Member Data
Description: CalcG1 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 3' 2.00" 197 49 Live
Replacement Uniform (PLF) Top 3' 2.00" 3' 9.50" -74 0 Snow
Replacement Uniform (PLF) Top 3' 2.00" 3' 9.50" 150 -13 Live
1 2
3 9 8
3 9 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 402# --
2 3' 9.500" Girder N/A N/A N/A 370# -13#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 315# 0# 87#
2 301# -22# 69#
Design spans
3' 2.500"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 321.'# 10637.'# 3% 1.9' Total Load D+L
Negative Moment 1.'# 12233.'# 0% 3.34' Total Load D+S
Shear 157.# 3948.# 3% 2.54' Total Load D+L
TL Deflection 0.0012" 0.1604" L/999+ 1.9' Total Load D+L
LL Deflection 0.0010" 0.1069" L/999+ 1.9' Total Load L
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
2 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG2 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 3' 10.63" 47 12 Live
Replacement Uniform (PLF) Top 3' 10.63" 3' 11.50" 47 12 Live
Replacement Uniform (PLF) Top 3' 10.63" 3' 11.50" 129 14 Live
1 2
3 11 8
3 11 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 105# --
2 3' 11.500" Wall N/A N/A 1.500" 105# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 77# 29#
2 77# 29#
Design spans
3' 3.375"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 86.'# 10637.'# 0% 1.93' Total Load D+L
Shear 42.# 3948.# 1% 2.59' Total Load D+L
TL Deflection 0.0010" 0.1641" L/999+ 1.93' Total Load D+L
LL Deflection 0.0010" 0.1094" L/999+ 1.93' Total Load L
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
3 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG3 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" 6 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" 40 13 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" 79 104 Snow
1 2
7 10 15
7 10 15
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 875# -215#
2 7' 10.938" Wall N/A N/A 1.500" 875# -215#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 259# 284# 468#
2 259# 284# 468#
Design spans
7' 1.688"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1562.'# 12233.'# 12% 3.96' Total Load D+0.75(L+S)
Negative Moment 386.'# 10637.'# 3% 3.96' Total Load D+L
Shear 633.# 4541.# 13% 6.81' Total Load D+0.75(L+S)
TL Deflection 0.0294" 0.3571" L/999+ 3.96' Total Load D+0.75(L+S)
LL Deflection 0.0137" 0.2380" L/999+ 3.96' Total Load 0.75(L+S)
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
4 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG4 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 11.7 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 10' 9.75" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 10' 9.75" 27 7 Live
Replacement Uniform (PLF) Top 4' 5.75" 9' 5.75" 1 186 Live
Replacement Uniform (PLF) Top 4' 5.75" 9' 5.75" 362 0 Snow
Replacement Uniform (PLF) Top 9' 5.75" 10' 9.75" 1 260 Live
Replacement Uniform (PLF) Top 9' 5.75" 10' 9.75" 521 0 Snow
Point (LBS) Top 0' 4.63" 187 58 Snow
Point (LBS) Top 4' 8.00" -0 441 Live
Point (LBS) Top 4' 8.00" 955 0 Snow
1 2
10 9 12
10 9 12
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 2149# --
2 10' 9.750" Wall N/A N/A 1.500" 3228# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 269# 1380# 769#
2 272# 2067# 1161#
Design spans
10' 0.500"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 7974.'# 24466.'# 32% 5.41' Total Load D+S
Shear 2440.# 9081.# 26% 9.47' Total Load D+S
TL Deflection 0.1404" 0.5021" L/858 5.41' Total Load D+S
LL Deflection 0.0901" 0.3347" L/999+ 5.41' Total Load S
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
5 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG5 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 11.7 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 0.00" 1 73 Live
Replacement Uniform (PLF) Top 0' 0.00" 2' 0.00" 227 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" 40 13 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" 0 81 Live
Replacement Uniform (PLF) Top 2' 0.00" 15' 4.00" 1 85 Live
Replacement Uniform (PLF) Top 2' 0.00" 15' 4.00" 263 0 Snow
Replacement Uniform (PLF) Top 2' 1.75" 15' 4.00" -23 -7 Snow
Point (LBS) Top 0' 4.63" -1012 0 Snow
Point (LBS) Top 0' 4.63" -3 -110 Live
Point (LBS) Top 14' 11.38" 1 84 Live
Point (LBS) Top 14' 11.38" 97 126 Snow
Point (LBS) Top 14' 11.38" 261 0 Snow
Point (LBS) Top 14' 11.38" 35 10 Snow
1 2
15 4 0
15 4 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 3375# -437#
2 15' 4.000" Wall N/A N/A 1.500" 4007# -224#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 682# 845# 1359#
2 686# 2301# 1706#
Design spans
14' 6.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 437lbs at bearing 1 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 12477.'# 24466.'# 50% 7.67' Total Load D+0.75(L+S)
Negative Moment 1623.'# 21275.'# 7% 7.67' Total Load D+L
Shear 2964.# 9081.# 32% 14.22' Total Load D+0.75(L+S)
TL Deflection 0.4874" 0.7281" L/358 7.67' Total Load D+0.75(L+S)
LL Deflection 0.2762" 0.4854" L/632 7.67' Total Load 0.75(L+S)
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
6 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Control: TL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
7 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG6 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 0' 7.50" 150 38 Live
Replacement Uniform (PLF) Top 0' 7.50" 3' 9.50" 197 49 Live
1 2
3 9 8
3 9 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 385# --
2 3' 9.500" Girder N/A N/A N/A 403# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 301# 85#
2 315# 88#
Design spans
3' 2.500"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 322.'# 10637.'# 3% 1.9' Total Load D+L
Shear 156.# 3948.# 3% 0.3' Total Load D+L
TL Deflection 0.0012" 0.1604" L/999+ 1.9' Total Load D+L
LL Deflection 0.0010" 0.1069" L/999+ 1.9' Total Load L
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
8 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG7 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 0' 5.50" 47 12 Live
Replacement Uniform (PLF) Top 0' 0.00" 0' 5.50" 129 14 Live
Replacement Uniform (PLF) Top 0' 5.50" 3' 11.50" 47 12 Live
1 2
3 11 8
3 11 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 116# --
2 3' 11.500" Girder N/A N/A N/A 105# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 86# 30#
2 77# 29#
Design spans
3' 3.375"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 87.'# 10637.'# 0% 2.03' Total Load D+L
Shear 42.# 3948.# 1% 2.68' Total Load D+L
TL Deflection 0.0010" 0.1641" L/999+ 2.03' Total Load D+L
LL Deflection 0.0010" 0.1094" L/999+ 2.03' Total Load L
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
9 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG8 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" 6 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" 40 13 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 10.94" 79 104 Snow
1 2
7 10 15
7 10 15
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 875# -215#
2 7' 10.938" Wall N/A N/A 1.500" 875# -215#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 259# 284# 468#
2 259# 284# 468#
Design spans
7' 1.688"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1562.'# 12233.'# 12% 3.96' Total Load D+0.75(L+S)
Negative Moment 386.'# 10637.'# 3% 3.96' Total Load D+L
Shear 633.# 4541.# 13% 6.81' Total Load D+0.75(L+S)
TL Deflection 0.0294" 0.3571" L/999+ 3.96' Total Load D+0.75(L+S)
LL Deflection 0.0137" 0.2380" L/999+ 3.96' Total Load 0.75(L+S)
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
10 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG9 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 11.7 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 1' 4.00" 1 259 Live
Replacement Uniform (PLF) Top 0' 0.00" 1' 4.00" 520 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 10' 9.75" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 10' 9.75" 27 7 Live
Replacement Uniform (PLF) Top 1' 4.00" 6' 4.00" 1 186 Live
Replacement Uniform (PLF) Top 1' 4.00" 6' 4.00" 360 0 Snow
Point (LBS) Top 6' 1.75" -0 441 Live
Point (LBS) Top 6' 1.75" 955 0 Snow
Point (LBS) Top 10' 5.13" 187 58 Snow
1 2
10 9 12
10 9 12
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 3218# --
2 10' 9.750" Wall N/A N/A 1.500" 2145# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 272# 2060# 1158#
2 269# 1377# 768#
Design spans
10' 0.500"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 7954.'# 24466.'# 32% 5.41' Total Load D+S
Shear 2432.# 9081.# 26% 0.4' Total Load D+S
TL Deflection 0.1401" 0.5021" L/860 5.41' Total Load D+S
LL Deflection 0.0898" 0.3347" L/999+ 5.41' Total Load S
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
11 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG10 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 11.7 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 13' 2.25" -23 -7 Snow
Replacement Uniform (PLF) Top 0' 0.00" 13' 4.00" 1 85 Live
Replacement Uniform (PLF) Top 0' 0.00" 13' 4.00" 263 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" 40 13 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 4.00" 0 81 Live
Replacement Uniform (PLF) Top 13' 4.00" 15' 4.00" 1 73 Live
Replacement Uniform (PLF) Top 13' 4.00" 15' 4.00" 227 0 Snow
Point (LBS) Top 0' 4.63" 35 10 Snow
Point (LBS) Top 0' 4.63" 1 84 Live
Point (LBS) Top 0' 4.63" 97 126 Snow
Point (LBS) Top 0' 4.63" 261 0 Snow
Point (LBS) Top 14' 11.38" -1012 0 Snow
Point (LBS) Top 14' 11.38" -3 -110 Live
1 2
15 4 0
15 4 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 4007# -224#
2 15' 4.000" Wall N/A N/A 1.500" 3375# -437#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 686# 2301# 1706#
2 682# 845# 1359#
Design spans
14' 6.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 437lbs at bearing 2 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 12477.'# 24466.'# 50% 7.67' Total Load D+0.75(L+S)
Negative Moment 1623.'# 21275.'# 7% 7.67' Total Load D+L
Shear 2964.# 9081.# 32% 0.4' Total Load D+0.75(L+S)
TL Deflection 0.4874" 0.7281" L/358 7.67' Total Load D+0.75(L+S)
LL Deflection 0.2762" 0.4854" L/632 7.67' Total Load 0.75(L+S)
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
12 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Control: TL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Manufacturer's installation guide MUST be consulted for multi-ply connection details and alternatives
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
13 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG11 Member Type: Girder Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 3' 6.50" 0 25 Live
Replacement Uniform (PLF) Top 0' 0.00" 3' 6.50" 79 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 8' 0.25" 0 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 0.25" 6 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 0.25" 27 7 Live
Replacement Uniform (PLF) Top 3' 6.50" 8' 0.25" 1 107 Live
Replacement Uniform (PLF) Top 3' 6.50" 8' 0.25" 334 0 Snow
Point (LBS) Top 7' 7.63" 107 33 Snow
1 2
8 0 4
8 0 4
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 822# --
2 8' 0.250" Wall N/A N/A 1.500" 1562# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 119# 581# 241#
2 121# 1142# 420#
Design spans
7' 3.000"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2211.'# 12233.'# 18% 4.37' Total Load D+S
Shear 970.# 4541.# 21% 6.91' Total Load D+S
TL Deflection 0.0410" 0.3624" L/999+ 4.01' Total Load D+S
LL Deflection 0.0296" 0.2416" L/999+ 4.01' Total Load S
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
14 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG12 Member Type: Girder Application: Roof
Comments:Top Lateral Bracing: Continuous Slope: 0.00 / 12
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 4' 5.75" 1 107 Live
Replacement Uniform (PLF) Top 0' 0.00" 4' 5.75" 334 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 8' 0.25" 0 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 0.25" 6 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 8' 0.25" 27 7 Live
Replacement Uniform (PLF) Top 4' 5.75" 8' 0.25" 0 25 Live
Replacement Uniform (PLF) Top 4' 5.75" 8' 0.25" 79 0 Snow
Point (LBS) Top 0' 4.63" 107 33 Snow
1 2
8 0 4
8 0 4
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1562# --
2 8' 0.250" Wall N/A N/A 1.500" 822# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 121# 1142# 420#
2 119# 581# 241#
Design spans
7' 3.000"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2211.'# 12233.'# 18% 3.65' Total Load D+S
Shear 970.# 4541.# 21% 0.4' Total Load D+S
TL Deflection 0.0410" 0.3624" L/999+ 4.01' Total Load D+S
LL Deflection 0.0296" 0.2416" L/999+ 4.01' Total Load S
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
15 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG16 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 0' 5.50" 47 94 Snow
Replacement Uniform (PLF) Top 0' 0.00" 13' 0.00" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 13' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 13' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 13' 0.00" 40 13 Live
Point (LBS) Top 0' 4.63" 12 1651 Live
Point (LBS) Top 0' 4.63" 4337 0 Snow
Point (LBS) Top 3' 3.75" -1 0 Snow
Point (LBS) Top 3' 3.75" 315 100 Live
Point (LBS) Top 12' 7.38" 2 331 Live
Point (LBS) Top 12' 7.38" 525 0 Snow
1 2
13 0 0
13 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 6275# --
2 13' 0.000" Wall N/A N/A 1.500" 1434# -37#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 822# 4341# 1934#
2 648# 525# 555#
Design spans
12' 2.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 3000.'# 10637.'# 28% 5.89' Total Load D+L
Negative Moment 1134.'# 10637.'# 10% 6.5' Total Load D+L
Shear 961.# 3948.# 24% 0.4' Total Load D+L
TL Deflection 0.1669" 0.6115" L/879 6.5' Total Load D+L
LL Deflection 0.1243" 0.4076" L/999+ 6.5' Total Load L
Control: LL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
16 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG17 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 20' 1.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 20' 1.50" 27 7 Live
Point (LBS) Top 7' 4.25" -23 0 Snow
Point (LBS) Top 7' 4.25" 301 82 Live
Point (LBS) Top 17' 7.75" 89 47 Live
1 2 3
15 10 4 4 3 4
20 1 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 604# --
2 15' 10.250" Wall N/A N/A 1.500" 1782# --
3 20' 1.500" Girder N/A N/A N/A 33# -589#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 453# -8# 152#
2 1325# -26# 457#
3 -485# 13# -104#
Design spans
15' 5.625" 3' 11.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 590lbs at bearing 3 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2449.'# 10637.'# 23% 7.35' Odd Spans D+L
Negative Moment 2622.'# 10637.'# 24% 15.85' Total Load D+L
Shear 831.# 3948.# 21% 15.08' Total Load D+L
TL Deflection 0.1605" 0.7734" L/999+ 7.34' Odd Spans D+L
LL Deflection 0.1215" 0.5156" L/999+ 7.34' Odd Spans L
Control: Negative Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
17 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG18 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 4.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 13' 0.00" -53 -13 Live
Replacement Uniform (PLF) Top 0' 0.00" 13' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 13' 0.00" 40 13 Live
Replacement Uniform (PLF) Top 2' 4.00" 9' 10.00" 27 7 Live
Replacement Uniform (PLF) Top 9' 10.00" 13' 0.00" 13 3 Live
Replacement Uniform (PLF) Top 12' 11.13" 13' 0.00" 47 94 Snow
Point (LBS) Top 0' 4.63" 2 331 Live
Point (LBS) Top 0' 4.63" 525 0 Snow
Point (LBS) Top 9' 8.25" 315 101 Live
Point (LBS) Top 12' 7.38" 12 1651 Live
Point (LBS) Top 12' 7.38" 4337 0 Snow
1 2
13 0 0
13 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1430# -37#
2 13' 0.000" Wall N/A N/A 1.500" 6257# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 643# 525# 554#
2 788# 4337# 1919#
Design spans
12' 2.750"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2964.'# 10637.'# 27% 7.11' Total Load D+L
Negative Moment 1134.'# 10637.'# 10% 6.5' Total Load D+L
Shear 936.# 3948.# 23% 12' Total Load D+L
TL Deflection 0.1649" 0.6115" L/890 6.5' Total Load D+L
LL Deflection 0.1226" 0.4076" L/999+ 6.5' Total Load L
Control: LL Deflection
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
18 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG19 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 7.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 20' 1.50" 27 7 Live
Replacement Uniform (PLF) Top 2' 7.50" 12' 7.50" 13 3 Live
Replacement Uniform (PLF) Top 12' 7.50" 20' 1.50" 27 7 Live
Point (LBS) Top 2' 5.75" 89 47 Live
Point (LBS) Top 12' 9.25" 301 98 Live
1 2 3
4 3 4 15 10 4
20 1 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 32# -535#
2 4' 3.250" Wall N/A N/A 1.500" 1589# --
3 20' 1.500" Wall N/A N/A 1.500" 588# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 -433# -101#
2 1157# 432#
3 435# 153#
Design spans
3' 11.750" 15' 5.625"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 535lbs at bearing 1 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2337.'# 10637.'# 21% 12.77' Even Spans D+L
Negative Moment 2397.'# 10637.'# 22% 4.27' Total Load D+L
Shear 745.# 3948.# 18% 3.48' Total Load D+L
TL Deflection 0.1509" 0.7734" L/999+ 12.78' Even Spans D+L
LL Deflection 0.1119" 0.5156" L/999+ 12.78' Even Spans L
Control: Negative Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
19 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG20 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 3' 9.50" -252 -6 Live
Replacement Uniform (PLF) Top 0' 0.00" 3' 9.50" 55 0 Snow
Replacement Uniform (PLF) Top 0' 0.00" 7' 5.50" 212 53 Live
Replacement Uniform (PLF) Top 3' 9.50" 7' 4.63" 47 12 Live
Replacement Uniform (PLF) Top 7' 4.63" 7' 5.50" 47 12 Live
Point (LBS) Top 3' 7.75" -174 -90 Live
Point (LBS) Top 3' 7.75" 13 0 Snow
1 2
7 5 8
7 5 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 952# -771#
2 7' 5.500" Wall N/A N/A 1.500" 1049# -332#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 745# 148# 206#
2 823# 55# 226#
Design spans
6' 8.250"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 772lbs at bearing 1 and ensure that the structure can resist appropriately.
Review gravity uplift reaction force of 333lbs at bearing 2 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1672.'# 10637.'# 15% 3.8' Total Load D+L
Negative Moment 1179.'# 10637.'# 11% 3.39' Total Load D+L
Shear 724.# 3948.# 18% 6.4' Total Load D+L
TL Deflection 0.0275" 0.3344" L/999+ 3.78' Total Load D+L
LL Deflection 0.0216" 0.2229" L/999+ 3.78' Total Load L
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12- 5-14
7:40am
20 of 20
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG21 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 5.9 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 0' 5.50" 47 12 Live
Replacement Uniform (PLF) Top 0' 0.00" 7' 5.50" 212 53 Live
Replacement Uniform (PLF) Top 0' 5.50" 3' 8.00" 47 12 Live
Replacement Uniform (PLF) Top 3' 8.00" 7' 5.50" -252 -44 Live
Point (LBS) Top 3' 9.75" -174 -99 Live
1 2
7 5 8
7 5 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1049# -369#
2 7' 5.500" Wall N/A N/A 1.500" 952# -872#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 823# 226#
2 745# 206#
Design spans
6' 8.250"
Product: 1-3/4x11-7/8 VERSA-LAM 2.0 3100 SP 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Review gravity uplift reaction force of 370lbs at bearing 1 and ensure that the structure can resist appropriately.
Review gravity uplift reaction force of 873lbs at bearing 2 and ensure that the structure can resist appropriately.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1672.'# 10637.'# 15% 3.66' Total Load D+L
Negative Moment 1311.'# 10637.'# 12% 4.06' Total Load D+L
Shear 724.# 3948.# 18% 0.4' Total Load D+L
TL Deflection 0.0275" 0.3344" L/999+ 3.68' Total Load D+L
LL Deflection 0.0216" 0.2229" L/999+ 3.68' Total Load L
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%