32A-201 garage headers(1)CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:41am
1 of 3
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB13 Member Type: Beam Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 11.7 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 0' 2.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 4' 10.50" 1 105 Live
Replacement Uniform (PLF) Top 0' 0.00" 4' 10.50" 325 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" 0 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" 9 2 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" 27 13 Live
Replacement Uniform (PLF) Top 0' 2.50" 8' 3.00" 27 7 Live
Replacement Uniform (PLF) Top 4' 10.50" 8' 3.00" 1 99 Live
Replacement Uniform (PLF) Top 4' 10.50" 8' 3.00" 316 0 Snow
1 2
8 3 0
8 3 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1884# -222#
2 8' 3.000" Wall N/A N/A 1.500" 1856# -222#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 258# 1317# 567#
2 258# 1299# 556#
Design spans
8' 1.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 3817.'# 24466.'# 15% 4.13' Total Load D+S
Negative Moment 454.'# 21275.'# 2% 4.13' Total Load D+L
Shear 1424.# 9081.# 15% 0.06' Total Load D+S
TL Deflection 0.0466" 0.4073" L/999+ 4.13' Total Load D+S
LL Deflection 0.0326" 0.2715" L/999+ 4.13' Total Load S
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:41am
2 of 3
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB14 Member Type: Beam Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 11.7 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 3' 1.56" 1 99 Live
Replacement Uniform (PLF) Top 0' 0.00" 3' 1.56" 316 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" 0 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" 9 2 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 3.00" 27 13 Live
Replacement Uniform (PLF) Top 3' 1.56" 8' 3.00" 1 105 Live
Replacement Uniform (PLF) Top 3' 1.56" 8' 3.00" 325 0 Snow
1 2
8 3 0
8 3 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1858# -222#
2 8' 3.000" Wall N/A N/A 1.500" 1886# -222#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 258# 1301# 557#
2 258# 1318# 568#
Design spans
8' 1.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 3823.'# 24466.'# 15% 4.13' Total Load D+S
Negative Moment 454.'# 21275.'# 2% 4.13' Total Load D+L
Shear 1425.# 9081.# 15% 7.38' Total Load D+S
TL Deflection 0.0467" 0.4073" L/999+ 4.13' Total Load D+S
LL Deflection 0.0327" 0.2715" L/999+ 4.13' Total Load S
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:41am
3 of 3
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcB15 Member Type: Beam Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 11.7 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 1' 10.38" 1 99 Live
Replacement Uniform (PLF) Top 0' 0.00" 1' 10.38" 316 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 6' 6.38" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 14' 3.00" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 14' 3.00" 0 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 14' 3.00" 9 2 Live
Replacement Uniform (PLF) Top 0' 0.00" 14' 3.00" 27 13 Live
Replacement Uniform (PLF) Top 1' 10.38" 12' 10.38" 1 105 Live
Replacement Uniform (PLF) Top 1' 10.38" 12' 10.38" 325 0 Snow
Replacement Uniform (PLF) Top 6' 6.38" 14' 3.00" 27 7 Live
Replacement Uniform (PLF) Top 12' 10.38" 14' 3.00" 1 99 Live
Replacement Uniform (PLF) Top 12' 10.38" 14' 3.00" 316 0 Snow
1 2
14 3 0
14 3 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 3264# -386#
2 14' 3.000" Wall N/A N/A 1.500" 3269# -386#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 449# 2282# 982#
2 449# 2285# 984#
Design spans
14' 1.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 387lbs at bearing 1 and ensure that the structure can resist appropriately.
Review gravity uplift reaction force of 387lbs at bearing 2 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 11614.'# 24466.'# 47% 7.13' Total Load D+S
Negative Moment 1370.'# 21275.'# 6% 7.13' Total Load D+L
Shear 2823.# 9081.# 31% 13.49' Total Load D+S
TL Deflection 0.4281" 0.7073" L/396 7.13' Total Load D+S
LL Deflection 0.2991" 0.4715" L/567 7.13' Total Load S
Control: LL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives