46-027 Mass Amendments 8th 1-2 2011-12-12780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
780 CMR 51.00:MASSACHUSETTS RESIDENTIAL CODE
5101.1 Scope. The provisions of 780 CMR 51.00 shall be known as the Massachusetts Residential Code and
are comprised of the International Residential Code 2009 (IRC) with Massachusetts amendments. The
Massachusetts amendments to the IRC are:
R101.1 Replace as follows:
R101.1 Title. The Board of Building Regulations and Standards (BBRS) hereby adopts and
incorporates by reference herein the International Residential Code for One- and Two-family
Dwellings 2009 (IRC). The IRC together with modifications as set forth herein shall collectively
comprise the Eighth Edition Massachusetts Residential Code for One- and Two-family
Dwellings hereinafter referred to as “this code.”
R101.1.1 Add subsection:
R101.1.1 Appendices and Appended Regulations. In adopting the IRC, BBRS does not adopt
Appendices A through F or N through Q, but does adopt IRC Appendices G through M as
modified herein. BBRS also incorporates into this code the unique Massachusetts regulations
110.R1 trough 110.R7 of the Eighth Edition of the MA State Building Code (780 CMR).
R101.2 Add a first sentence as follows:
This code shall be the building code for all towns, cities, state agencies or authorities in
accordance with M.G.L. c. 143, § 94.
R102.2 Replace as follows:
R102.2 Other Laws. Massachusetts General Laws (M.G.L.) and the Code of Massachusetts
Regulations (CMR) are often referenced in this code. It is the code user’s responsibility to
determine all applicable laws and regulations relevant to sections in this code.
R102.2.1 Add subsection:
R102.2.1 DDS Facilities. Additional building features required by the Massachusetts
Department of Developmental Services (DDS) do not change the classification of residences
operated or licensed by DDS as dwellings subject to this code.
R102.2.2 Add subsection:
R102.2.2 Municipal Bylaws or Ordinances. When provisions of this code conflict with
municipal bylaws and ordinances, this code shall govern unless the bylaws or ordinances were
promulgated in accordance with M.G.L. c. 143, § 98.
R102.4 After the word “codes” in the first sentence, add the following: “, regulations,”
R102.4.1 Add the following subsections:
R102.4.1 Specialized Codes. Referenced codes include the specialized codes of M.G.L. c. 143,
§ 96 and other codes and regulations listed in R102.4.2 through R102.4.12. The specialized
codes are hereby incorporated into this code. Other codes and regulations shall be considered
part of this code to the prescribed extent of each such reference.
Note 1. Work regulated by the specialized codes shall be designed, installed and inspected
by individuals authorized to do so in accordance with the specialized codes. However, the
impact of work regulated by the specialized codes and other codes and regulations on work
governed by this code shall be subject to inspection by the building official.
Note 2. Work regulated by the Architectural Access Board regulations (521 CMR) shall be
enforced by the building official. See M.G.L. c. 22, § 13A.
Note 3. Work regulated by the Board of Sheet Metal Regulations shall be enforced by the
building official. See M.G.L. c. 13, § 102.
2/4/11 780 CMR - Eighth Edition - 201
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R102.4.2 Gas and Fossil Fuel Burning Appliances. Reference to the International Fuel Gas
Code shall be considered reference to the Massachusetts Fuel Gas and Plumbing Code
(248 CMR). Gas fired appliances are governed by the Massachusetts Fuel Gas and Plumbing
Code. Oil fired appliances are governed by the Board of Fire Prevention Regulations (527
CMR).
R102.4.3 Mechanical. The provisions of the International Mechanical Code shall apply to the
installation, alterations, repairs and replacement of mechanical systems, including equipment,
appliances, fixtures, fittings and/or appurtenances, including ventilating, heating, cooling, air-
conditioning and refrigeration systems, incinerators and other energy-related systems.
R102.4.4 Plumbing. Reference to the International Plumbing Code shall be considered
reference to the Massachusetts Fuel Gas and Plumbing Code (248 CMR). For sewerage disposal
or water connections also see 310 CMR 15.00: The State Environmental Code, Title 5: Standard
Requirements for the Siting, Construction, Inspection, Upgrade and Expansion of On-site
Sewage Treatment and Disposal Systems and for the Transport and Disposal of Septage and
314 CMR 3.00: Surface Water Discharge Permit Program, 5.00: Ground Water Discharge
Permit Program and 20.00: Reclaimed Water Permit Program and Standards.
R102.4.5 Property Maintenance. Reference to the International Property Maintenance Code
shall be considered reference to this code, the specialized codes of M.G.L. c. 143, § 96, and
105 CMR 410.000: Minimum Standards of Fitness for Human Habitation (State Sanitary Code,
Chapter II).
R102.4.6 Fire Prevention. Reference to the International Fire Code (IFC) or International
Mechanical Code (IMC) for fire prevention issues shall be considered reference to the Board of
Fire Prevention Regulations (527 CMR). If 527 CMR does not address an issue covered by the
IFC or IMC, then that said reference code shall apply. If a conflict regarding fire prevention
requirements exists between 527 CMR and 780 CMR the more stringent standard shall apply.
Note: Building code requirements in the IFC and IMC are made a part of 780 CMR and
are enforceable by the building official.
R102.4.7 Energy. The provisions of Chapter 11 and/or the International Energy Conservation
Code (IECC) shall apply to all matters governing the design and construction of buildings for
energy efficiency. See Chapter 11 for guidance.
R101.4.8 Architectural Access. See the Architectural Access Board regulations at 521 CMR.
R102.4.9 Environmental Protection. See the Department of Environmental Protection
regulations at 310 CMR and the Division of Water Pollution Control regulations at 314 CMR.
R101.4.10 Elevators. See the Massachusetts Board of Elevator Regulations at 524 CMR.
R102.4.11 Electrical. Reference to the International Electrical Code shall be considered
reference to 527 CMR 12.00: Massachusetts Electrical Code (Amendments).
R102.4.12 Sheet Metal. See the Board of Examiners of Sheet Metal Workers regulations at
271 CMR.
R102.5 Delete subsection.
R102.7 Delete the following phrase:
“the International Property Maintenance Code or the International Fire Code,”
R102.7.2 Add subsection:
R102.7.2 Laws in Effect. Unless specifically provided otherwise in this code, and narrow to
the provisions of this code, any existing building or structure shall meet and shall be presumed
to meet the provisions of the applicable laws, codes, rules or regulations, bylaws or ordinances
in effect at the time such building or structure was constructed or altered and shall be allowed
to continue to be occupied pursuant to its use and occupancy, provided that the building or
structure shall be maintained by the owner in accordance with this code.
2/4/11 780 CMR - Eighth Edition - 202
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R102.7.3 Add subsection:
R102.7.3. Laws Not in Existence. In cases where applicable codes, rules or regulations, bylaws
or ordinances were not in existence at the time of such construction or alteration, the building
or structure shall be maintained by the owner in accordance with this code.
R102.7.4 Add subsection:
R102.7.4. Less Stringent. In cases where the provisions of this code are less stringent than the
applicable codes, rules or regulations, bylaws or ordinances in effect at the time of such
construction or substantial alteration, the applicable provisions of this code shall apply, provided
that such application of these provisions can be reasonably demonstrated to not result in danger
to the public, as determined by the building official.
R103 Replace entire section R103 as follows:
R103.1 Municipal and State Enforcement. This code shall be enforced, and enforcement
officials shall be appointed, in accordance with M.G.L. c. 143, §§ 3 and 3A and M.G.L. c. 22.
Reference to The Department of Building Safety shall be considered reference to the building
official.
R104.1 Replace as follows:
R104.1 General. The building official is hereby authorized and directed to enforce the
provisions of this code in accordance with M.G.L. c. 143.
R104.4.1 Add subsection:
R104.4.1 Coordination of Inspections. Whenever in the enforcement of this code, or another
code or ordinance, the responsibility of more than one enforcement official of the jurisdiction
is involved, it shall be the duty of the enforcement officials involved to coordinate their
inspections and administrative orders as fully as practicable so that the owners and occupants of
the building or structure shall not be subjected to visits by numerous inspectors or multiple or
conflicting orders. Whenever an enforcement official observes an apparent or actual violation
not within the official’s authority, the official shall report the findings to the official having
jurisdiction.
R104.8 Replace as follows:
R104.8 Liability. All claims of liability relative to building officials shall be governed by
M.G.L. c. 258.
R104.10 Replace the last sentence with the following two sentences:
The details of action granting modifications shall be recorded and entered in the files of the
building official and a copy forwarded to the BBRS within seven days. A building official may
seek assistance from the district’s State building inspector for modifications.
R104.10.1 Replace as follows:
R104.10.1 Areas Prone to Flooding. The building official shall not grant modifications to any
provision related to areas prone to flooding as established by this code without the granting of
a variance to such provisions by the building code appeals board. Also, no variance to
requirements of this code can be solely utilized to argue for lawful construction/reconstruction
where such construction/reconstruction would conflict with requirements of M.G.L. c. 131, § 40:
Removal, Fill, Dredging or Altering of Land Bordering Waters (the Wetlands Protection Act),
and/or 310 CMR and 314 CMR, as applicable.
2/4/11 780 CMR - Eighth Edition - 203
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R104.10.2 Add subsection:
R104.10.2 Matters Not Provided For. In recognition of the inherent difficulty of drafting a
functional code that contemplates every situation that may arise in the area of building safety,
this section provides the building official, the building code appeals board, or the BBRS itself,
with reasonable discretion to ensure that all life safety issues that may arise in the enforcement
of this code may be appropriately addressed. Matters not specifically provided for in this code
regarding structural, egress, fire, energy, sanitary or other requirements essential to occupant
safety shall be determined by the building official or, in the case of an appeal, the building code
appeals board. If this provision is used, the building official shall notify the BBRS in writing
within seven days of such determination. For highly specialized buildings and structures that
conform to unique code requirements or nationally recognized standards not required in this
code, registered design professionals shall provide sufficient information to the building official
to support their approval.
R105.1 Replace as follows:
R105.1 Required. It shall be unlawful to construct, reconstruct, alter, repair, remove or
demolish a building or structure; or to change the use or occupancy of a building or structure;
or to install or alter any equipment for which provision is made or the installation of which is
regulated by this code without first filing a written application with the building official and
obtaining the required permit.
R105.2 Replace as follows:
R105.2 Work Exempt from Permit. Except for activities which may require a permit pursuant
to other laws, by-laws, rules and the specialized codes, a building permit is not required for the
following activities:
Building:
1. One-story detached accessory structures used as tool and storage sheds, playhouses
and similar uses, but not garages, provided the floor area does not exceed 200 square feet
(18.58 m )2
2. Fences not over six feet (1829 mm) high.
3. Retaining walls that are not over four feet (1219 mm) in height measured from the
bottom of the footing to the top of the wall, unless supporting a surcharge, or that retain
over four feet of unbalanced fill.
4. Sidewalks and driveways.
5. Painting, papering, tiling, carpeting, cabinets, counter tops and similar finish work.
6. Prefabricated swimming pools that are less than 24 inches (610 mm) deep.
7. Swings and other playground equipment.
8. Window awnings supported by an exterior wall which do not project more than 54
inches (1372 mm) from the exterior wall and do not require additional support.
9. Decks not exceeding 200 square feet (18.58 m ) in area, that are not more than 302
inches (762 mm) above grade at any point, are not attached to a dwelling and do not
serve the exit door required by subsection R311.4.
R105.2.1 Add the following note:
Note: Pursuant to the terms of the specialized codes of M.G.L. c. 143, § 96, this exemption
might not apply to emergency repairs conducted under those specialized codes.
R105.2.2 Replace as follows:
R105.2.2 Ordinary Repairs. A building permit is not required for ordinary repairs.
R105.2.3 Delete subsection.
2/4/11 780 CMR - Eighth Edition - 204
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R105.3 Replace items 3. and 4. as follows:
3. Indicate the use and occupancy for which the proposed work is intended. If the work
involves a care facility or residence licensed by a State agency, indicate the agency name and
appropriate licensing regulation on the permit.
4. Be accompanied by construction documents and other information as required in Subsection
R106.1. Construction documents shall list any building features required by a Massachusetts
agency for licensed care facilities that are beyond the requirements of this code. Any additional
building features required by the Massachusetts Department of Developmental Services shall not
result in a change in the classification of a DDS operated or licensed residences for five or fewer
occupants and their compliance with this code.
R105.3.1.1 Replace as follows:
R105.3.1.1 Determination of Substantially Improved or Substantially Damaged Existing
Buildings in Flood Hazard Areas and Coastal Dunes. For applications for reconstruction,
rehabilitation, addition or other improvement of existing buildings or structures located in an
area prone to flooding as established by Table R301.2(1), the building official shall examine or
cause to be examined the construction documents and shall prepare a finding with regard to the
value of the proposed work. For buildings that have sustained damage of any origin, the value
of the proposed work shall include the cost to repair the building or structure to its predamaged
condition.
In determining the value of the proposed work, the building official shall consider the
following:
A substantial improvement means any repair, reconstruction, rehabilitation, addition or
improvement of a building or structure, the cost of which equals or exceeds 50% of the market
value of the building or structure before the improvement or repair is started. If the building or
structure has sustained substantial damage, all repairs are considered substantial improvement
regardless of the actual repair work performed. The term does not include:
1. Improvements of a building or structure required to correct existing health, sanitary or
safety code violations identified by the building official and which are the minimum
necessary to assure safe living conditions; or
2. Any alteration of an historic building or structure, provided that the alteration will not
preclude the continued designation as an historic building or structure. For the purpose of
this exclusion, an historic building is:
2.1. Listed or preliminarily determined to be eligible for listing in the National Register
of Historic Places; or
2.2. Determined by the Secretary of the U.S. Department of Interior as contributing to
the historical significance of a registered historic district or a district preliminarily
determined to qualify as an historic district; or
2.3. Designated as historic under a state or local historic preservation program that is
approved by the Department of Interior.
If the building official finds that the value of proposed work equals or exceeds 50% of the
market value of the building or structure before the damage has occurred or the improvement
is started, the building official shall determine it to be substantial damage or substantial
improvement.
Applications determined by the building official to constitute substantial improvement
or substantial damage shall require all existing portions of the entire building or structure to
meet the requirements of Section R322.
R105.3.1.1.1 Add subsection:
R105.3.1.1.1 Determination of Substantial Repair of a Foundation. When work to repair or
replace a foundation results in the repair or replacement of a portion of the foundation with a
perimeter along the base of the foundation that equals or exceeds 50% of the perimeter of the
base of the foundation measured in linear feet the building official shall determine it to be
substantial repair of a foundation. Applications determined by the building official to constitute
substantial repair of a foundation shall require all existing portions of the entire building or
structure to meet the requirements of Section R322.
2/4/11 780 CMR - Eighth Edition - 205
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R105.3.1.2 Add subsection:
R105.3.1.2 Other Requirements. The following requirements must be satisfied before a
building permit is issued:
Zoning: in accordance with M.G.L. c. 40A or St. 1956, c. 665.
Railroad Right-of-way: in accordance with M.G.L. c. 40, § 54A.
Water Supply: in accordance with M.G.L. c. 40, § 54; also refer to 310 CMR 22.00:
Drinking Water and/or 310 CMR 36.00: Massachusetts Water Resources Management
Program, when applicable.
Wastewater: in accordance with 310 CMR 15.00: The State Environmental Code, Title 5:
Standard Requirements for the Siting, Construction, Inspection, Upgrade and Expansion of
On-site Sewage Treatment and Disposal Systems and for the Transport and Disposal of
Septage and 314 CMR 3.00: Surface Water Discharge Permit Program, 5.00: Ground
Water Discharge Permit Program 7.00: Sewer System Extension and Connection Permit
Program, and 20.00: Reclaimed Water Permit Program and Standards
Debris Removal: in accordance with M.G.L. c. 40, § 54 and M.G.L. c. 111, § 150A; also
refer to DEP Regulations 310 CMR 7.09(2) and 310 CMR 7.15, when applicable.
Workers Compensation Insurance: in accordance with M.G.L. c. 152, § 25C(6).
Hazards to Air Navigation: in accordance with M.G.L. c. 90, § 35B.
Construction in Coastal Dunes: in accordance with M.G.L. c. 131, § 40 and the Coastal
Wetland regulations at 310 CMR 10.21 through 10.35.
R105.7 After the word “work” insert the phrase “and be posted conspicuously”
R105.8.1 Add subsection:
R105.8.1 Workmanship. All work shall be conducted, installed, protected and completed in
a workmanlike and acceptable manner so as to secure the results intended by this code.
R106.1 At the end of the first paragraph add the following:
All plans and specifications for work designed by a registered design professional shall bear
the seal and signature of the responsible registered design professional in accordance with
M.G.L. c. 143, § 54A. See also www.mass.gov/dpl for policy on electronic seal and signature
for certain registered design professionals.
R106.3.3.4 Add Subsection:
R106.3.3.4 Fire Department Review. For permits that include fire protection system work,
construction documents shall be filed simultaneously with the head of the local fire department
and building official for review and approval. The fire department shall complete its review
within ten-working days after receiving the documents. Upon the fire department’s request, the
building official may grant one or more extensions up to a total review period maximum of 30-
days. If the fire department review is not received within the allowed time frame the building
official may upon review deem the documents in compliance. If the head of the local fire
department disapproves such construction documents, he or she shall notify the building official
(refer to M.G.L. c. 148, § 28A) in writing citing relevant sections of noncompliance with this
code or the section of the referenced standards of Chapter 44.
R106.5 Replace as follows:
R106.5 Retention of Construction Documents. Sets of approved construction documents shall
be retained by the building official in accordance with M.G.L. c. 66, § 8.
R107.1 Add this last sentence:
Prior to issuing a certificate, the building official shall consult with the head of the fire
department.
2/4/11 780 CMR - Eighth Edition - 206
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R107.3 Replace as follows:
R107.3 Temporary Power. See 527 CMR 12.00: Massachusetts Electrical Code (Amendments).
R108.3 Replace as follows:
R108.3 Building Permit Valuations. The applicant for a permit shall provide an estimated
permit value at time of application. If, in the opinion of the building official the valuation is
underestimated on the application, the permit shall be denied, unless the applicant can provide
detailed estimates acceptable to the building official. Final building permit valuation shall be
set by the building official.
108.5 Delete this subsection.
108.6 Replace as follows:
108.6 Work Commencing Before Building Permit Issued. Any person who commences any
work on a building or structure governed by this code before obtaining the necessary building
permit shall be in violation of this code and subject to penalties. See Section 114.
R109.1 At the end of this subsection add the following:
It shall be the duty of the permit holder to provide access to and means for inspections of work
required by this code. The building official may require the permit holder or his representative
to attend these inspections.
R109.1.2 At the end of the sentence add the following and delete the exception:
‘and as otherwise required by the specialized codes’.
R109.1.3 After the word “flooding” add “and coastal dunes”.
R109.1.5 Add a second sentence as follows:
The building official shall inform the applicant of the required points of inspection at the time
of the permit application.
R110.1 Add a last sentence as follows:
Conformance is required to all applicable specialized codes and when applicable, 310 CMR
7.00: Air Pollution, 310 CMR 15.00: The State Environmental Code, Title 5: Standard
Requirements for the Siting, Construction, Inspection, Upgrade and Expansion of On-site
Sewage Treatment and Disposal Systems and for the Transport and Disposal of Septage,
310 CMR 22.00: Drinking Water or 310 CMR 30.000: Hazardous Waste, prior to the issuance
of the certificate of occupancy.
R110.2 Replace as follows:
R110.2 Altered Buildings or Structures. A building or structure, in whole or in part, altered
to change from one use group to another; to a different use within the same use group; the
maximum live load capacity; or the occupancy load capacity shall not be occupied or used until
a certificate has been issued certifying that the work has been completed in accordance with the
provisions of the approved permits and applicable codes.
R110.2.1 Add subsection:
R110.2.1 Massachusetts’ Licensed Care Facilities. Certificate of Occupancy inspections for
Massachusetts licensed care facilities, including inspection of special building features required
by the licensing agency, shall be limited to verifying compliance with the provisions of this code.
2/4/11 780 CMR - Eighth Edition - 207
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R110.3 Add an item 10. as follows:
10. If a care facility is licensed by a State agency, then the name of the agency and the name and
number of any relevant Code of Massachusetts Regulations (CMR) that apply regarding building
features and a list of those building features above and beyond those required by this code.
R111 Delete this section.
112.1 Replace as follows:
112.1 General. Appeals of orders, decisions, determinations and failures to act made by any
state or local agency or any person or state or local agency charged with the administration or
enforcement of the state building code or any of its rules and regulations, except the specialized
codes, relative to the application and interpretation of this code shall be addressed by the building
code appeals board in accordance with M.G.L. c. 143, § 100.
R112.2.1 Delete subsection.
R112.2.2 Delete subsection.
R112.3 Replace as follows:
R112.3 Qualifications. See M.G.L. c. 143, § 100, and 780 CMR 113.
R112.4 Replace as follows:
R112.4 Administration. See M.G.L. c. 143, § 100, and 780 CMR 113.
R113.1 After the words “demolish or” add the following phrase “change the use or”
R113.2 After the words “demolition or” add the following phrase “change the use or”
113.2.1 Add subsection:
113.2.1 Notice Issuance. Every notice or order shall be in writing and shall be served on the
person responsible:
1. Personally, by any person authorized by the building official; or
2. By any person authorized to serve civil process by leaving a copy of the order or notice
at the responsible party’s last and usual place of business or abode; or
3. By sending the party responsible or their agent authorized to accept service of process in
the Massachusetts a copy of the order by registered or certified mail return receipt requested,
if he is within the Massachusetts; or
4. If the responsible party’s last and usual place of business or abode is unknown, by posting
a copy of this order or notice in a conspicuous place on or about the premises in violation and
by publishing it for at least three out of five consecutive days in one or more newspapers of
general circulation wherein the building or premises affected is situated.
113.3 Replace as follows:
113.3 Enforcement. Violations to this code shall be enforced in accordance with the applicable
provisions of M.G.L. c. 143, §§ 6 through 10 and § 94, M.G.L. c. 148, and M.G.L. c. 148A, and
any other applicable state law.
113.4 Insert after the word “alters” the text “, makes a change of use”
R115 Add section:
SECTION R115
UNSAFE STRUCTURES AND EQUIPMENT
R115.1 General. Unsafe or dangerous structures are governed by M.G.L. c. 143, §§ 6, 7, 8, 9
and 10.
2/4/11 780 CMR - Eighth Edition - 208
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R202 Add or replace definitions as follows:
BUILDING OFFICIAL. The building commissioner/inspector of buildings, local inspector or
state building inspector charged with the administration and enforcement of this code in
accordance with M.G.L. c. 143, §§ 3 and 3A.
BASIC WIND SPEED. Replace the text ‘Figure R301.2(4)’ with ‘Table R301.2(4)’
COASTAL WETLAND RESOURCE AREA. Any coastal wetland resource area subject to
protection under the Wetlands Protection Act, M.G.L. c. 131, § 40, and the Wetlands Protection
Act Regulations, 310 CMR 10.21 through 10.35. Coastal Wetland Resource Areas include
barrier beaches, coastal beaches, coastal dunes, rocky intertidal shores, tidal flats, land subject
to 100 year coastal storm flowage, coastal banks, land containing shellfish, lands subject to tidal
action, and lands under an estuary, salt pond or certain streams, ponds, rivers, lakes or creeks
within the coastal zone that are anadromous/catadromous fish runs.
CODE OF MASSACHUSETTS REGULATION (CMR). Regulations that are codified by
the Secretary of State, Commonwealth of Massachusetts. 780 CMR 1.00. lists various CMRs
applicable to building construction and/or design.
CONDITIONED SPACE. An area or room within a building being heated or cooled,
containing uninsulated ducts, or with a fixed opening directly into an adjacent conditioned space.
CONSTRUCTION CONTROL. The compilation of Building Code requirements found in
780 CMR 1, Section 107 or otherwise referenced in 780 CMR and directed toward all buildings
and structures requiring registered architectural services or registered professional engineering
services in accordance with M.G.L. c. 143, § 54A; M.G.L. c. 112, §§ 60A through 60L; and,
M.G.L. c. 112, §§ 81D through 81T.
JURISDICTION. The Board of Building Regulations and Standards.
LOCAL ENFORCEMENT AGENCY. A department or agency in a municipality charged
with the enforcement of this code and appropriate specialized codes which include, but are not
limited to, 248 CMR, the State Plumbing and Gas Fitting Code, and 527 CMR 12.00,
Massachusetts Electrical Code (Amendments).
MANUFACTURED BUILDING. Any building which has concealed elements, such as
electrical, mechanical, plumbing, fire protection, insulation and other systems affecting health
and safety, and which is manufactured and assembled in manufacturing facilities, on or off the
building site. Also, any building as defined above which does not have concealed elements, but
which has been approved by the BBRS at the request of the manufacturer.
NATIVE LUMBER. Native lumber is wood processed in the Commonwealth of Massachusetts
by a mill registered in accordance with 780 CMR 110.R4: Licensing Native Lumber Producers.
Such wood is ungraded but is stamped or certified in accordance with the requirements of
780 CMR 110.R4. For the purpose of this definition, native lumber shall be restricted to the use
in one- and two-story dwellings, barns, sheds, agricultural and accessory buildings and other
structures when permitted by 780 CMR 110.R4.
OFFICIAL INTERPRETATION. A written interpretation made by the Board of Building
Regulations and Standards (BBRS), under authority of M.G.L. c. 143, § 94(e), or by the State
Building Code Appeals Board under authority of M.G.L. c. 143, § 100 of any provision of this
code, or its referenced standards, except the specialized codes.
ORDINANCE. Ordinance or bylaw.
REGISTERED DESIGN PROFESSIONAL. An individual who is licensed or otherwise
authorized to practice his respective design profession as defined by the statutory requirements
of the professional registration laws of Massachusetts.
REPAIRS, ORDINARY. Any maintenance which does not affect the structure, egress, fire
protection systems, fire ratings, energy conservation provisions, plumbing, sanitary, gas,
electrical or other utilities.
2/4/11 780 CMR - Eighth Edition - 209
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
SPECIALIZED CODES. Codes, rules or regulations pertaining to building construction,
reconstruction, alteration, repair or demolition promulgated by and under the authority of various
boards authorized by the general court. See M.G.L. c. 143, § 96.
WIND-BORNE DEBRIS REGION. Areas within hurricane-prone regions within one mile
of the coastal mean high water line where the basic wind speed is 110 miles per hour (49 m/s)
or greater; or where the basic wind speed is equal to or greater than 120 miles per hour (54 m/s).
The coastal mean high water line, in the Massachusetts 110 mph wind zones, forms the outer
edge of the red bands overlaid onto the satellite images found on the MA Department of Public
Safety website at www.mass.gov/dps For estimating purposes, the inner edge of the red bands
is approximately one mile inland from coastal mean high water. For buildings in close proximity
to the inner edge of the red band, to determine whether a building is in a wind borne debris
region, the building official shall use a survey, provided with the permit application and the
building plan, which indicates the distance, in feet, from the location of the proposed building
to the closest location of the coastal mean high water line as described.
R301.1 Add the following note:
Note. Seismic requirements in this code only apply to townhouses three stories or less per
Subsection R101.2, and do not apply to one- and two-family dwellings.
R301.1.1 Add to the end of the second sentence: “and be performed by a registered design professional.”
R301.1.1 Add a fourth note as follows:
4. American Forest and Paper Association (AF&PA) Prescriptive Residential Wood Deck
Construction Guide (DCA6-09) and does not require the services of a registered design
professional.
R301.1.3 Add a last sentence as follows:
‘Engineered design shall be provided by a registered design professional using the wind and
snow loads, and seismic loads if applicable, from this code.’
R301.2.1 Replace “Figure R301.2(4)” with “Table R301.2(4)”.
R301.2.1.1 Add to subsection 1. the text as follows:
or the Guide to Wood Construction in High Wind Areas for One- and Two-Family Dwellings,
110 mph Exposure B. A Commonwealth of Massachusetts version of the checklist can be used
in place of the checklist at the end of the guide. The Massachusetts version is found at
www.mass.gov/dps; or
TABLE R301.2(1) Replace the table as follows and delete the footnotes:
TABLE R301.2(1) CLIMATIC AND GEOGRAPHIC DESIGN CRITERIA
GROUND
SNOW
LOAD
WIND DESIGN SEISMIC DESIGN
CATEGORY
SUBJECT TO DAMAGE FROM
Speed
(mph)
Topographic
Effects Weathering Frost Line
Depth Termite
See Table
R301.2 (4)
See Table
R301.2(5)No
Applies to townhouses
three stories or less,
see Figure R301.2(2)
or 780 CMR Table
1604.11.
Severe 48
inches
See
Figure
301.2 (6)
WINTER
DESIGN
TEMP
ICE BARRIER
UNDERLAYMENT
REQUIRED
FLOOD HAZARDS AIR FREEZING INDEX MEAN ANNUAL
TEMP
Dry bulb Applicable to roofing,, see
Subsection R905.2.7.1
See Section
322.0 and local flood
maps.
Applicable to shallow
foundations,
see Table R403.3(2).
See:
www.ncdc.noaa.gov/fps
f.html
2/4/11 780 CMR - Eighth Edition - 210
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R301.2.1.2 Add a second exception as follows:
Exception 2. Doors and windows which meet the construction requirements approved by a
registered design professional.
301.2.1.3 Replace “Figure R301.2(4)” with “Table R301.2(4)”.
R301.2.1.5.1 Replace “Figure R301.2(4)” with “Table R301.2(4)”.
FIGURE R301.2(4) Delete this figure and footnotes and replace with the following table:
2/4/11 780 CMR - Eighth Edition - 211
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
TABLE R301.2(4) MASSACHUSETTS BASIC WIND SPEEDS
<90 MPH 90 MPH 100 MPH 110 MPH
Adams Acton New Braintree Abington Middleton Acushnet
Alford Agawam New Marlborough Amesbury Milford Aquinnah
Ashfield Amherst New Salem Andover Millis Barnstable
Becket Ashburnham North Brookfield Arlington Millville Bourne
Bernardston Ashby Northampton Ashland Milton Brewster
Buckland Athol Northborough Attleboro Nahant Carver
Cheshire Auburn Northfield Avon Natick Chatham
Clarksburg Ayer Oakham Bedford Needham Chillmark
Colrain Barre Orange Bellingham Newbury Dartmouth
Cummington Belchertown Otis Belmont Newburyport Dennis
Dalton Berlin Palmer Berkley Newton Duxbury
Egremont Blandford Paxton Beverly Norfolk Eastham
Florida Bolton Pelham Billerica North Andover Edgartown
Great Barrington Boxborough Pepperell Blackstone North Attleborough Fairhaven
Greenfield Boylston Petersham Boston North Reading Fall River
Hancock Brimfield Phillipston Boxford Northbridge Falmouth
Hawley Brookfield Princeton Braintree Norton Freetown
Heath Carlisle Rolyalston Bridgewater Norwell Gay Head
Hinsdale Charlton Russell Brockton Norwood Gosnold
Lanesborough Chelmsford Rutland Brookline Oxford Halifax
Lee Chester Sandisfield Burlington Peabody Harwich
Lenox Chesterfield Shirley Cambridge Plainville Kingston
Leyden Chicopee Shrewsbury Canton Quincy Lakeville
Middlefield Clinton Shutesbury Chelsea Randolph Marion
Monroe Conway South Hadley Cohasset Raynham Marshfield
Monterey Deerfield Southampton Concord Reading Mashpee
Mount Washington Dracut Southbridge Danvers Rehoboth Mattapoisett
New Ashford Dunstable Southwick Dedham Revere Middleborough
North Adams East Brookfield Spencer Dighton Rockland Nantucket
Peru East Longmeadow Springfield Douglas Rockport New Bedford
Pittsfield Easthampton Sterling Dover Rowley Oak Bluffs
Plainfield Erving Stow Dudley Salem Orleans
Richmond Fitchburg Sturbridge East Bridgewater Salisbury Pembroke
Rowe Gardner Sunderland Easton Saugus Plymouth
Savoy Gill Templeton Essex Seekonk Plympton
Sheffield Goshen Tolland Everett Sharon Provincetown
Shelburne Granby Townsend Foxborough Sherborn Rochester
Stockbridge Granville Tyngsborough Framingham Somerville Sandwich
Tyringham Groton Wales Franklin Southborough Scituate
Washington Hadley Ware Georgetown Stoneham Somerset
West Stockbridge Hampden Warren Gloucester Stoughton Swansea
Williamstown Hardwick Warwick Grafton Sudbury Tisbury
Windsor Harfield Wendell Groveland Sutton Truro
Worthington Harvard West Boylston Hamilton Swampscott Wareham
Holden West Brookfield Hanover Taunton Welfleet
Holland West Springfield Hanson Tewksbury West Tisbury
Holyoke Westfield Haverhill Topsfield Westport
Hubbardston Westford Hingham Upton Yarmouth
Hudson Westhampton Holbrook Uxbridge
Huntington Westminster Holliston Wakefield
Lancaster Whately mm Walpole
Lawrence Wilbraham Hopkington Waltham
Leicester Williamsburg Hull Watertown
Leominster Winchendon Ipswich Wayland
Leverett Worcester Lexington Webster
Littleton Lincoln Wellesley
Longmeadow Lynn Wenham
Lowell Lynnfield West Bridgewater
Ludlow Malden West Newbury
Lunenburg Manchester Westborough
Maynard Mansfield Weston
Methuen Marblehead Westwood
Millbury Marlborough Weymouth
Monson Medfield Whitman
Montague Medford Willmington
Montgomery Medway Winchester
Melrose Winthrop
Mendon Woburn
Merrimac Wrentham
2/4/11 780 CMR - Eighth Edition - 212
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
g.FIGURE R301.2(5) Delete this Figure and replace with Table R301.2(5) for ground snow loads, P
g.TABLE R301.2(5) MASSACHUSETTS GROUND SNOW LOADS, P
25 PSF 35 PSF 40 PSF 40 PSF 50 PSF
Brewster Abington Alford Nahant Acton Goshen Paxton
Carver Agawam Arlington Natick Adams Greenfield Pepperell
Chatham Amherst Ashland Needham Amesbury Groton Peru
Eastham Avon Belmont New Braintree Andover Groveland Petersham
Harwich Belchertown Bellingham New Marlborough Ashburnham Hamilton Phillipston
Martha’s Vineyard Braintree Beverly New Salem Ashby Hancock Pittsfield
Nantucket Brockton Blackstone Newton Ashfield Harvard Plainfield
Orleans Chicopee Blandford Norfolk Athol Haverhill Princeton
Plymouth Cohasset Boston North Brookfield Auburn Hawley Reading
Provincetown East Longmeadow Brimfield Northampton Ayer Heath Richmond
Truro Easton Brookfield Northbridge Barre Hinsdale Rockport
Wareham Foxborough Brookline Norwood Becket Holden Rolyalston
Wellfleet Granby Cambridge Peabody Bedford Hubbardston Rowe
Hadley Canton Pelham Berlin Hudson Rowley
Hampden Charlton Quincy Bernardston Huntington Rutland
Hingham Chelsea Revere Billerica Ipswich Salisbury
Holbrook Dedham Russell Bolton Lancaster Sandisfield
30 PSF Holyoke Douglas Salem Boxborough Lanesborough Savoy
Acushnet Hull Dover Saugus Boxford Lawrence Shelburne
Attleboro Longmeadow Dudley Sheffield Boylston Lee Shirley
Barnstable Ludlow East Brookfield Sherborn Buckland Leicester Shrewsbury
Berkley Mansfield Easthampton Shutesbury Burlington Lenox Spencer
Bourne Monson Egremont Somerville Carlisle Leominster Sterling
Bridgewater North Attleborough Everett Southampton Charlemont Leyden Stockbridge
Dartmouth Norwell Framingham Southborough Chelmsford Littleton Stow
Dennis Palmer Franklin Southbridge Cheshire Lowell Templeton
Dighton Plainville Grafton Stoneham Chester Lunenburg Tewksbury
Duxbury Randolph Granville Sturbridge Chesterfield Maynard Topsfield
East Bridgewater Rockland Great Barrington Sudbury Clarksburg Merrimac Townsend
Fairhaven Scituate Hardwick Sunderland Clinton Methuen Tyngsborough
Fall River Sharon Hatfield Sutton Colrain Middlefield Tyringham
Falmouth South Hadley Holland Swampscott Concord Millbury Warwick
Freetown Southwick Holliston Tolland Conway Monroe Washington
Gosnold Springfield Hopedale Upton Cummington Montague Wendell
Halifax Stoughton Hopkington Uxbridge Dalton Monterey Wenham
Hanover West Springfield Leverett Wakefield Danvers New Ashford West Boylston
Hanson Westfield Lexington Wales Deerfield Newbury West Newbury
Kingston Weymouth Lincoln Walpole Dracut Newburyport West Stockbridge
Lakeville Wilbraham Lynn Waltham Dunstable North Adams Westford
Marion Lynnfield Ware Erving North Andover Westminster
Marshfield Malden Warren Essex North Reading Williamsburg
Mashpee Manchester Washington Fitchburg Northborough Williamstown
Mattapoisett Marblehead Watertown Florida Northfield Willmington
Middleborough Marlborough Wayland Gardner Oakham Winchendon
New Bedford Medfield Webster Georgetown Orange Windsor
Norton Medford Wellesley Gill Otis Worcester
Pembroke Medway West Brookfield Gloucester Oxford Worthington
Plympton Melrose Westborough
Raynham Mendon Westhampton
Rehoboth Middleton Weston
Rochester Milford Westwood
Sandwich Millis Whately
Seekonk Millville Winchester
Somerset Milton Winthrop
Swansea Montgomery Woburn
Taunton Mount Washington Worcester
West Bridgewater Wrentham
Westport
Whitman
2/4/11 780 CMR - Eighth Edition - 213
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R301.2.2 Exception Delete the following text: ‘located in Seismic Design Category C’
R301.2.4 Delete the exception, only.
R301.2.4.1 Delete subsection.
R303.3 Add two sentences as follows:
Mechanical ventilation is required for bathrooms with a shower or bathtub. Also see 105 CMR
410.000: Minimum Standards of Fitness for Human Habitation (State Sanitary Code, Chapter
II) and 248 CMR 10.00: Uniform State Plumbing Code as these codes may also have mechanical
ventilation requirements.
R303.6 Add a first sentence as follows:
‘Stairway illumination shall comply with 527 CMR 10.00: Fire Prevention, General Provisions.’
and retain the remaining text of the paragraph.
R303.8 Add a last sentence as follows:
‘See 105 CMR 410.000: Minimum Standards of Fitness for Human Habitation (State Sanitary
Code, Chapter II) for rental property.’
R305.1 Delete the text ‘and portions of basements containing these spaces’
R305.1.1 Replace the paragraph as follows:
‘Basements areas, including but not limited to areas with suspended ceilings, shall have a
ceiling height of not less than six feet eight inches.’ Retain the Exception.
R306.5 Add subsection:
R306.5 Other Regulations. Requirements of Section R306 shall be in conformance with the
Board of Fire Prevention Regulations at 527 CMR, 248 CMR 10.00: Uniform State Plumbing
Code, 310 CMR 15.00: The State Environmental Code, Title 5: Standard Requirements for the
Siting, Construction, Inspection, Upgrade and Expansion of On-site Sewage Treatment and
Disposal Systems and for the Transport and Disposal of Septage and 105 CMR 410.000:
Minimum Standards of Fitness for Human Habitation (State Sanitary Code, Chapter II).
R307 Replace in its entirety as follows:
R307.1 Toilet, Bath, and Shower. Requirements of Section R307 shall be in conformance with
248 CMR 10.00: Uniform State Plumbing Code.
R308.1 Add a last sentence as follows: ‘Also see M.G.L. c. 143 §§ 3t, 3u, and 3v’
R310.1.1 Add a second exception:
Exception. Double hung windows shall have a minimum net clear opening of 3.3 square feet
(0.31 m ).2
R310.1.2 Replace as follows:
R310.1.2 Dimensions. The minimum net clear opening dimensions shall be 20 inches by 24
inches in either direction.
R310.1.3 Reserved.
2/4/11 780 CMR - Eighth Edition - 214
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R311.1 and R311.2 Replace as follows:
R311.1 Means of Egress. All dwellings shall be provided with two means of egress as provided
in this section. The means of egress shall provide a continuous and unobstructed path of vertical
and horizontal egress travel from all portions of the dwelling to the exterior of the dwelling at
the required egress doors without requiring travel through a garage. For townhouses also see the
Architectural Access Board’s regulations at 521 CMR.
Exception. Egress through the secondary egress door, required in subsection R311.2, may
include travel through a garage provided the garage has an exit door meeting the
requirements of a secondary egress door.
R311.2 Egress Door. At least two egress doors shall be provided for each dwelling unit, remote
as possible from each other, at the normal level of exit.
Exceptions:
1. In multi-level dwellings, including but not limited to townhouses, split-level and
raised ranch style layouts, the two separate egress doors required by R311.2 are permitted
to be located on different levels.
2. Where site topography prevents direct access at two remote locations to grade from
the normal level of entry, the two separate egress doors required by R311.2 are permitted
to be located on different levels.
The primary egress door shall be side-hinged, and shall provide a minimum clear width of 32
inches (813 mm) when measured between the face of the door and the stop, with the door open
90 degrees (1.57 rad). The secondary egress door shall be side-hinged or sliding, and shall
provide a minimum clear width of 28 inches (711mm) when measured between the face of the
door and the stop, with the door open 90 degrees (1.57 rad). The minimum clear height of the
primary and secondary egress door opening shall not be less than 78 inches (1981 mm) in height
measured from the top of the threshold to the bottom of the stop. Other exterior doors shall not
be required to comply with these minimum dimensions. Egress doors shall be readily openable
from inside the dwelling without the use of a key or special knowledge or effort.
R311.2.1 Add subsection:
R311.2.1 Interior Doors. All doors providing access to habitable rooms shall have a minimum
nominal width of 30 inches (762 mm) and a minimum nominal height of six feet, six inches
(1981 mm).
Exceptions:
1. Doors providing access to bathrooms are permitted to be 28 inches (711 mm) in
nominal width.
2. Doors providing access to bathrooms in existing buildings are permitted to be 24
inches (610 mm) in nominal width.
R311.7.4.1 Replace the phrase ‘7¾ inches (196 mm)’ with ‘8¼ inches (210 mm)’.
R311.7.4.2 Replace the phrase ‘10 inches (254 mm)’ with ‘9 inches (229 mm)’
R311.7.4.2 Replace the second paragraph as follows:
Winder treads shall have a minimum tread depth equal to the tread depth of the straight run
portion of the stairs measured as above at a point 12 inches from the side where the treads are
narrower. Winder treads shall have a minimum tread depth of three inches at any point. Within
any flight of stairs, the greatest winder tread depth at the 12 inch walk line shall not exceed the
smallest by more than d inch.
R313.1.1 Replace as follows:
R313.1.1 Design and Installation. Automatic residential fire sprinkler systems for townhouses
shall be designed and installed in accordance with NFPA 13, 13R, or 13 D, as applicable.
1. A townhouse building with an aggregate area of 12,000 square feet or more shall use a
NFPA 13 system.
2/4/11 780 CMR - Eighth Edition - 215
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
2. A townhouse building with an aggregate area less than 12,000 square feet shall be
permitted to use a NFPA 13-R system.
Exception. A three unit townhouse building with an aggregate area less than 12,000
square feet shall be permitted to use a NFPA 13-D system.
For the purposes of this section the aggregate area shall be the combined area of all stories of the
building and fire walls shall not be considered to create separate buildings. Aggregate area shall
include garage area, basement area, and finished attic area. Unfinished attic area shall not be
included in aggregate area.
R313.2 Replace as follows:
R313.2 One- and Two-family Dwellings Automatic Fire Sprinkler Systems. Only one- and
two-family dwellings having an aggregate area greater than 14,400 square feet shall have fire
sprinklers installed in accordance with NFPA 13D. Aggregate area for the purpose of this
section shall include basements but not garages and unfinished attics. Additions to such
dwellings with automatic sprinkler systems shall have automatic sprinklers installed in
accordance with NFPA 13D.
R313.2.1 Delete the text: ‘Section P2904 or’
R314.1 Replace the text “listed in accordance with UL 217” as follows “photoelectric type smoke alarms
listed in accordance with UL 217 or UL 268.
R314.3 Add subsections 4 and 5 as follows:
4. Near the base of all stairs where such stairs lead to another occupied floor.
5. For each 1,200 square feet of area or part thereof.
R314.5 Add a section and a subsection:
R314.5 Heat Detector. A single heat detector listed for the ambient environment shall be
installed in:
1. Any integral garage (“garage under”) or attached garage to the main house (detached
garages do not require a heat detector).
2. A new addition attached garage to an existing dwelling. If the existing house contains
a fire detection system that is compatible with the garage heat detector, then the detector shall
be interconnected to the existing system. Where the existing fire detection system is not
compatible with the garage heat detector, the garage heat detector shall be connected to a
sounder (occupant notification appliance) or compatible heat detector containing a sounding
device, located in the dwelling and within 20 feet (6096 mm) of the nearest door to the
garage from the dwelling. The required garage heat detector is neither required to
incorporate audible alarm notification nor is any audible notification device required in the
garage.
R314.5.1 Heat Detector Placement. For flat-finished ceilings, the single heat detector shall
be placed on or near the center of the garage ceiling. For sloped ceilings having a rise to run
of greater than one foot in eight feet (305 mm in 2438 mm), the single heat detector shall be
placed in the approximate center of the vaulted ceiling but no closer than four inches (102
mm) to any wall.
R315.1 Replace as follows:
R315.1 Governing Regulations. Carbon monoxide alarms (alarms) for new construction and
existing dwellings shall be furnished, installed and maintained by the owner in accordance with
this section, M.G.L. c. 148, § 26F½ , 527 CMR 31.00: Carbon Monoxide Alarms, 248 CMR,
NFPA 720 and the manufacturer’s instructions.
2/4/11 780 CMR - Eighth Edition - 216
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R315.2 Replace as follows:
R315.2 Installation Locations. One alarm shall be installed on each story of a dwelling unit,
including basements and cellars (but not including crawl spaces and uninhabitable attics). When
mounting a carbon monoxide alarm on a story with a bedroom, the alarm, shall be located
outside of bedrooms but no further than 10 feet of any bedroom door. If a combination
smoke/carbon monoxide alarm is used, its location must comply with this section.
R315.3 Replace as follows:
R315.3 New Construction. Alarms shall either be an interconnected 120V or part of a low-
voltage combination system or wireless system. Alarms shall have secondary (standby) power
from monitored batteries in accordance with NFPA 72. For fire alarm control units (panels) and
wireless systems, the panel battery shall serve as the source of secondary power. Alarms shall
be UL 2034 or UL 2075 listed, as applicable. Alarms may be interconnected with fire alarms
providing they are compatible and the fire alarms take precedence.
R315.4 Add subsection:
R315.4 Existing Dwellings. For existing dwellings, carbon monoxide alarms shall be provided
in accordance with Section 315 for new construction, as applicable, for the following
circumstances:
1. When one or more bedrooms are added or created in a dwelling unit, the entire dwelling
shall be provided with alarms.
2. When a dwelling unit undergoes complete reconstruction such that all walls and ceilings
are open to framing the entire dwelling unit shall be provided with alarms.
3. In an existing two-family dwelling, when one or more bedrooms are added or created in
both of the two dwelling units, the entire building shall be provided with alarms.
4. In a townhouse building when one or more bedrooms are added or created in a dwelling
then that dwelling unit shall be provided with carbon monoxide alarms.
5. In a townhouse building when a dwelling unit undergoes complete reconstruction such
that all walls and ceilings are open to framing, that dwelling unit shall be provided with
carbon monoxide alarms.
R319.1 Replace subsection:
R319.1 Address Numbers. See M.G.L. c. 148, § 59.
R320.1 Replace subsection:
R320.1 Scope. For townhouses see 521 CMR.
R321.1 Replace ‘ASME A17.1’ with ‘524 CMR’.
R321.2 Replace ‘ASME A18.1’ with ‘524 CMR’.
R321.3 Replace ‘ICC A117.1’ with ‘524 CMR and 521 CMR’.
R322.1 Replace as follows and delete the exception:
R322.1 General. Buildings and structures constructed in whole or in part in flood hazard areas
(including A or V Zones) as established in Table R301.2(1), or in a coastal dune as established
in Section R322.4 shall be designed and constructed in accordance with the provisions contained
in this section.
R322.1.1 Add the following note to this subsection:
Note. In using ASCE 24 delete tables 1-1, 2-1, 4-1, 5-1, 6-1, and 7-1. For elevation
requirements use elevation requirements of R322, as amended. Also, delete references to
Coastal A zones and instead use requirements for A zones in R322.
2/4/11 780 CMR - Eighth Edition - 217
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R322.1.4 Replace as follows:
R322.1.4 Establishing the Design Flood Elevation. The design flood elevation shall be used
to define areas prone to flooding. The design flood elevation is the base flood elevation at the
depth of peak elevation of flooding (including wave height) which has a 1% (100-year flood) or
greater chance of being equaled or exceeded in any given year, and as obtained from the
community’s Flood Insurance Study (FIS) with the accompanying Flood Insurance Rate Map
(FIRM) and Flood Boundary and Floodway Map (FBFM).
R322.1.4.2 Delete subsection.
R322.1.5 Replace “is useable” with “is not a basement and is useable”.
R322.1.7 Delete.
R322.1.11 Add subsection:
R322.1.11 Basement. The portion of a building having its floor subgrade (below ground level)
on all sides, but is not a crawlspace. This definition of “Basement” is limited in application to
the provisions of Section R322.
R322.1.12 Add subsection:
R322.1.12 Construction documents. The construction documents shall include documentation
that is prepared and sealed by a registered design professional that the design and methods of
construction to be used meet the applicable criteria of this section.
R322.2 Replace as follows:
R322.2 Flood Hazard Areas (A Zones). All areas that have been determined to be prone to
flooding but not subject to high velocity wave action shall be designated as flood hazard areas.
Flood Hazard areas shall include all areas shown as A zones on the most recent Flood Hazard
Boundary Map or Flood Insurance Rate Map. All building and structures constructed in whole
or in part in flood hazard areas shall be designed and constructed in accordance with subsections
R322.2.1 through R322.2.3.
R322.2.1 Revise as follows and delete the exception:
R322.2.1 Elevation Requirements.
1. Buildings and structures in flood hazard areas shall have the lowest floors elevated to or
above the design flood elevation.
2. In areas of shallow flooding (AO Zones), buildings and structures shall have the lowest
floor (including basement) elevated at least as high above the highest adjacent grade as the
depth number specified in feet on the FIRM, or at least 2 feet (610 mm) if a depth number
is not specified.
3. Basement floors shall be elevated to or above the design flood elevation.
4. For lateral additions that are a substantial improvement, only the addition shall be
elevated so that the lowest floor, including basement/cellars, is located at or above design
flood elevation.
R322.2.2 In the first sentence, after “design flood elevation” insert “and are not basements”.
R322.3 Add a second sentence as follows:
“Coastal high-hazard areas shall include all areas shown as V zones on the most recent Flood
Hazard Boundary Map or Flood Insurance Rate Map.”
R322.3.1 Delete item 2.
2/4/11 780 CMR - Eighth Edition - 218
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R322.3.2 Replace item 1 and add item 5 as follows:
1. All buildings and structures erected within coastal high hazard areas shall be elevated so that
the lowest portion of all structural members supporting the lowest floor, with the exception of
mat or raft foundations, piling, pile caps, columns, grade beams and bracing, is located at or
above the design flood elevation plus two feet.
5. For lateral additions that are not a substantial improvement, only the addition shall be
elevated so that the bottom of the lowest horizontal structural member of the lowest floor with
the exception of pilings or pile caps is located at an elevation that is at least two feet above the
design flood elevation.
322.3.6 Delete.
R322.4 Add subsection:
R322.4 Coastal Dunes. The following applies to construction in a coastal wetland resource
area:
R322.4.1 Determination of Coastal Dunes. To reduce flood damage, ensure the structural
integrity of buildings or structures including manufactured homes, located in coastal dunes,
to protect the public safety and to eliminate certain conflicts between the coastal dune
performance standards set forth in the Wetlands Protection Act Regulations, 310 CMR
10.28, and this code, R322.4 establishes requirements for design and construction in coastal
dunes significant to the interests of flood control and/or storm damage prevention identified
in 310 CMR 10.28: Coastal Dunes.
To determine whether a proposed building or structure, including a manufactured home,
a lateral addition, work on a foundation that under R105.3.1.2 requires compliance with
R322, or substantial improvement to a building or structure that has incurred substantial
damage as the result of flooding and/or storms is located within an area that is a coastal dune
significant to the interests of flood control and/or storm damage prevention, the building
official shall require the submission of certain construction documents in accordance with
R322.4.2.
R322.4.2 Construction Documents. For buildings and structures, including new or replacement
manufactured homes, lateral additions, foundations that are replaced in total or repaired so as to
constitute substantial repair of a foundation, or substantial repair or improvement of a building
or structure that has incurred substantial damage as a result of flooding and/or storms, proposed
on a parcel of land that is located wholly or partially within a coastal wetland resource area
shown on the map entitled “Map of Coastal Wetland Resources For Building Officials”, the
building official shall require submission of one of the construction documents specified in (a)
through (d) along with a notarized statement by the applicant that the Order, Determination or
Notice is in effect and is not the subject of any administrative appeals before the Department of
Environmental Protection or the Division of Administrative Law Appeals. No building permit
shall issue unless and until a construction document that conforms to the requirements of this
section is submitted.
(a) An Order of Conditions establishing the boundaries of all coastal wetland resource areas
in a plan referenced in and accompanying the Order. The Order shall determine whether the
coastal wetland resource areas are significant to any of the interests identified in the
Wetlands Protection Act, M.G.L. c. 131, § 40 including the interests of flood control and
storm damage prevention. If the Order indicates that the proposed construction work is
located within a coastal dune that is significant to the interests of flood control and/or storm
damage prevention, the Order of Conditions must allow the proposed construction.
(b) An Order of Resource Area Delineation stating that the proposed construction work is
outside the boundaries of all coastal wetland resource areas as shown on a plan referenced
in and accompanying the Order.
(c) A Determination of Applicability stating that the proposed construction work is outside
the boundaries of all coastal wetland resource areas as shown on a plan referenced in and
accompanying the Determination or will not fill, dredge or alter a coastal wetland resource
area.
2/4/11 780 CMR - Eighth Edition - 219
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
(d) A Notice of Non-significance evidencing that the proposed construction work is within
a coastal wetland resource area as shown on a plan referenced in and accompanying the
Notice and stating that the coastal wetland resource area is not significant to any of the
interests identified in M.G.L. c. 131, § 40: Removal, Fill, Dredging or Altering of Land
Bordering Waters (the Wetlands Protection Act).
R322.4.3 Structural Elevation. The elevation of the bottom of the lowest horizontal structural
member, as required by the lowest floor elevation inspection in Subsection R109.1.3, shall be
submitted.
R322.4.4 Additional Documentation. Documentation for buildings located in more than one
zone shall meet the requirements of all zones.
R322.4.5 Elevation Requirements. For new buildings and structures, new foundations,
replacement or substantial repair of a foundation, or repair of a substantially damaged structure
where damage is the result of a storm or flooding the entire structure shall be elevated so that the
bottom of the lowest horizontal structural member of the lowest floor with the exception of
pilings or pile caps is located at the elevation required by the Order of Conditions of the local
Conservation Commission in accordance with the Wetlands Protection Act, M.G.L. c. 131, §40:
Removal, Fill, Dredging or Altering Land Bordering Waters (the Wetland Protection Act) and
Wetlands Protection Regulations, 310 CMR 10.21 through 10.35: Additional Regulations for
Coastal Wetlands. For lateral additions that are not a substantial improvement, only the addition
shall be elevated so that the bottom of the lowest horizontal structural member of the lowest floor
with the exception of pilings or pile caps is located at the elevation required by the Order of
Conditions of the local Conservation Commission in accordance with M.G.L. c. 131, § 40 and
Wetlands Protection Regulations, 310 CMR 10.21 through 10.35.
R322.4.6 Foundations. Foundations for work meeting the elevation requirements of Section
R322 shall consist of open pilings without footings to allow the movement of the dune.
Exception. Where surface or subsurface conditions consist of non-erodible soil that prevents
the use of pile foundations, spread footings or mat foundations may be permitted. Such
foundations shall be anchored to prevent sliding, uplift or overturning of the footing and the
non-erodible soil it is attached to and be designed to withstand any combination of loads.
R322.4.7 Enclosed Areas below Design Flood Elevation. Enclosures are not permitted below
the lowest horizontal structural member of the lowest floor.
R401.2 Add exception:
Exception. Compacted fill not more than 12 inches (305 mm) in depth, provided that the fill
is adequately compacted using appropriate mechanical means.
R401.3 Add a last sentence as follows:
“Temporary and finished grading shall not direct nor create flooding or damage to adjacent
property during or after completion of construction”.
R401.4.1 Insert after “Table R401.4.1” the text “or 780 CMR Table 1806.2a”
R401.5 Add subsection:
R401.5 Seismic Requirements. Seismic requirements in this chapter shall only apply to
townhouses and shall not apply to one- and two-family dwellings.
R401.6 Add subsection:
R401.6 Flood Resistant Construction. See section 322 for flood-resistant construction
requirements.
R403.1 Add the following to the end of the second sentence:
“as per subsection R401.2”
2/4/11 780 CMR - Eighth Edition - 220
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R403.1.6 Add the designation “A 307 or other applicable steel” before the word “anchor bolt” in the first
sentence of the second paragraph. Also, after the words “anchor bolts” insert the text “installed in accordance
with the manufacturer’s printed instructions.”
R404.1.7 Add a last sentence as follows:
Backfill material shall be free draining and free of organic materials, construction debris, cobbles
and boulders, shall be placed in lifts not exceeding 12-inches and shall be mechanically
compacted.
R406.2 After the last paragraph (on membranes) add this paragraph:
Through-wall formwork ties shall be removed from both faces of the foundation walls which
enclose basements, cellars, below-grade garages or any space having the potential to be
converted to useable or occupied space. Remaining holes shall be patched with hydraulic
cement.
R408.7 Delete the exception.
R502.2.2 At the end of this paragraph add this text “and no live load acting on the interior span.”
R502.3 At the end of the second sentence add this text:
“or the American Wood Council (AWC) Maximum Span Calculator for Wood Joists & Rafters
found at http://www.awc.org/calculators/span/calc/timbercalcstyle.asp”
R502.11.1 Replace “registered professional” with “registered design professional”.
R506.1.1 Add subsection, exception, and associated table:
R506.1.1 Control Joints. Slabs shall be constructed with control joints having a depth of at
least one quarter of the slab thickness but not less than one inch (25 mm). Joints shall be spaced
at intervals not greater than 30 feet (9144 mm) in each direction. Control joints shall be placed
at locations where the slab width or length changes.
Exception. Control joints may be omitted when the slab is reinforced in accordance with
Table R506.1.1. Reinforcement shall be placed at the mid-depth of the slab or two inches
(51 mm) from the top of slabs greater than four inches (102 mm) in thickness.
Table R506.1.1
Maximum Dimension of Slab or
Distance Between Control Joints (ft.)WWF Wire Spacing (in.)WWF Wire Size Designation (in.)Slab Thickness (in.)
3.5 4 4.5 5.0 5.5 6
42 36 32 29 26 24 6 x 6 W1.4 x W1.4
59 52 46 42 38 35 6 x 6 W2.0 x W2.0
86 75 67 60 55 50 6 x 6 W2.9 x W2.9
R602.10 Add a second exception as follows:
Exception 2. Unconditioned single story rooms, of areas less than 600 sq. ft., where the main
dwelling is connected to the room via an exterior door or slider and no other openings between
the main dwelling and room exist (i.e. thermally isolated).
702.3.5.1 Add subsection:
702.3.5.1 Ceiling attachment. Only designs or methods that use mechanical fasteners in
accordance with Table R702.3.5 shall be used for attaching gypsum board to ceilings in buildings
governed by this code including manufactured buildings. Alternative designs, such as using
adhesive only, are not permitted.
2/4/11 780 CMR - Eighth Edition - 221
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
R802.4 Add this text to the end of the second sentence:
‘or utilize the American Wood Council (AWC) Maximum Span Calculator for Wood Joists &
Rafters found at http://www.awc.org/calculators/span/calc/timbercalcstyle.asp
R802.5 Add this text to the end of the second sentence:
‘or utilize the American Wood Council (AWC) Maximum Span Calculator for Wood Joists &
Rafters found at http://www.awc.org/calculators/span/calc/timbercalcstyle.asp
R901.1 Add a final sentence as follows:
In roofing and reroofing, the energy conservation requirements of Chapter 11 must also be
satisfied.
R905.1 Add a final sentence as follows:
Where there is a discrepancy between the requirements of this section and the manufacturer’s
printed instructions or code evaluation report, the manufacturer’s printed instructions or code
evaluation report shall govern.
R906.1 Add a final sentence as follows:
In roofing and reroofing, the energy conservation requirements of Chapter 11 must also be
satisfied.
R1001.1 Add a second sentence that reads:
Chimneys shall be structurally sound, durable, smoke tight and capable of conveying flue gases
to the exterior safely.
R1003.11 Add a second sentence that reads:
Liner size, length and installation shall be in accordance with this code or the appliance
manufacturer’s requirements as applicable.
N1101.2 and N1101.2.1 Replace as follows:
N1101.2 Compliance. Climate zone 5A shall be used for municipalities in MA. Compliance
to this chapter shall be demonstrated by, either:
1. Meeting the requirements of the International Energy Conservation Code 2009 or,
2. Compliance with Sections N1101, N1102.4, N1102.5, N1103.1, N1103.2.2, N1103.2.3,
and N1103.3 to N1103.9 and either:
a. Sections N1102.1 through N1102.3, N1103.2.1 and N1104.1 or
b. Section 405 of the International Energy Conservation Code 2009 and these Massa-
chusetts amendments:
405.6.2.1 Add subsection:
405.6.2.1 Approved Calculation Software Tools. Software tools meeting the
requirements of Subsection 405.6 are:
1. REScheck: found at http://www.energycodes.gov/
405.7 Add subsections:
405.7 Approved Alternative Energy Performance Methods. In addition to the
IECC performance compliance path detailed in subsections 405.1 to 405.5 the
following rating threshold criteria of this section are sufficient to demonstrate
energy code compliance under section 405 without calculation of a standard
reference design.
2/4/11 780 CMR - Eighth Edition - 222
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
1. RESNET Approved Software for the Home Energy Rating System
(HERS). Where the HERS rater verified index on the building is 75 or fewer
points for the finished building together with a completed and HERS rater
verified ENERGY STAR Thermal Enclosure Checklist. The mandatory
provisions of subsection 401.2 apply.
2. Passive House Institute US (PHIUS) Approved Software: Passive
House Planning Package (PHPP). Where the Specific Space Heat Demand
as modeled in Passive House Planning Package (PHPP) by a Certified
Passive House Consultant is less than or equal to 20 KBtu/sq ft/year. The
mandatory provisions of subsection 401.2 apply.
405.7.1 Documentation. The following documentation is required for energy
code compliance under subsection 405.7:
1. For HERS compliance, a compliance report which includes a proposed
HERS index of 75 or lower, a description of the building’s energy features,
and a statement that the rating index is “based on plans” will be required for
issuance of a building permit. A copy of the final certificate indicating that
the HERS rater verified index is 75 or less for the finished building together
with a completed HERS rater verified ENERGY STAR Thermal Enclosure
Checklist is to be submitted to the building official before the certificate of
occupancy is issued.
2. For Passive House Planning Package (PHPP) verified compliance, a
compliance features, and a statement that the estimated Specific Space Heat
Demand is “based on plans” will be required for issuance of a building
permit. A copy of the final PHPP report indicating the finished building
achieves a Certified Passive House Consultant-verified Specific Space Heat
Demand of less than or equal to 20 KBtus/sq ft/year shall be submitted to the
building official before the certificate of occupancy is issued.
N1101.2.1 Interior Design Conditions. The interior design temperatures used for heating
and cooling load calculations shall be a maximum of 72EF (22EC) for heating and minimum
of 74EF (24EC) for cooling.
Table N1102.2.1 In the Climate Zone 5 row, replace the value ‘.060’ with ‘.057’.
N1102.2.2 Replace the second sentence as follows: ‘This reduction of insulation from the requirements of
Section N1102.1 shall be limited to 500 square feet (46 m ) or 20% of the total insulated ceiling area,2
whichever is less.’
Table N1102.2.1 To the criteria of the first row of the table add ‘Air-permeable insulation is inside of an air
barrier’ and to the criteria of the fifth row of the table replace ‘floor’ with ‘insulation’
N1102.5 Add subsection:
N1102.5 Maximum Fenestration U-factor and SHGC. The area-weighted average maximum
fenestration U-factor permitted using trade-offs from Subsection N1102.1.3 or N1105 shall be
0.48.
N1103.8.3 Add an exception as follows:
Exception. Pool covers deriving over 60% of the energy for heating from site-recovered energy
or solar energy source.
M1201.1 Add a final sentence as follows:
In this chapter where the design, installation, maintenance, alteration and/or inspection of
mechanical systems is controlled by one of the specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement shall be by a person other than
the building official.
2/4/11 780 CMR - Eighth Edition - 223
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
M1301.1 Add a final sentence as follows:
In this chapter where the design, installation, maintenance, alteration and/or inspection of
mechanical systems is controlled by one of the specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement shall be by a person other than
the building official.
M1303.2 Add subsection:
M1303.2 Solid Fuel-burning Appliance Labeling. Solid fuel-burning appliances (see
Subsection M1303.3 for Central Heating Appliances) shall bear a permanent and legible factory-
applied label supplied to the manufacturer and controlled by an approved testing agency; such
label shall contain the following information:
1. Manufacturer’s name and trademark;
2. Model and/or identification number of the appliance;
3. Type(s) of fuel(s) approved;
4. Testing laboratory’s name or trademark and location;
5. Date tested;
6. Clearances to combustibles:
a. Above top
b. From front
c. From back
d. From sides
7. Floor protection*;
8. National test (listing) standard(s); and
9. Label serial number.
*If floor protection information is not on the label, it will be acceptable if contained with the
User/Installation Manual.
M1303.3 Add subsection:
M1303.3 Solid Fuel-burning Central Heating Appliance Labeling. Solid fuel-burning boilers
or warm air furnaces shall bear a permanent and legible factory-applied label supplied to the
manufacturer and controlled by an approved testing agency; such label shall contain Subsection
M1303.2 items 1. to 9. and the following information:
10. Type of appliance (boiler or warm air furnace);
11. Boilers, pressure vessels, and pressure relief devices must be stamped in accordance
with M.G.L. c. 146, §§ 24 and 34.
M1401.1 Add a final sentence as follows:
In this chapter where the design, installation, maintenance, alteration and/or inspection of
mechanical systems is controlled by one of the specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement shall be by a person other than
the building official.
M1401.6 Add subsection:
M1401.6 Solid Fuel-Burning Heating Appliances. Solid fuel-burning heating appliances
include, but are not limited to: room heaters and stoves, fireplace inserts, furnaces and boilers.
The fuel for such appliances includes, but is not limited to: wood, wood pellets, coal, nut shells,
and corn. Solid fuel-burning appliances shall be tested and listed by approved agencies and
installed, operated and maintained in accordance with such listing, the manufacturers’
requirements and otherwise conform to the requirements of this chapter or those found in the
International Mechanical Code.
Notes:
1. No solid fuel-burning appliance shall be installed in Massachusetts unless such appliance
conforms to all applicable requirements of this chapter, including the testing and listing of
all clearances to combustibles and identification of required floor protection.
2/4/11 780 CMR - Eighth Edition - 224
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
2. In the absence of explicit requirements of this chapter, the applicable requirements of
NFPA 211 shall apply.
M1401.6.1 Hazardous Locations. Solid fuel-burning appliances shall not be installed in
hazardous locations (any location considered to be a fire hazard for flammable vapors, dust,
combustible fibers or other highly combustible substances)
Exception. Solid fuel-fired appliances listed for such locations.
M1401.6.2 Floor Protection General. Floor protection listing requirements for a new or
used appliance shall be met. In the absence of listing requirements, solid fuel-burning
appliances shall have floor protection that is noncombustible material applied to the
combustible or noncombustible floor area underneath and extending in front, to the sides and
to the rear of a heat producing appliance, and have the necessary thermal conductivity to
satisfy the floor protection requirements of the appliance. Various “hearth rugs,” “mats,”
“tile board,” “hearth board” and similar products sold as floor protectors may be
noncombustible but may not satisfy thermal conductivity requirements of this section.
M1401.6.2.1 Floor Protection Requirements. Floor protection requirements shall be:
1. four inches (102 mm) of millboard having a thermal conductivity k = 0.84 (Btu)
(inch)/(ft ) (hour) (°F) or,2
2. a noncombustible floor protector of the same overall thermal conductivity in (1.)
or,
3. approved by a registered design professional.
Exception. If existing floor protection can be demonstrated to have been
adequate for a previous installation of a used solid fuel-burning appliance, then
such floor protection shall be allowed. If calculations demonstrate that the
existing floor protection has a thermal conductivity lower than that set by this
section, then the existing floor protection may be maintained.
M1401.6.3 Used Solid Fuel-burning Appliances. Used solid fuel-burning appliances that
predate the listing requirements set forth in this code may be utilized but the installation of
such appliances shall otherwise conform to the requirements of this code, as applicable and
such installations shall be inspected by the building official (or fire official in such towns that
utilize the fire official for such inspection purposes).
M1401.6.3.1 Used Solid Fuel-burning Appliance Clearances to Combustibles. In the
absence of listed clearances and floor protection requirements, used solid fuel-burning
appliances shall be installed in accordance with the clearances of this code.
M1414.1 Add a final sentence as follows:
Also see Chapter 10 for detailed guidance on solid fuel-burning appliances.
M1501.1 Add a final sentence as follows:
In this chapter where the design, installation, maintenance, alteration and/or inspection of
mechanical systems is controlled by one of the specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement shall be by a person other than
the building official.
M1507.1 Replace as follows:
M1507.1 General. Toilet rooms and bathrooms shall be mechanically ventilated in accordance
with the requirements of Table M1507.3 and the ventilation equipment shall be installed in
accordance with this chapter and the governing specialized codes.
M1601.1 Add a final sentence as follows:
In this chapter where the design, installation, maintenance, alteration and/or inspection of
mechanical systems is controlled by one of the specialized codes (see Chapter 1) the
requirements of the specialized codes govern and enforcement shall be by a person other than
the building official.
2/4/11 780 CMR - Eighth Edition - 225
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
M1601.3 Replace the first sentence as follows:
Duct insulation shall conform to the following requirements and the requirements of Chapter 11.
M1601.4 Delete the sentence and replace with:
Duct installation shall comply with Subsections M1601.4.1 through M1601.4.7 and the
requirements of Chapter 11.
M1601.4.5 Delete the first phrase and replace with:
Duct insulation shall be installed in accordance with the following requirements and the
requirements of Chapter 11. Where conflict exists between the requirements of this Section and
Chapter 11, Chapter 11 requirements shall govern.
M1701.1 Replace as follows:
M1701.1 Scope. Solid-fuel-burning appliances shall be provided with combustion air in
accordance with the appliance manufacturer’s installation instructions. Oil-fired appliances shall
be provided with combustion air in accordance with 527 CMR 4.00: Oil Burning Equipment.
The methods of providing combustion air in this chapter do not apply to fireplaces, fireplace
stoves and direct-vent appliances. The requirements for combustion and dilution air for gas-fired
appliances shall be in accordance with Chapter 24. In this chapter where the design, installation,
maintenance, alteration and/or inspection of mechanical systems is controlled by one of the
specialized codes (see Chapter 1) the requirements of the specialized codes govern and
enforcement shall be by a person other than the building official.
M1801.1 Replace the third sentence as follows:
The requirements of this chapter shall not apply to gas-fired and oil-fired appliances. For gas-
fired appliances see the Board of State Examiners of Plumbers and Gas Fitters regulations at
248 CMR. For oil-fired appliances see 527 CMR 4.00: Oil Burning Equipment. For electrical
requirements see 527 CMR 12.00: Massachusetts Electrical Code (Amendments). For fire
prevention regulations 527 CMR governs, except where 527 CMR is silent, in which case the
International Fire Code requirements, as applicable, apply. Solid fuel-burning appliances shall
satisfy the manufacturer’s requirements, and in the absence of same, this code shall apply.
M1801.11 Delete the Exception to subsection 1.
M1801.12 Add an Exception as follows:
Exception. Unless common connection is allowed by 248 CMR or 527 CMR. If allowed, the
common flue shall be of such size to serve all appliances connected if such appliances were
operated simultaneously. Note that 248 CMR and 527 CMR are enforced by gas inspectors, and
the heads of fire departments, respectively.
M1803.2 In the subsection title and the paragraph delete the text “oil and”
M1900 Add section:
M1900 General. The requirement of this chapter shall not apply to gas-fired and oil-fired
appliances. For gas-fired appliances see the Board of State Examiners of Plumbers and Gas
Fitters regulations at 248 CMR. For oil-fired appliances see 527 CMR 4.00: Oil Burning
Equipment. For electrical requirements see 527 CMR 12.00: Massachusetts Electrical Code
(Amendments). For fire prevention regulations 527 CMR governs, except where 527 CMR is
silent, in which case the International Fire Code requirements, as applicable, apply. Solid fuel-
burning appliances shall satisfy the manufacturer’s requirements, and in the absence of same, this
code shall apply.
2/4/11 780 CMR - Eighth Edition - 226
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
M2000 Add section:
M2000 General. The requirement of this chapter shall not apply to gas-fired and oil-fired
appliances. For gas-fired appliances see the Board of State Examiners of Plumbers and Gas
Fitters regulations at 248 CMR. For oil-fired appliances see 527 CMR 4.00: Oil Burning
Equipment. For electrical requirements see 527 CMR 12.00: Massachusetts Electrical Code
(Amendments). For fire prevention regulations 527 CMR governs, except where 527 CMR is
silent, in which case the International Fire Code requirements, as applicable, apply. Solid fuel-
burning appliances shall satisfy the manufacturer’s requirements, and in the absence of same, this
code shall apply. Additional requirements for boilers and other pressure vessels may be found
in M.G.L. c. 146 and the Board of Boiler Rules at 522 CMR, as applicable.
M2100 Add section:
M2100 General. The requirement of this chapter shall not apply to gas-fired and oil-fired
appliances. For gas-fired appliances see the Board of State Examiners of Plumbers and Gas
Fitters regulations at 248 CMR. For oil-fired appliances see 527 CMR 4.00: Oil Burning
Equipment. For electrical requirements see 527 CMR 12.00: Massachusetts Electrical Code
(Amendments). For fire prevention regulations 527 CMR governs, except where 527 CMR is
silent, in which case the International Fire Code requirements, as applicable, apply. Solid fuel-
burning appliances shall satisfy the manufacturer’s requirements, and in the absence of same, this
code shall apply. Additional requirements for boilers and other pressure vessels may be found
in M.G.L. c. 146 and the Board of Boiler Rules at 522 CMR, as applicable.
M2101.3 Replace ‘listed in Section P2902’ with ‘of the Department of Environmental Protection and/or the
local water purveyor, as applicable.’
M2201 through M2204 Replace in their entirety, as follows:
M2201 Special Piping and Storage Systems. Special laws and/or regulations impact
requirements for oil tanks, piping, fittings, connections, installation, and oil pumps and valves.
Refer to M.G.L. c. 148, § 13, M.G.L. c. 148, § 37, the Board of Fire Prevention Regulations
at 527 CMR, the Board of Boiler Rules at 522 CMR and EPA regulations (as well as this code
for tank structural design).
M2301.1 Add three notes as follows:
Notes:
1. Additional requirements for boilers and other pressure vessels may be found in M.G.L.
c. 146 and the Board of Boiler Rules at 522 CMR, as applicable.
2. Where solar thermal systems involve matters of potable water and/or wastewater see the
Board of State Examiners for Plumbers and Gas Fitters regulations at 248 CMR.
3. Photovoltaic systems shall be designed and installed in accordance all governing loading
conditions, fire protection, energy conservation and weatherization requirements dictated by
this code and the electrical requirements of 527 CMR 12.00: Massachusetts Electrical Code
(Amendments) and those of the manufacturer.
2400 Add section:
2400 General. Retain the sections listed in Table 2400. For all other requirements of this chapter see the
Board of State Examiners of Plumbers and Gas Fitters regulations at 248 CMR.
2/4/11 780 CMR - Eighth Edition - 227
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
TABLE 2400
G2404.6 (301.10) Wind resistance G2427.5.6.1 (503.5.7.1) Solid fuel-burning appliances
G2404.7 (301.11) Flood hazard G2427.5.6.3 (503.5.7.3) Combination gas- and solid
fuel-burning appliances
G2404.8 (301.12) Seismic resistance G2427.5.8 (503.5.9) Cleanouts
G2404.9 (301.14) Rodentproofing G2427.5.9 (503.5.10) Space surrounding lining or vent
G2405 Structural Safety G2427.6.3.1 (503.6.4.1) Decorative shrouds
G2408.2 (305.3) Elevation of ignition source G2427.7.5 (503.7.5) Roof penetrations
G2408.2.1 (305.3.1) Installation in residential garages G2427.10.13 (503.10.13) Fireplaces
G2408.3 (305.5) Private garages.G2427.16 (503.16) (IFGC) Outside wall penetrations
G2408.5 (305.8) Clearances to combustible construction G2430.2 (506.2) Support
G2415.1 (404.1) Prohibited locations G2439.2 (614.2) Duct penetrations
G2415.5 (404.5) Protection against physical damage G2439.5 (614.6) Domestic clothes dryer exhaust ducts
G2415.6 (404.6) Piping in solid floors G2439.5.2 (614.6.2) Duct installation
G2418.2 (407.2) Design and installation G2439.5.3 (614.6.3) Protection required
G2426.4 (502.4) Insulation shield
G2426.7 (502.7) Protection against physical damage
G2427.5.3 (503.5.4) Chimney termination
G2445 (621) Replace this section in its entirety as follows:
G2445.1 (621.1) General. Unvented gas-fired room heaters shall conform to the requirements
of 527 CMR 30.00: Unvented Propane or Natural Gas-fired Space Heaters.
G2452.1 (631.1) Add a last sentence as follows:
Additional requirements for boilers and other pressure vessels may be found in M.G.L. c. 146
and the Board of Boiler Rules at 522 CMR, as applicable.
P2501.1 Replace all subsections of this chapter as follows:
P2501.1 Scope. For plumbing requirements see 248 CMR 10.00: Uniform State Plumbing Code.
P2601.1 Replace as follows:
P2601.1 Scope. Retain the subsections listed in Table 2601.1. For all other requirements of this
chapter see 248 CMR 10.00: Uniform State Plumbing Code.
TABLE 2601.1
P2603.2 Drilling and notching P2604.1 Trenching and bedding
P2603.2.1 Protection against physical damage P2604.3 Backfilling
P2603.3 Breakage and corrosion P2604.4 Protection of footings
P2603.5 Pipes through footings or foundation walls P2606.1 General
P2701.1 Replace all subsections of this chapter as follows:
P2701.1 Scope. For plumbing fixture requirements see 248 CMR 10.00: Uniform State
Plumbing Code.
P2801.1 Replace as follows:
P2801.1 Scope. Retain the subsections listed in Table 2801.1. For all other requirements of this
chapter see 248 CMR 10.00: Uniform State Plumbing Code.
TABLE 2801.1
P2801.5 Required pan (if not in 248 CMR)P2801.7 Water heater seismic bracing.
P2801.6 Water heaters installed in garages.
2/4/11 780 CMR - Eighth Edition - 228
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
P2901.1 Replace all subsections of this chapter as follows:
P2901.1 Scope. For plumbing requirements for water supply and distribution see 248 CMR
10.00: Uniform State Plumbing Code. 310 CMR 22.00: Drinking Water and/or the local water
purveyor, as applicable, govern backflow protection requirements. Fire Sprinkler requirements
are found in Chapter 3.
P3001.1 Replace all subsections of this chapter as follows:
P3001.1 Scope. For municipal sewage disposal see 248 CMR 10.00: Uniform State Plumbing
Code and for private sewage disposal see 310 CMR 15.00: The State Environmental Code,
Title 5: Standard Requirements for the Siting, Construction, Inspection, Upgrade and
Expansion of On-site Sewage Treatment and Disposal Systems and for the Transport and
Disposal of Septage.
P3101.1 Replace all subsections of this chapter as follows:
P3101.1 General. For vent requirements see the Board of State Examiners of Plumbers and Gas
Fitters regulations at 248 CMR.
P3201.1 Replace all subsections of this chapter as follows:
P3201.1 General. For trap requirements see 248 CMR 10.00: Uniform State Plumbing Code.
P3301.1 Replace all subsections of this chapter as follows:
P3301.1 Scope. For storm drainage requirements see the applicable requirements of:
1. 248 CMR 10.00: Uniform State Plumbing Code,
2. Division of Water Pollution Control regulations at 314 CMR, and
3. Local municipal requirements.
E3401.1 Replace all subsections of this chapter as follows:
E3401.1 Applicability. Retain the subsections listed in Table 3401.1. For all other
requirements of this chapter see 527 CMR 12.00: Massachusetts Electrical Code (Amenrments).
TABLE 3401.1
E3402.1 Drilling and notching 3402.3 Penetrations of firestops and draftstops.
E3402.2 Penetrations of fire-resistance-rated assemblies
E3501.1 Replace all subsections of this chapter as follows:
E3501.1 Scope. For electrical definitions see 527 CMR 12.00: Massachusetts Electrical Code
(Amendments).
E3601.1 Replace all subsections of this chapter as follows:
E3601.1 Scope. For electrical services see 527 CMR 12.00: Massachusetts Electrical Code
(Amendments).
E3701.1 Replace all subsections of this chapter as follows:
E3701.1 Scope. For branch circuit and feeder requirements see 527 CMR 12.00: Massachusetts
Electrical Code (Amendments).
E3801.1 Replace all subsections of this chapter as follows:
E3801.1 Scope. Retain the table or subsections listed in Table 3801.1. For all other
requirements of this chapter see 527 CMR 12.00: Massachusetts Electrical Code (Amendments).
2/4/11 780 CMR - Eighth Edition - 229
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
TABLE 3801.1
E3802.2.1 Across structural members Table E3802.1: (Subjects which pertain to framing
or protection).
E3802.2.2 Cable installed through or parallel to framing
members
E3901.1 Replace all subsections of this chapter as follows:
E3901.1 General. For power and lighting distribution requirements see 527 CMR 12.00:
Massachusetts Electrical Code (Amendments).
4000 Add section:
4000 Scope. For devices and luminaires requirements see 527 CMR 12.00: Massachusetts
Electrical Code (Amendments).
E4101.1 Replace all subsections of this chapter as follows:
E4101.1 General. For appliance installation requirements see 527 CMR 12.00: Massachusetts
Electrical Code (Amendments).
E4201.1 At the end of this subsection add two sentences as follows:
For electrical requirements see 527 CMR 12.00: Massachusetts Electrical Code (Amendments).
For pool barrier and other pool safety requirements, see Appendix G.
E4301.1 Replace all subsections of this chapter as follows:
E4301.1 Scope. For Class 2 remote-control, signaling and power-limited circuit requirements
see 527 CMR 12.00: Massachusetts Electrical Code (Amendments).
CHAPTER 44 Add standards as follows:
NFPA 13R-07 Standard for the Installation of Sprinkler Systems in Residential Occupancies up
to and Including Four Stories in Height.
NFPA 720-09 Standard for the Installation of Carbon Monoxide (CO) Detection and Warning
Equipment
APPENDIX A -SIZING AND CAPACITIES OF GAS PIPING
A.0 Add section:
A.0 General. Delete all sections of this Appendix and for requirements see the Board of State
Examiners of Plumbers and Gas Fitters regulations at 248 CMR.
APPENDIX B -SIZING OF VENTING SYSTEMS SERVING APPLIANCES EQUIPPED WITH
DRAFT HOODS, CATEGORY 1 APPLIANCES, AND APPLIANCES LISTED
FOR USE WITH TYPE B VENTS
B.0 Add section:
B.0 General. Delete all sections of this Appendix and for requirements see the Board of State
Examiners of Plumbers and Gas Fitters regulations at 248 CMR.
APPENDIX C -EXIT TERMINALS OF MECHANICAL DRAFT AND DIRECT-VENT
VENTING SYSTEMS
C.0 Add section:
C.0 General. Exit terminals of gas-fired mechanical draft and direct-vent venting systems shall
conform to the applicable requirements of the Board of State Examiners of Plumbers and Gas
Fitters regulations at 248 CMR.
2/4/11 780 CMR - Eighth Edition - 230
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
Exit terminals of oil-fired mechanical draft and direct-vent venting systems shall conform
to the applicable requirements of 527 CMR 4.00: Oil Burning Equipment or, in the absence of
such guidance, shall conform to the criteria of Figure C-1, or the equipment manufacturer’s
requirements, whichever are more stringent.
Exit terminals of solid fuel-burning mechanical draft and direct-vent venting systems shall
conform to the applicable requirements of Figure C-1, or the equipment manufacturer’s
requirements, whichever are more stringent.
APPENDIX D -RECOMMENDED PROCEDURE FOR SAFETY INSPECTION OF AN
EXISTING APPLIANCE INSTALLATION: Reserved.
APPENDIX E -MANUFACTURED HOUSING USED AS DWELLINGS
AE101.1 Add a note as follows:
Note. Construction, installation, addition, repair or maintenance of building systems that fall
under that authority of the specialized codes shall be overridden by and shall conform to
applicable specialized code(s) requirements.
AE102.2 Replace subsections 1., 2., and 3. as follows:
1. Be designed and constructed in conformance with this code and the applicable specialized
codes.
AE301 to AE304 Replace as follows:
AE301.1 Permits and Fees. For permit requirements see Chapter 1. Refer to local municipality
for permit fees.
AE305 Replace as follows:
AE305.1 General. For inspection requirements see Chapter 1.
AE507.1 Replace as follows:
AE507.1 General. Alterations made to a manufactured home subsequent to its initial
installation shall conform to the occupancy, fire-safety and energy conservation requirements of
this code.
APPENDIX F -RADON CONTROL METHODS: Reserved.
APPENDIX G -SWIMMING POOLS, SPAS AND HOT TUBS
AG101.1 Add the following Notes:
Notes:
1. Public and semi-public outdoor in-ground swimming pool enclosures shall conform to the
requirements of M.G.L. c. 140, § 206.
2. Also see 521 CMR 19.00: Recreational Facilities.
3. Also see 105 CMR 430.00: Minimum Standards for Recreational Camps for Children (State
Sanitary Code, Chapter IV) and 435.00: Minimum Standards for Swimming Pools (State
Samitary Code: Chapter V) as such regulate swimming pool requirements.
4. Installation of electrical wiring and electrical devices shall be in accordance with 527 CMR
12.00: Massachusetts Electrical Code (Amendments).
5. Installation of gas-fired pool heaters shall be in accordance with the Board of State
Examiners of Plumber and Gas Fitters regulations at 248 CMR.
APPENDIX H - PATIO COVERS
Massachusetts adopts this Appendix without amendment.
2/4/11 780 CMR - Eighth Edition - 231
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
APPENDIX I -PRIVATE SEWAGE DISPOSAL
A1101.1 Replace as follows:
AI101.1 Scope. Private sewage disposal systems shall conform to the requirements of 310 CMR
15.00: The State Environmental Code, Title 5: Standard Requirements for the Siting,
Construction, Inspection, Upgrade and Expansion of On-site Sewage Treatment and Disposal
Systems and for the Transport and Disposal of Septage and any additional legal restrictions
imposed by the municipal Health Department
APPENDIX J -EXISTING BUILDINGS AND STRUCTURES
AJ101.1 Add a second paragraph, exception, and two notes as follows:
Features of existing construction which do not meet the requirements of this code for new
construction shall be presumed to have met the regulations, codes or laws in effect at the time
of construction or alteration and, if so, shall be deemed to be existing nonconforming. Unless
stated otherwise, nothing in this chapter shall require the upgrading or replacement of any
existing nonconforming features or component of an existing building, provided the feature(s)
or components or systems are in a serviceable condition unless the building official determines
that an unsafe or dangerous condition would exist, in which case he shall order the remediation
of such condition. Nor shall this chapter be deemed to require the replacement or upgrading of
serviceable components which are not included in the scope of work for which a permit is
applied unless expressly required by this code, or unless the building official determines that an
unsafe or dangerous condition would result.
Exception. Existing components or features of an existing building which, in the opinion
of the building official, are dangerous, unsafe, unserviceable or demonstrate damage or
significant deterioration or which otherwise present a threat to the occupants or to the public
safety shall be remediated in accordance with the applicable sections of this code.
Note 1. Any new building system or portion thereof shall conform to 780 CMR for new
construction to the fullest extent practicable. However, individual components of an existing
building system may be repaired or replaced without requiring that system to comply fully with
the code for new construction unless specifically required by this appendix.
Note 2. For existing buildings and structures conformance to requirements of the Specialized
Codes refer to the applicable Specialized Codes.
AJ101.1.1 Add subsection:
AJ101.1.1 Buildings Which Qualify. A building erected prior to the date of adoption of
the appropriate code, or one for which a legal building permit has been issued.
Note. Existing townhouse buildings regulated by this code shall also conform to the
seismic requirements of this code.
AJ102.1 Replace the phrase “mechanical or plumbing system” with “system controlled by this code”
AJ102.3 Replace as follows:
AJ102.3 Smoke, Heat, Carbon Monoxide Detection and Alarm Systems. When one or more
sleeping rooms are added or created in existing dwellings, the entire existing dwelling shall be
provided with smoke detectors, heat detector and carbon monoxide detectors designed, located
and installed in accordance with the provisions for new construction, as applicable. If a garage
is created under an existing dwelling or attached to an existing dwelling, a heat detector,
conforming to the requirements of the code for new construction shall be installed in the garage;
such requirement is not applicable for detached garages (see Chapter 3).
If the dwelling undergoes complete reconstruction such that all walls and ceilings are open
to framing, then the entire existing building shall be provided with smoke detectors, heat detector
and carbon monoxide detectors designed, located and installed in accordance with the provisions
for new construction.
2/4/11 780 CMR - Eighth Edition - 232
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
In an existing two-family dwelling, if one or more sleeping rooms are added or created in
only one of the two dwelling units, the dwelling unit acquiring new sleeping rooms shall be
provided with smoke detectors, heat detector and carbon monoxide detectors, as applicable,
designed, located and installed in accordance with the provisions for new construction.
In an existing two-family dwelling, if, during a repair/reconstruction event, one or more
sleeping rooms are added or created in both of the two dwelling units, the entire building shall
be provided with smoke detectors, heat detector and carbon monoxide detectors, as applicable,
designed, located and installed in accordance with the provisions for new construction for two-
family dwellings.
Note 1. It is the intention of this code to require that all required smoke alarms and required
CO alarms be interconnected by hard-wire methods or acceptable wireless methods per the
interconnection requirements of NFPA 72; additionally, required heat detectors are either to
activate sounders or be compatible with the smoke alarm system so that heat activation of
the heat detector operates a sounder or the smoke alarms of all interconnected smoke alarms
sound if heat is detected by the interconnected heat detector. Where combination smoke/CO
alarms are utilized, such are to be interconnected and fire alarm signals have precedence over
CO alarm in accordance with the requirements of NFPA 720.
Note 2. CO detector requirements for existing R-uses are also governed by 527 CMR 31.00:
Carbon Monoxide Alarms and the Board of State Examiners of Plumbers and Gas Fitters at
248 CMR.
AJ102.7.1 Add subsection:
AJ102.7.1 Documentation of Compliance Alternatives. The building official shall ensure that
the BBRS is provided with information regarding the compliance alternatives accepted by the
building official.
AJ102.10 Add subsection:
AJ102.10 Unlined Chimneys. Where new HVAC appliances are connected to an unlined
chimney, the chimney lining requirements of the Board of State Examiners of Plumbers and Gas
Fitters regulations at 248 CMR or the Board of Fire Prevention regulations at 527 CMR, as
applicable, and those of the appliance manufacturer shall be satisfied. If the appliance is a solid
fuel-burning appliance, the chimney shall be relined to satisfy requirements both of the code for
new construction and those of the manufacturer, as applicable.
AJ102.11 Add subsection:
AJ102.11 Latent Conditions. When latent conditions are observed and which are determined
by the licensed construction supervisor, the owner or the building official to be dangerous or
unsafe, or when a component or system is determined to be unserviceable, said conditions shall
be corrected in accordance with applicable provisions of this code. A building permit shall be
obtained or the building permit shall be amended in accordance with the provisions of Section
R105 in order to reflect the necessary required work and the approval shall be obtained from the
building official prior to commencement of the corrections.
Exception. If the public safety so warrants, the building permittable corrective actions are
permitted to be made prior to amending the building permit application, providing that the
building official is notified in writing within 24 hours of actions taken pursuant to this
exception. This exception shall not be construed as to authorize constructive approval nor
set aside the requirements to amend the permit application, nor shall the authority of the
building official to enforce this code be abridged. Such corrective actions shall be
documented by the construction supervisor or the owner and submitted to the building
official within 48 hours of the completion of the action under this exception. Such corrective
work shall not be concealed until the building official has inspected and approved the work.
2/4/11 780 CMR - Eighth Edition - 233
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
AJ102.12 Add subsection:
AJ102.12 Existing non Conforming Means of Egress. The following conditions, when
observed by the building official, and believed shall be cited, in writing as a violation. Said
citation shall order the abatement of the non conformance and shall include such a time element
as the building official deems necessary for the protection of the occupants thereof, or as
otherwise provided for by statute.
1. Less than the number of means of egress serving every space and/or story, required by
this code.
2. Any required means of egress component which is not of sufficient width to comply with
the code for new construction, or is not so arranged as to provide safe and adequate means
of egress.
AJ102.13 Add subsection:
AJ102.13 Hazardous Means of Egress. In any existing building or structure not provided with
exit facilities as herein prescribed for new buildings and in which the exits are deemed hazardous
or dangerous to life and limb, the building official shall declare such building dangerous and
unsafe in accordance with the provisions of Section R115.1.
AJ102.14 Add subsection:
AJ102.14 Roofing and Reroofing. See Chapter 9 generally and Section R907.
AJ102.15 Add subsection:
AJ102.15 Additions. New construction additions shall comply with all requirements of the code
for new construction.
AJ102.16 Add subsection:
AJ102.16 Accessibility for Persons with Disabilities. Accessibility requirements shall be in
accordance with 521 CMR.
AJ103.1 Replace “designee shall” with “legal designee may”
AJ301.1.2 Delete.
AJ301.2 Delete.
AJ301.4 Delete.
AJ401.2.1 Add subsection:
AJ401.2.1 Emergency Egress Windows. For one- and two-family dwellings and townhouses
of no more than three stories in height, all emergency escape windows from sleeping rooms shall
have a net clear opening of 3.3 square feet (0.307 m ). The minimum net clear opening shall be2
20 inches by 24 inches (508 mm by 610 mm) in either direction except that windows in sleeping
rooms of existing dwellings which do not conform to these requirements may be replaced
without conforming to these dimensional requirements, provided that the windows do not
significantly reduce the existing opening size.
Exception. Replacement windows utilized as emergency egress windows, other than
double-hung windows, shall generally conform to the requirements of this section without
conforming to the cited dimensional requirements, provided that such replacement windows
do not significantly reduce the existing opening size.
2/4/11 780 CMR - Eighth Edition - 234
780 CMR: STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
51.00: continued
AJ401.4 Replace as follows:
AJ401.4 Structural. Unreinforced masonry townhouse buildings shall have parapet bracing and
wall anchors installed at the roofline whenever a reroofing permit is issued if required by
780 CMR 34.00: Existing Structures. Such parapet bracing and wall anchors shall be of an
approved design. Where renovations may decrease the structural performance of the existing
building, such proposed activities shall be evaluated by a registered design professional for
adequacy, prior to such actual structural renovation.
AJ501.4 Add a final sentence as follows:
“Where alterations may decrease the structural performance of the existing building, such
proposed activities shall be evaluated by a registered design professional for adequacy, prior to
such actual structural alterations”.
AJ501.5 Replace this subsection in its entirety as follows:
AJ501.5 Electrical Equipment and Wiring. See 527 CMR 12.00: Massachusetts Electrical
Code (Amendments).
AJ601.5. Add subsection:
AJ601.5 Structural. Where reconstruction may decrease the structural performance of the
existing building, such proposed activities shall be evaluated by a registered design professional
for adequacy, prior to such actual structural reconstruction.
AJ701 Add section:
SECTION AJ701
HISTORIC BUILDINGS
AJ701.1 General. For historic building requirements see 780 CMR 34.00: Existing Buildings.
APPENDIX K -SOUND TRANSMISSION
Massachusetts adopts this Appendix without amendment.
APPENDIX L - PERMIT FEES
Massachusetts does not adopt this Appendix. See 801 CMR 4.00: Rates, as applicable.
APPENDIX M - HOME DAY CARE -- R-3 OCCUPANCY
Delete
APPENDIX N - VENTING METHODS
Delete.
APPENDIX O -GRAY WATER RECYCLING SYSTEMS: Reserved.
APPENDIX P -SIZING OF WATER PIPING SYSTEM
Delete.
APPENDIX Q -ICC INTERNATIONAL RE S ID ENTIAL CO D E E LECT R I CAL
PROVISIONS/NATIONAL ELECTRICAL CODE CROSS-REFERENCE
Delete.