR TOTAL WEIGHT, 10 DIGIT FACTORY INSTALLED OPTION (ECONOMIZER AND/OR OVERSIZED MOTOR OR FIOP/ACCESSORY WEIGHT MUST BE ADDED. F INSTALLED OPTIONS NET WEIGHT DATA Accessory Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 12 of 21 Accessory - Packaged Gas/Electric Rooftop Units Item: A1 Qty: 1 Tag(s): RTU-2 78"19 1/2"ECONOMIZER HOODEND PANELACCESS PANELDOWNFLOW ACCESSORY- ECONOMIZER Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 13 of 21 Tag Data - Split System Air Conditioning Units (Small) (Qty: 1) Item Tag(s) Qty Description Model Number B1 AH-1, CU-1 1 4 Ton Unitary Split Systems ( SSC ) 4TTR5024E1000-GAM5A0A04M-1S-0----000- 0--0 Product Data - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): AH-1, CU-1 Split System Cooling Outdoor Unit 2 Ton Nominal Cooling Capacity 200 - 230 Volt 1 Phase 60 Hertz Air handler 2 Ton Nominal Cooling Capacity Multi-poise 4-way Major designs sequence 17.5" wide x 21.5" deep Multi-speed ECM Performance Data - Split System Air Conditioning Units (Small) Tags AH-1, CU-1 Design clg outdoor DB (F) 95.00 Cooling EDB (F) 80.00 Cooling EWB (F) 67.00 Rated gross capacity (AHRI) (Btuh) 21600.00 Clg net total capacity (Btuh) 21800.00 Clg net sensible capacity (Btuh) 17400.00 Clg net latent capacity (Btuh) 4400.00 Calc clg LDB (F) 59.50 Calc clg LWB (F) 58.20 SEER @ AHRI (btuh/watt) 16.25 EER @ AHRI (EER) 13.5 Cooling airflow (cfm) 800 Min system airflow clg (cfm) 700 Max system airflow clg (cfm) 900 AHRI airflow (cfm) 760 AHRI reference number ( ) 4150905 Compressor power @ (specific Ambient) (W) 1357.0 Condenser fan power @ (specific SP) (W) 128.0 Supply fan power @ (specified SP) (W) 115.0 ASHRAE 90.1 S6.4.1 compliant Yes Blower capability 2.0 ton to 2.5 ton airflow 80 to 90 second blower off delay Not Required OD AHRI Model (Each) -1.00 Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 14 of 21 Mechanical Specifications - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): AH-1, CU-1 GAM5 Air-Tite II cabinet 2% or less air leakage Precision applied - durable door seals Specially designed air seal around refrigerant, Condensate and conduit connections Double wall foamed cabinet system R-4.2 insulating value No loose fiber design Smooth cleanable interior design Sweat eliminating design Composite foamed cabinet doors Water proof cabinet design Integrated horizontal drain pans Modular cabinet with " allen wrench "quick latch" design Multi-position up/down flow horizontal left/right Side return option Control board protection pocket built into cabinet wall Alert port to view control board codes without door removal 10 alert codes Low voltage terminal connection point Quarter turn phillips head door fasteners Vortica blower with polarized plug connections and integrated slide deck for easy removal Patented enhanced coil fin Dual refrigerant compatible as shipped Slide in electric heaters with polarized plug connections (sold as accessory) UVC light kit with safety switch and polarized plug connections (sold as accessory) Labeled panels and connections Molded in 1" standard filter rail High efficiency ECM motor Soft start fan motor operation Built in fan delay modes Maximum width of 23 1/2" Compact 20 13/16" depth with doors removed Two tone color Fused 24v power Safety door switch 1-year warranty 10-year warranty registered Optional extended warranty available General - 4TTR5 The 4TTR5 is fully charged from the factory for up to 15 feet of piping. This unit is designed to operate at outdoor ambient temperatures as high as 115°F. Cooling capacities are matched with a wide selection of air handlers and furnace coils that are AHRI certified. The unit is certified to UL 1995. Exterior is designed for outdoor application. Casing - 4TTR5 Unit casing is constructed of heavy gauge, G90 galvanized steel and painted with a weather-resistant powder painton all louvers, panels, prepaint on all other panels. Corrosion and weather-proof CMBP-G30 DuraTuff base. Refrigerant Controls - 4TTR5 Refrigeration system controls include condenser fan and compressor contac-tor. High and low pressure controls are inherent to the compressor. A factory installed liquid line drier is standard. Compressor - 4TTR5 The Climatuff compressor features internal over temperature and pressure protection and total dipped hermetic motor. Other features include: centrifugal oil pump and low vibration and noise. Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 15 of 21 Condenser Coil - 4TTR5 The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Low Ambient Cooling - 4TTR5 As manufactured, this unit has a cool-ing capability to 55 F. The addition of an evaporator defrost control with TXV permits low ambient cooling to 30 F. Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 16 of 21 Unit Dimensions - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): AH-1, CU-1 49 7/8" 21 13/16" 1 1/2" 14 1/2" 1 1/2"1 1/2" 17 1/8" 3 3/16" 17 1/2" 1 1/2" 14 1/2" 1 1/2" 39 5/8" 24 3/8" 1 1/2" 21 3/4" 14 3/8"5 15/16" 3"7 5/16" GAM5A0A18 & 24 AIR HANDLER- COOLING UNIT DIMENSION DRAWING 3/4" GAS LINE 3/8" LIQUID LINE CONDENSATE DRAIN CONDENSATE DRAIN CONDENSATE DRAIN NOTES: 1. BADGE ROTATION WILL KEEP BRAND IN CORRECT POSITION. 2. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. 3. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION 4. GAM5 AIR HANDLERS ARE ALL TWO PIECE CABINETS. 5. SEE WEIGHT AND RIGGING PAGE FOR CONDENSATE DRAIN CONFIGURATION SEE NOTE 1 CONDENSATE DRAIN Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 17 of 21 Unit Dimensions - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): AH-1, CU-1 GAM5A0A24M21SA 208 230 60 1 4.0/4.0 15.0/15.0 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1 0.33 1050 1 2.8 - R410 Brazed 3/4" 3/8" Throwaway No 1 16"x20"x1" 120.0 lb 126.0 lb 1. These air handlers are a.r.i. certified with various split system air conditioners and heat pumps (ari standard 210/240). refer tothesplit system outdoor unit product data guides for performance data. 2. 3/4" male plastic pipe (ref.: astm 1785-76) 3. Minimum filter size for horizontal applications will be based on airflow selection and will be calculated as follows: low velocity filter: face area (sq. ft.) = cfm / 300 high velocity filter: face area (sq. ft.) = cfm / 500 4. For customer ease of filter maintenance, it is recommended that a properly sized, remote filter and grille be installed for horizontal applications. airflow should not exceed the face value of the filter being used 5. Standard mca and mop without electric heat. NOTES: REFRIGERANT Number: Horsepower: Motor Speed (RPM): Phase: Full Load Amps: Locked Rotor Amps: Type: Furnished: Number: Recommended: FILTERS INDOOR MOTOR Model: Unit Primary Voltage: Unit Secondary Voltage: Unit Hertz: Unit Phase: GENERAL (1)(2)(4) ELECTRIC HEAT 230 Volt / 208 Volt ELECTRICAL / GENERAL DATA STANDARD Minimum Circuit Ampacity: Maximum Overload Protection: 230 Volt / 208 Volt (1)(3) Capacity Circuit #1: Capacity Circuit #2: Capacity Circuit #3: # of Circuit: Phase: Heater Amps Per Circuit Circuit #1: Heater Amps Per Circuit Circuit #2: Heater Amps Per Circuit Circuit #3: Minimum Circuit Ampacity Circuit #1: Minimum Circuit Ampacity Circuit #2: Minimum Circuit Ampacity Circuit #3: Maximum Overload Protection Circuit #1: Maximum Overload Protection Circuit #2: Maximum Overload Protection Circuit #3: (5)Weights Net: Shipping: Type: REF. Line Connections Coupling or Conn. Size - Gas: Coupling or Conn. Size - Liq.: Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 18 of 21 Unit Dimensions - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): AH-1, CU-1 GAS LINE 1/4" TURN BALL SERVICE VALVE, 3/4" I.D. FEMALE BRAZED CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING. LIQUID LINE SERVICE VALVE, 3/8" I.D. FEMALE BRAZE CONNECTION WITH 1/4" SAE FLARE PRESSURE TAP FITTING. 7/8" DIA. HOLE LOW VOLTAGE 1 1/8" DIA. K.O. WITH 7/8" DIA. HOLE IN CONTROL BOX BOTTOM FOR ELECTRICAL POWER SUPPLY 32 5/8" 29 3/4" 28 3/4" 20" 1" 7 3/4"5" 2 1/4" 3" ELECTRICAL SERVICE PANEL SERVICE PANEL SEE NOTE 2 SEE NOTE 1" AIRHANDLER - 4TTR5024 OUTLINE DRAWING NOTES 1. TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 60" ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 12" FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED. 2. ELECTRICAL AND REFRIGERANT COMPONENT CLEARANCES PER PREVAILING CODES. 3. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 19 of 21 Weight, Clearance & Rigging Diagram - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): AH-1, CU-1 NOTES 1. NO INTERNAL MODIFICATIONS REQUIRED FOR ANY POSITION. 2. BADGE ROTATION WILL BRAND IN CORRECT POSITION. VERTICAL DOWNFLOW FRONT SIDE BACK INLET DUCT OUTLET DUCT TO COMBUSTIBLE MATERIALS (REQUIRED) SERVICE CLEARANCE (RECOMMENDED) 0 0 0 0 0 2" 21" 0 0 0 MINIMUM UNIT CLEARANCE TABLE CLEARANCE NOTES: * 1" FOR THE FIRST 3 FT. OF OUTLET DUCT WHEN ELECTRIC HEATERS ARE INSTALED EXCEPT MODELS BAYHTR1405, 1408, AND 1410 ARE APPROVED FOR 0" PLEMUM AND DUCT CLEARANCE IN THE UPFLOW CONFIGURATION ONLY ON TWE-P MODELS. VERTICAL UPFLOW HORIZONTAL RIGHT FLOW HORIZONTAL LEFT FLOW REFRIGERANT CONNECTION DOWNFLOW CONDENSATE DRAIN REFRIGERANT CONNECTION DOWNFLOW CONDENSATE DRAIN REFRIGERANT CONNECTION DOWNFLOW CONDENSATE DRAIN DOWNFLOW CONDENSATE DRAIN REFRIGERANT CONNECTION Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 20 of 21 Accessory - Split System Air Conditioning Units (Small) Item: B1 Qty: 1 Tag(s): AH-1, CU-1 W G Y R B O WHITE GREEN YELLOW RED BLUE ORANGE W 3 W 2 W 1 G YI O R B YO COMFORT CONTROL AIR HANDLER AIR CONDITIONER WHITE GREEN YELLOW RED BLUE B - BLUE Y - YELLOW BLUE YELLOW NOTES: 1. * FOR MULTIPLE STAGES OF ELECTRIC HEAT, JUMPER W1, W2, AND W3 TOGETHER IF COMFORT CONTROL HAS ONLY ONE STAGE OF HEAT. 2. ** R TO ••O JUMPER MUST BE IN PLACE AS SHOWN FOR COOLING ONLY, NON-HEAT PUMP SYSTEMS FOR PROPER OPERATION. 3. YI AND YO CONNECTIONS MUST BE MADE AS SHOWN FOR FREEZE PROTECTION AND INTERNALLY MOUNTED CONDENSATE OVER FLOW CIRCUITS TO WORK PROPERLY. 4. INTERNALLY MOUNTED CONDENSATE SWITCH IS OPTIONAL AND MUST BE ORDERED SEPARATELY. 5. IF 3RD PARTY CONDENSATE OVERFLOW SWITCHES ARE INSTALLED, THEY SHOULD BE WIRED IN SERIES BETWEEN YO AND Y TO THE OUTDOOR UNIT. 6. MAKE CONNECTIONS PER HOOKUP DIAGRAMS. 7. POWER WIRING AND GROUNDING OF EQUIPMENT MUST COMPLY WITH LOCAL CODES 8. BE SURE POWER SUPPLY AGREES WITH EQUIPMENT NAMEPLATE. AIR HANDLER HOOK-UP - COOLING FIELD WIRING DIAGRAM Hurley & David - 264 Elm St Phase 2 September 17, 2013 FLD = Furnished by Trane U.S. Inc. dba Trane / Installed by Others Equipment Submittal Page 21 of 21 Field Installed Options - Part/Order Number Summary This is a report to help you locate field installed options that arrive at the jobsite. This report provides part or order numbers for each field installed option, and references it to a specific product tag. It is NOT intended as a bill of material for the job. Product Family - Packaged Gas/Electric Rooftop Units Item Tag(s) Qty Description Model Number A1 RTU-2 1 15 Ton Packaged Unitary Gas/Elec YHD180F3RLA--H 000000000000000 00000000000 Field Installed Option Description Part/Ordering Number 3H/2C Touchscreen, programmable, remote temperature, remote humidity BAYSTAT152A