23A-061 CS 2nd floor Girder CalcsCS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
Keiter63MapleSt - Level 8 5- 7-18
7:19am
1 of 4
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG1 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 4.4 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 4' 1.00" 84 28 Live
1 2
4 1 0
4 1 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 202# --
2 4' 1.000" Wall N/A N/A 1.500" 202# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 145# 56#
2 145# 56#
Design spans
3' 5.375"
Product: Spruce-Pine-Fir #2 2 x 8 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 174.'# 2300.'# 7% 1.97' Total Load D+L
Shear 131.# 1958.# 6% 0.26' Total Load D+L
LL Deflection 0.0020" 0.1149" L/999+ 1.97' Total Load L
TL Deflection 0.0028" 0.1724" L/999+ 1.97' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
Keiter63MapleSt - Level 8 5- 7-18
7:19am
2 of 4
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG2 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 4.4 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 7' 3.75" 167 56 Live
1 2
7 3 12
7 3 12
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 758# --
2 7' 3.750" Wall N/A N/A 1.500" 758# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 557# 200#
2 557# 200#
Design spans
6' 8.125"
Product: Spruce-Pine-Fir #2 2 x 8 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1264.'# 2300.'# 54% 3.59' Total Load D+L
Shear 620.# 1958.# 31% 6.59' Total Load D+L
LL Deflection 0.0560" 0.2226" L/999+ 3.59' Total Load L
TL Deflection 0.0761" 0.3339" L/999+ 3.59' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
Keiter63MapleSt - Level 8 5- 7-18
7:19am
3 of 4
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG4 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 4.4 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 5' 8.75" 5 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 11' 7.75" 27 7 Live
Replacement Uniform (PLF) Top 5' 8.75" 11' 7.75" -53 -13 Live
Replacement Uniform (PLF) Top 5' 8.75" 11' 7.75" 27 7 Live
Replacement Uniform (PLF) Top 5' 8.75" 11' 7.75" 40 13 Live
Point (LBS) Top 5' 10.25" 162 81 Live
1 2
11 7 12
11 7 12
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 479# -70#
2 11' 7.750" Girder N/A N/A N/A 699# -253#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 344# 135#
2 512# 187#
Design spans
10' 11.625"
Product: Spruce-Pine-Fir #2 2 x 8 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 254lbs at bearing 2 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1961.'# 2300.'# 85% 5.85' Total Load D+L
Negative Moment 517.'# 2300.'# 22% 7.52' Total Load D+L
Shear 624.# 1958.# 31% 10.81' Total Load D+L
LL Deflection 0.2133" 0.3656" L/617 5.87' Total Load L
TL Deflection 0.2961" 0.5484" L/444 5.87' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2016.11 [Build 16]
kmBeamEngine 2016.9.0.3
Materials Database 1557
Keiter63MapleSt - Level 8 5- 7-18
7:19am
4 of 4
All product names are trademarks of their respective owners
Copyright (C) 2016 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG5 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 9.6 PLF
Filename: C:\KMW\JOBS\
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 3' 10.00" 5 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 3.00" 27 7 Live
Replacement Uniform (PLF) Top 3' 10.00" 9' 4.00" 27 7 Live
Replacement Uniform (PLF) Top 3' 10.00" 15' 3.00" -53 -13 Live
Replacement Uniform (PLF) Top 3' 10.00" 15' 3.00" 40 13 Live
Replacement Uniform (PLF) Top 9' 4.00" 15' 3.00" 27 7 Live
Point (LBS) Top 0' 4.63" 1 201 Live
Point (LBS) Top 0' 4.63" 363 0 Snow
Point (LBS) Top 3' 11.50" 570 238 Live
1 2
15 3 0
15 3 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1554# -9#
2 15' 3.000" Girder N/A N/A N/A 1110# -387#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 924# 363# 588#
2 795# 0# 316#
Design spans
14' 6.875"
Product: 1-3/4x9-1/2 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 387lbs at bearing 2 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 4750.'# 13958.'# 34% 6.21' Total Load D+L
Negative Moment 1319.'# 13958.'# 9% 8.4' Total Load D+L
Shear 1271.# 6317.# 20% 0.4' Total Load D+L
TL Deflection 0.3638" 0.7286" L/480 7.67' Total Load D+L
LL Deflection 0.2591" 0.4858" L/674 7.67' Total Load L
Control: LL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.