32A-201 1ST FLOOR GIRDER CALCS(3)CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
1 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG1 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 3' 2.63" 106 12 Live
Replacement Uniform (PLF) Top 3' 2.63" 3' 11.50" 106 12 Live
1 2
3 11 8
3 11 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 203# --
2 3' 11.500" Girder N/A N/A N/A 203# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 173# 30#
2 173# 30#
Design spans
3' 3.375"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 167.'# 4614.'# 3% 2.03' Total Load D+L
Shear 87.# 3038.# 2% 0.4' Total Load D+L
LL Deflection 0.0010" 0.1094" L/999+ 2.03' Total Load L
TL Deflection 0.0010" 0.1641" L/999+ 2.03' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
2 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG2 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 0' 11.50" 122 31 Live
Replacement Uniform (PLF) Top 0' 11.50" 3' 9.50" 167 42 Live
1 2
3 9 8
3 9 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 313# --
2 3' 9.500" Girder N/A N/A N/A 343# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 242# 71#
2 266# 77#
Design spans
3' 2.500"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 272.'# 4614.'# 5% 1.9' Total Load D+L
Shear 148.# 3038.# 4% 0.3' Total Load D+L
LL Deflection 0.0010" 0.1069" L/999+ 1.9' Total Load L
TL Deflection 0.0010" 0.1604" L/999+ 1.9' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
3 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG3 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 3.4 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 2' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 2' 0.00" 6' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 2' 0.00" 6' 3.50" 27 7 Live
Point (LBS) Top 0' 2.75" 0 87 Live
Point (LBS) Top 0' 3.00" 0 125 Live
1 2
2 0 0 4 3 8
6 3 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 2' 0.000" Wall N/A N/A 1.500" 620# --
2 6' 3.500" Girder N/A N/A N/A 39# -94#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 240# 380#
2 107# -67#
Design spans
2' 0.000" (left cant) 4' 0.000"
Product: Spruce-Pine-Fir #2 2 x 12 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 11.'# 2307.'# 0% 5.4' Even Spans D+L
Negative Moment 512.'# 2307.'# 22% 2' Total Load D+L
Shear 286.# 1519.# 18% 1.1' Total Load D+L
LL Deflection 0.0012" 0.1333" L/999+ 4' Even Spans L
TL Deflection -0.0033" 0.2000" L/999+ 3.6' Cants Only D+L
LL Defl., Lt. 0.0027" 0.2000" 2L/999+ 0' Cants Only L
TL Defl., Lt. 0.0130" 0.2000" 2L/999+ 0' Cants Only D+L
Control: Negative Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
4 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG4 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 3.4 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 4' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 4' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 4' 3.50" 6' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 4' 3.50" 6' 3.50" 27 7 Live
Point (LBS) Top 6' 0.50" 0 125 Live
Point (LBS) Top 6' 0.75" 0 87 Live
1 2
4 3 8 2 0 0
6 3 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 39# -94#
2 4' 3.500" Wall N/A N/A 1.500" 620# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 107# -67#
2 240# 380#
Design spans
4' 0.000" 2' 0.000" (right cant)
Product: Spruce-Pine-Fir #2 2 x 12 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 11.'# 2307.'# 0% 0.89' Odd Spans D+L
Negative Moment 512.'# 2307.'# 22% 4.29' Total Load D+L
Shear 286.# 1519.# 18% 4.3' Total Load D+L
LL Deflection 0.0012" 0.1333" L/999+ 2.29' Odd Spans L
TL Deflection -0.0033" 0.2000" L/999+ 2.69' Cants Only D+L
LL Defl., Rt. 0.0027" 0.2000" 2L/999+ 6.29' Cants Only L
TL Defl., Rt. 0.0130" 0.2000" 2L/999+ 6.29' Cants Only D+L
Control: Negative Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
5 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG5 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 3.4 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 1' 8.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 6' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 1' 8.00" 6' 3.50" 27 7 Live
Point (LBS) Top 0' 2.75" 0 87 Live
Point (LBS) Top 0' 3.00" 116 177 Snow
1 2
2 0 0 4 3 8
6 3 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 2' 0.000" Wall N/A N/A 1.500" 760# --
2 6' 3.500" Girder N/A N/A N/A 16# -148#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 240# 166# 455#
2 107# -50# -90#
Design spans
2' 0.000" (left cant) 4' 0.000"
Product: Spruce-Pine-Fir #2 2 x 12 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2.'# 2307.'# 0% 5.8' Even Spans D+L
Negative Moment 728.'# 2653.'# 27% 2' Total Load D+0.75(L+S)
Shear 411.# 1747.# 23% 1.1' Total Load D+0.75(L+S)
LL Deflection -0.0016" 0.1333" L/999+ 3.6' Cants Only 0.75(L+S)
TL Deflection -0.0048" 0.2000" L/999+ 3.6' Cants Only D+0.75(L+S)
LL Defl., Lt. 0.0061" 0.2000" 2L/999+ 0' Cants Only 0.75(L+S)
TL Defl., Lt. 0.0189" 0.2000" 2L/999+ 0' Cants Only D+0.75(L+S)
Control: Negative Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
6 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG6 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 0' 9.25" 69 17 Live
Replacement Uniform (PLF) Top 0' 0.00" 0' 9.25" 231 58 Live
Replacement Uniform (PLF) Top 0' 9.25" 1' 11.50" 69 17 Live
Replacement Uniform (PLF) Top 0' 9.25" 1' 11.50" 231 58 Live
1 2
1 11 8
1 11 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 318# --
2 1' 11.500" Girder N/A N/A N/A 318# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 250# 68#
2 250# 68#
Design spans
1' 8.000"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 133.'# 4614.'# 2% 0.98' Total Load D+L
LL Deflection 0.0010" 0.0556" L/999+ 0.98' Total Load L
TL Deflection 0.0010" 0.0833" L/999+ 0.98' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Shear cannot be calculated because member`s length is less then 2d.
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
7 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG7 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 0' 8.88" 106 12 Live
Replacement Uniform (PLF) Top 0' 8.88" 3' 11.50" 106 12 Live
1 2
3 11 8
3 11 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 203# --
2 3' 11.500" Wall N/A N/A 1.500" 203# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 173# 30#
2 173# 30#
Design spans
3' 3.375"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 167.'# 4614.'# 3% 1.93' Total Load D+L
Shear 87.# 3038.# 2% 2.75' Total Load D+L
LL Deflection 0.0010" 0.1094" L/999+ 1.93' Total Load L
TL Deflection 0.0010" 0.1641" L/999+ 1.93' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
8 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG8 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 10.00" 167 42 Live
Replacement Uniform (PLF) Top 2' 10.00" 3' 9.50" 122 31 Live
1 2
3 9 8
3 9 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 343# --
2 3' 9.500" Girder N/A N/A N/A 313# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 266# 77#
2 242# 71#
Design spans
3' 2.500"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 272.'# 4614.'# 5% 1.9' Total Load D+L
Shear 148.# 3038.# 4% 2.7' Total Load D+L
LL Deflection 0.0010" 0.1069" L/999+ 1.9' Total Load L
TL Deflection 0.0010" 0.1604" L/999+ 1.9' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
9 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG9 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 3.4 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 4' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 4' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 4' 3.50" 6' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 4' 3.50" 6' 3.50" 27 7 Live
Point (LBS) Top 6' 0.50" 0 125 Live
Point (LBS) Top 6' 0.75" 0 87 Live
1 2
4 3 8 2 0 0
6 3 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 39# -94#
2 4' 3.500" Wall N/A N/A 1.500" 620# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 107# -67#
2 240# 380#
Design spans
4' 0.000" 2' 0.000" (right cant)
Product: Spruce-Pine-Fir #2 2 x 12 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 11.'# 2307.'# 0% 0.89' Odd Spans D+L
Negative Moment 512.'# 2307.'# 22% 4.29' Total Load D+L
Shear 286.# 1519.# 18% 4.3' Total Load D+L
LL Deflection 0.0012" 0.1333" L/999+ 2.29' Odd Spans L
TL Deflection -0.0033" 0.2000" L/999+ 2.69' Cants Only D+L
LL Defl., Rt. 0.0027" 0.2000" 2L/999+ 6.29' Cants Only L
TL Defl., Rt. 0.0130" 0.2000" 2L/999+ 6.29' Cants Only D+L
Control: Negative Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
10 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG10 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 3.4 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 2' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 2' 0.00" 6' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 2' 0.00" 6' 3.50" 27 7 Live
Point (LBS) Top 0' 2.75" 0 87 Live
Point (LBS) Top 0' 3.00" 0 125 Live
1 2
2 0 0 4 3 8
6 3 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 2' 0.000" Wall N/A N/A 1.500" 620# --
2 6' 3.500" Girder N/A N/A N/A 39# -94#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 240# 380#
2 107# -67#
Design spans
2' 0.000" (left cant) 4' 0.000"
Product: Spruce-Pine-Fir #2 2 x 12 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 11.'# 2307.'# 0% 5.4' Even Spans D+L
Negative Moment 512.'# 2307.'# 22% 2' Total Load D+L
Shear 286.# 1519.# 18% 1.1' Total Load D+L
LL Deflection 0.0012" 0.1333" L/999+ 4' Even Spans L
TL Deflection -0.0033" 0.2000" L/999+ 3.6' Cants Only D+L
LL Defl., Lt. 0.0027" 0.2000" 2L/999+ 0' Cants Only L
TL Defl., Lt. 0.0130" 0.2000" 2L/999+ 0' Cants Only D+L
Control: Negative Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
11 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG11 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 3.4 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 4' 7.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 6' 3.50" 27 7 Live
Replacement Uniform (PLF) Top 4' 7.50" 6' 3.50" 27 7 Live
Point (LBS) Top 6' 0.50" 116 177 Snow
Point (LBS) Top 6' 0.75" 0 87 Live
1 2
4 3 8 2 0 0
6 3 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 16# -148#
2 4' 3.500" Wall N/A N/A 1.500" 760# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 107# -50# -90#
2 240# 166# 455#
Design spans
4' 0.000" 2' 0.000" (right cant)
Product: Spruce-Pine-Fir #2 2 x 12 1 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2.'# 2307.'# 0% 0.49' Odd Spans D+L
Negative Moment 728.'# 2653.'# 27% 4.29' Total Load D+0.75(L+S)
Shear 411.# 1747.# 23% 4.3' Total Load D+0.75(L+S)
LL Deflection -0.0016" 0.1333" L/999+ 2.69' Cants Only 0.75(L+S)
TL Deflection -0.0048" 0.2000" L/999+ 2.69' Cants Only D+0.75(L+S)
LL Defl., Rt. 0.0061" 0.2000" 2L/999+ 6.29' Cants Only 0.75(L+S)
TL Defl., Rt. 0.0189" 0.2000" 2L/999+ 6.29' Cants Only D+0.75(L+S)
Control: Negative Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
12 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG12 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 1' 2.25" 69 17 Live
Replacement Uniform (PLF) Top 0' 0.00" 1' 2.25" 231 58 Live
Replacement Uniform (PLF) Top 1' 2.25" 1' 11.50" 69 17 Live
Replacement Uniform (PLF) Top 1' 2.25" 1' 11.50" 231 58 Live
1 2
1 11 8
1 11 8
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Girder N/A N/A N/A 318# --
2 1' 11.500" Girder N/A N/A N/A 318# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Dead
1 250# 68#
2 250# 68#
Design spans
1' 8.000"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 133.'# 4614.'# 2% 0.98' Total Load D+L
LL Deflection 0.0010" 0.0556" L/999+ 0.98' Total Load L
TL Deflection 0.0010" 0.0833" L/999+ 0.98' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
Shear cannot be calculated because member`s length is less then 2d.
This member has been designed in accordance with NDS 2005
Minimum bearing length requirements at hangared connections depend on the connection style and are not included in this design.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
13 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG13 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 6' 0.25" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 20' 1.75" 27 7 Live
Replacement Uniform (PLF) Top 6' 0.25" 9' 7.25" 6 1 Live
Replacement Uniform (PLF) Top 9' 7.25" 14' 0.25" 27 7 Live
Replacement Uniform (PLF) Top 14' 0.25" 20' 1.75" 27 7 Live
Point (LBS) Top 4' 5.00" -101 0 Snow
Point (LBS) Top 4' 5.00" -31 0 Snow
Point (LBS) Top 4' 5.00" 394 365 Live
Point (LBS) Top 4' 5.00" 814 190 Live
Point (LBS) Top 5' 10.50" 194 47 Live
Point (LBS) Top 14' 2.00" 242 83 Live
Point (LBS) Top 19' 9.13" -10 0 Snow
Point (LBS) Top 19' 9.13" 0 147 Live
Point (LBS) Top 19' 9.13" 115 117 Live
Point (LBS) Top 19' 9.13" 113 122 Live
Point (LBS) Top 19' 9.13" 439 0 Snow
Point (LBS) Top 19' 9.13" 403 324 Live
1 2 3
6 7 4 13 6 8
20 1 12
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 677# -34#
2 6' 7.250" Wall N/A N/A 2.101" 2679# -3#
3 20' 1.750" Wall N/A N/A 1.500" 1939# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 520# -37# 157#
2 1906# -97# 772#
3 1029# 432# 838#
Design spans
6' 2.875" 13' 1.875"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2139.'# 4614.'# 46% 4.42' Odd Spans D+L
Negative Moment 2346.'# 4614.'# 50% 6.6' Total Load D+L
Shear 1841.# 3038.# 60% 5.89' Total Load D+L
LL Deflection 0.0667" 0.4385" L/999+ 13.84' Even Spans L
TL Deflection 0.0822" 0.6578" L/999+ 14.01' Even Spans D+L
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
14 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
15 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG14 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 3.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 12' 11.00" 27 7 Live
Replacement Uniform (PLF) Top 2' 3.00" 8' 4.50" 27 7 Live
Replacement Uniform (PLF) Top 8' 4.50" 12' 11.00" 27 7 Live
Point (LBS) Top 0' 4.63" -1 0 Snow
Point (LBS) Top 0' 4.63" 0 162 Live
Point (LBS) Top 0' 4.63" 82 116 Live
Point (LBS) Top 0' 4.63" 119 137 Live
Point (LBS) Top 0' 4.63" 463 0 Snow
Point (LBS) Top 0' 4.63" 247 281 Live
Point (LBS) Top 8' 2.75" 266 89 Live
Point (LBS) Top 12' 6.38" 0 93 Live
Point (LBS) Top 12' 6.38" 198 60 Live
Point (LBS) Top 12' 6.38" 437 146 Live
Point (LBS) Top 12' 6.38" 238 1832 Live
Point (LBS) Top 12' 6.38" 3840 0 Snow
1 2
12 11 0
12 11 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1845# --
2 12' 11.000" Wall N/A N/A 1.500" 6216# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 865# 462# 849#
2 1368# 3840# 2310#
Design spans
12' 1.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2224.'# 4614.'# 48% 8.22' Total Load D+L
Shear 606.# 3038.# 19% 11.92' Total Load D+L
LL Deflection 0.0828" 0.4049" L/999+ 6.46' Total Load L
TL Deflection 0.1128" 0.6073" L/999+ 6.46' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
16 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG15 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 1' 2.75" 80 20 Live
Replacement Uniform (PLF) Top 0' 0.00" 2' 3.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 12' 11.00" 6 1 Live
Replacement Uniform (PLF) Top 1' 2.75" 2' 3.50" 80 20 Live
Replacement Uniform (PLF) Top 2' 3.00" 8' 4.50" 27 7 Live
Replacement Uniform (PLF) Top 2' 3.50" 2' 5.44" 80 20 Live
Replacement Uniform (PLF) Top 2' 5.44" 3' 5.44" 80 10 Live
Replacement Uniform (PLF) Top 3' 5.44" 4' 3.50" 80 -19 Live
Replacement Uniform (PLF) Top 4' 3.50" 8' 3.50" 80 -21 Live
Replacement Uniform (PLF) Top 8' 3.50" 9' 3.50" 80 -16 Live
Replacement Uniform (PLF) Top 8' 4.50" 12' 11.00" 27 7 Live
Replacement Uniform (PLF) Top 9' 3.50" 10' 1.38" 80 12 Live
Replacement Uniform (PLF) Top 10' 1.38" 10' 1.56" 80 20 Live
Replacement Uniform (PLF) Top 10' 1.56" 10' 3.50" 80 20 Live
Replacement Uniform (PLF) Top 10' 3.50" 11' 4.75" 80 20 Live
Replacement Uniform (PLF) Top 11' 4.75" 12' 11.00" 80 20 Live
Point (LBS) Top 0' 4.63" 44 0 Snow
Point (LBS) Top 0' 4.63" 0 93 Live
Point (LBS) Top 0' 4.63" 130 0 Snow
Point (LBS) Top 0' 4.63" 100 82 Live
Point (LBS) Top 0' 4.63" 97 112 Live
Point (LBS) Top 4' 4.38" 0 21 Live
Point (LBS) Top 8' 2.63" 0 21 Live
Point (LBS) Top 12' 6.38" 0 93 Live
Point (LBS) Top 12' 6.38" 572 243 Live
1 2
12 11 0
12 11 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1273# --
2 12' 11.000" Wall N/A N/A 1.500" 1702# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 881# 174# 393#
2 1255# 0# 447#
Design spans
12' 1.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
17 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2244.'# 4614.'# 48% 6.46' Total Load D+L
Shear 656.# 3038.# 21% 11.92' Total Load D+L
LL Deflection 0.1105" 0.4049" L/999+ 6.46' Total Load L
TL Deflection 0.1211" 0.6073" L/999+ 6.46' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
18 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG16 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 3.4 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 6' 0.75" 80 -23 Live
Replacement Uniform (PLF) Top 0' 0.00" 10' 9.75" 6 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 10' 9.75" 27 7 Live
Replacement Uniform (PLF) Top 6' 0.75" 7' 0.75" -31 0 Snow
Replacement Uniform (PLF) Top 6' 0.75" 7' 0.75" 80 -32 Live
Replacement Uniform (PLF) Top 7' 0.75" 7' 10.63" -7 0 Snow
Replacement Uniform (PLF) Top 7' 0.75" 7' 10.63" 80 8 Live
Replacement Uniform (PLF) Top 7' 10.63" 7' 10.81" 80 20 Live
Replacement Uniform (PLF) Top 7' 10.81" 8' 0.75" 80 20 Live
Replacement Uniform (PLF) Top 8' 0.75" 10' 9.75" 80 20 Live
Point (LBS) Top 0' 4.63" 0 130 Live
Point (LBS) Top 0' 4.63" 142 0 Snow
Point (LBS) Top 0' 4.63" 485 170 Live
Point (LBS) Top 5' 11.88" 0 21 Live
Point (LBS) Top 10' 5.38" 0 93 Live
Point (LBS) Top 10' 5.38" 243 61 Live
1 2
10 9 12
10 9 12
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1322# --
2 10' 9.750" Wall N/A N/A 1.500" 1025# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 1051# 128# 271#
2 809# -22# 216#
Design spans
10' 0.750"
Product: Spruce-Pine-Fir #2 2 x 12 1 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1420.'# 2307.'# 61% 5.92' Total Load D+L
Negative Moment 81.'# 2653.'# 3% 4.41' Total Load D+S
Shear 494.# 1519.# 32% 9.94' Total Load D+L
LL Deflection 0.1042" 0.3354" L/999+ 5.42' Total Load L
TL Deflection 0.1044" 0.5031" L/999+ 5.42' Total Load D+L
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
19 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
20 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG17 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 15' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 0.00" 27 7 Live
Point (LBS) Top 3' 6.38" 250 74 Live
Point (LBS) Top 14' 7.38" 88 0 Snow
Point (LBS) Top 14' 7.38" 68 55 Live
Point (LBS) Top 14' 7.38" 0 162 Live
Point (LBS) Top 14' 7.38" 384 586 Live
Point (LBS) Top 14' 7.38" 1151 0 Snow
1 2
15 0 0
15 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 775# --
2 15' 0.000" Wall N/A N/A 1.500" 2557# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 574# 0# 201#
2 887# 1239# 963#
Design spans
14' 2.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2402.'# 4614.'# 52% 6.79' Total Load D+L
Shear 706.# 3038.# 23% 0.4' Total Load D+L
LL Deflection 0.1310" 0.4743" L/999+ 7.5' Total Load L
TL Deflection 0.1778" 0.7115" L/960 7.5' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
21 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG18 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 15' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 0.00" 27 7 Live
Point (LBS) Top 0' 4.63" 0 162 Live
Point (LBS) Top 0' 4.63" 584 0 Snow
Point (LBS) Top 0' 4.63" 451 362 Live
Point (LBS) Top 11' 5.63" 250 74 Live
1 2
15 0 0
15 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1785# --
2 15' 0.000" Wall N/A N/A 1.500" 775# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 886# 584# 683#
2 574# 0# 201#
Design spans
14' 2.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2402.'# 4614.'# 52% 8.21' Total Load D+L
Shear 706.# 3038.# 23% 13.9' Total Load D+L
LL Deflection 0.1310" 0.4743" L/999+ 7.5' Total Load L
TL Deflection 0.1778" 0.7115" L/960 7.5' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
22 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG19 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 6' 1.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 20' 1.75" 27 7 Live
Replacement Uniform (PLF) Top 6' 1.50" 10' 6.50" 27 7 Live
Replacement Uniform (PLF) Top 10' 6.50" 14' 1.50" 6 1 Live
Replacement Uniform (PLF) Top 14' 1.50" 20' 1.75" 27 7 Live
Point (LBS) Top 0' 4.63" -10 0 Snow
Point (LBS) Top 0' 4.63" 0 147 Live
Point (LBS) Top 0' 4.63" 115 117 Live
Point (LBS) Top 0' 4.63" 113 122 Live
Point (LBS) Top 0' 4.63" 439 0 Snow
Point (LBS) Top 0' 4.63" 403 324 Live
Point (LBS) Top 5' 11.75" 242 83 Live
Point (LBS) Top 14' 3.25" 194 47 Live
Point (LBS) Top 15' 8.75" -101 0 Snow
Point (LBS) Top 15' 8.75" -31 0 Snow
Point (LBS) Top 15' 8.75" 394 365 Live
Point (LBS) Top 15' 8.75" 814 190 Live
1 2 3
13 6 8 6 7 4
20 1 12
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1939# --
2 13' 6.500" Wall N/A N/A 2.101" 2679# -3#
3 20' 1.750" Wall N/A N/A 1.500" 677# -34#
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 1029# 432# 838#
2 1906# -97# 772#
3 520# -37# 157#
Design spans
13' 1.875" 6' 2.875"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2139.'# 4614.'# 46% 15.73' Even Spans D+L
Negative Moment 2346.'# 4614.'# 50% 13.54' Total Load D+L
Shear 1841.# 3038.# 60% 13.55' Total Load D+L
LL Deflection 0.0667" 0.4385" L/999+ 6.31' Odd Spans L
TL Deflection 0.0822" 0.6578" L/999+ 6.14' Odd Spans D+L
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
23 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Control: Shear
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
24 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG20 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 4' 6.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 12' 11.00" 27 7 Live
Replacement Uniform (PLF) Top 4' 6.50" 10' 8.00" 27 7 Live
Replacement Uniform (PLF) Top 10' 8.00" 12' 11.00" 27 7 Live
Point (LBS) Top 0' 4.63" 0 93 Live
Point (LBS) Top 0' 4.63" 198 60 Live
Point (LBS) Top 0' 4.63" 437 146 Live
Point (LBS) Top 0' 4.63" 238 1832 Live
Point (LBS) Top 0' 4.63" 3840 0 Snow
Point (LBS) Top 4' 8.25" 266 89 Live
Point (LBS) Top 12' 6.38" -1 0 Snow
Point (LBS) Top 12' 6.38" 0 162 Live
Point (LBS) Top 12' 6.38" 82 116 Live
Point (LBS) Top 12' 6.38" 119 137 Live
Point (LBS) Top 12' 6.38" 463 0 Snow
Point (LBS) Top 12' 6.38" 247 281 Live
1 2
12 11 0
12 11 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 6216# --
2 12' 11.000" Wall N/A N/A 1.500" 1845# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 1368# 3840# 2310#
2 865# 462# 849#
Design spans
12' 1.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2224.'# 4614.'# 48% 4.7' Total Load D+L
Shear 606.# 3038.# 19% 0.4' Total Load D+L
LL Deflection 0.0828" 0.4049" L/999+ 6.46' Total Load L
TL Deflection 0.1128" 0.6073" L/999+ 6.46' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
25 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG21 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 1' 6.25" 80 20 Live
Replacement Uniform (PLF) Top 0' 0.00" 4' 6.50" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 12' 11.00" 6 1 Live
Replacement Uniform (PLF) Top 1' 6.25" 2' 7.50" 80 20 Live
Replacement Uniform (PLF) Top 2' 7.50" 2' 9.44" 80 20 Live
Replacement Uniform (PLF) Top 2' 9.44" 3' 7.50" 80 12 Live
Replacement Uniform (PLF) Top 3' 7.50" 4' 7.50" 80 -16 Live
Replacement Uniform (PLF) Top 4' 6.50" 10' 8.00" 27 7 Live
Replacement Uniform (PLF) Top 4' 7.50" 8' 7.50" 80 -21 Live
Replacement Uniform (PLF) Top 8' 7.50" 9' 5.56" 80 -19 Live
Replacement Uniform (PLF) Top 9' 5.56" 10' 5.56" 80 10 Live
Replacement Uniform (PLF) Top 10' 5.56" 10' 7.50" 80 20 Live
Replacement Uniform (PLF) Top 10' 7.50" 11' 8.25" 80 20 Live
Replacement Uniform (PLF) Top 10' 8.00" 12' 11.00" 27 7 Live
Replacement Uniform (PLF) Top 11' 8.25" 12' 11.00" 80 20 Live
Point (LBS) Top 0' 4.63" 0 93 Live
Point (LBS) Top 0' 4.63" 572 243 Live
Point (LBS) Top 4' 8.38" 0 21 Live
Point (LBS) Top 8' 6.63" 0 21 Live
Point (LBS) Top 12' 6.38" 44 0 Snow
Point (LBS) Top 12' 6.38" 0 93 Live
Point (LBS) Top 12' 6.38" 130 0 Snow
Point (LBS) Top 12' 6.38" 100 82 Live
Point (LBS) Top 12' 6.38" 97 112 Live
1 2
12 11 0
12 11 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1702# --
2 12' 11.000" Wall N/A N/A 1.500" 1273# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 1255# 0# 447#
2 881# 174# 393#
Design spans
12' 1.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
26 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2244.'# 4614.'# 48% 6.46' Total Load D+L
Shear 656.# 3038.# 21% 0.4' Total Load D+L
LL Deflection 0.1105" 0.4049" L/999+ 6.46' Total Load L
TL Deflection 0.1211" 0.6073" L/999+ 6.46' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
27 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG22 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 2' 9.00" 80 20 Live
Replacement Uniform (PLF) Top 0' 0.00" 10' 9.75" 6 1 Live
Replacement Uniform (PLF) Top 0' 0.00" 10' 9.75" 27 7 Live
Replacement Uniform (PLF) Top 2' 9.00" 2' 10.94" 80 20 Live
Replacement Uniform (PLF) Top 2' 10.94" 3' 9.00" -7 0 Snow
Replacement Uniform (PLF) Top 2' 10.94" 3' 9.00" 80 9 Live
Replacement Uniform (PLF) Top 3' 9.00" 4' 9.00" -31 0 Snow
Replacement Uniform (PLF) Top 3' 9.00" 4' 9.00" 80 -32 Live
Replacement Uniform (PLF) Top 4' 9.00" 10' 9.75" 80 -23 Live
Point (LBS) Top 0' 4.38" 0 93 Live
Point (LBS) Top 0' 4.38" 243 61 Live
Point (LBS) Top 4' 9.88" 0 21 Live
Point (LBS) Top 10' 5.13" 0 130 Live
Point (LBS) Top 10' 5.13" 142 0 Snow
Point (LBS) Top 10' 5.13" 485 170 Live
1 2
10 9 12
10 9 12
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 1042# --
2 10' 9.750" Wall N/A N/A 1.500" 1339# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 809# -22# 234#
2 1051# 128# 335#
Design spans
10' 0.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 1463.'# 4614.'# 31% 4.89' Total Load D+L
Negative Moment 42.'# 5306.'# 0% 6.91' Total Load D+S
Shear 508.# 3038.# 16% 0.37' Total Load D+L
LL Deflection 0.0521" 0.3354" L/999+ 5.4' Total Load L
TL Deflection 0.0538" 0.5031" L/999+ 5.4' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
28 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG23 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 15' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 0.00" 27 7 Live
Point (LBS) Top 0' 4.63" 88 0 Snow
Point (LBS) Top 0' 4.63" 68 55 Live
Point (LBS) Top 0' 4.63" 0 162 Live
Point (LBS) Top 0' 4.63" 384 587 Live
Point (LBS) Top 0' 4.63" 1153 0 Snow
Point (LBS) Top 11' 5.63" 250 74 Live
1 2
15 0 0
15 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 2560# --
2 15' 0.000" Wall N/A N/A 1.500" 775# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 887# 1241# 963#
2 574# 0# 201#
Design spans
14' 2.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2402.'# 4614.'# 52% 8.21' Total Load D+L
Shear 706.# 3038.# 23% 13.9' Total Load D+L
LL Deflection 0.1310" 0.4743" L/999+ 7.5' Total Load L
TL Deflection 0.1778" 0.7115" L/960 7.5' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table
CS Structure™ 2.06.13[Build 1]
kmBeamEngine 4.6.1.0
Materials Database 1492
DennoRich51PhillipsPlace - Lev 12-11-14
11:07am
29 of 32
All product names are trademarks of their respective owners
Copyright (C) 2013 by Simpson Strong-Tie Company Inc. ALL RIGHTS RESERVED.**Passing is defined as when the member, floor joist, beam or girder, shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet. The
design must be reviewed by a qualified designer or design professional as required for approval. This design assumes product installation according to the manufacturer`s specifications.
Doug Hodgins
rk Miles Inc.
21 West St.
West Hatfield Ma.
Member Data
Description: CalcG24 Member Type: Girder Application: Floor
Comments:Top Lateral Bracing: Continuous
Bottom Lateral Bracing: Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 0 PLF Deflection Criteria: L/360 live, L/240 total
Dead Load: 0 PLF Deck Connection: Nailed Member Weight: 6.8 PLF
Filename: Q:\DennoRich
Other Loads
Type
(Description) Side Begin End
Trib.
Width
Other
Start End
Dead
Start End Category
Replacement Uniform (PLF) Top 0' 0.00" 15' 0.00" 27 7 Live
Replacement Uniform (PLF) Top 0' 0.00" 15' 0.00" 27 7 Live
Point (LBS) Top 3' 6.38" 250 74 Live
Point (LBS) Top 14' 7.38" 0 162 Live
Point (LBS) Top 14' 7.38" 584 0 Snow
Point (LBS) Top 14' 7.38" 451 362 Live
1 2
15 0 0
15 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall N/A N/A 1.500" 775# --
2 15' 0.000" Wall N/A N/A 1.500" 1785# --
Maximum Load Case Reactions
Used for applying point loads (or line loads) to carrying members
Live Snow Dead
1 574# 0# 201#
2 886# 584# 683#
Design spans
14' 2.750"
Product: Spruce-Pine-Fir #2 2 x 12 2 ply PASSES DESIGN CHECKS
NOTE: Pass-thru framing is required at point loads over bearings.
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 2402.'# 4614.'# 52% 6.79' Total Load D+L
Shear 706.# 3038.# 23% 0.4' Total Load D+L
LL Deflection 0.1310" 0.4743" L/999+ 7.5' Total Load L
TL Deflection 0.1778" 0.7115" L/960 7.5' Total Load D+L
Control: Positive Moment
DOLs: Live=100% Snow=115% Roof=125% Wind=160%
This member has been designed in accordance with NDS 2005
Point loads over bearings are NOT included in the Design calculations, but ARE included in the Reaction table