5 Pomeroy Fire Alarm 2017-05-11Total Service to Industry
975 North Road
Westfield, MA 01085
Design Narrative Report-5 Pomeroy Terrace Corner House Shaw Hotel
Scope of Services:
The fire alarm system will provide addressable fire detection and control throughout the building,
Series main control panel.
The fire alarm system will provide building
The smoke/CO detectors in the apartments will be a supervisory signal upon activation; the heat detectors with be an alarm
upon activation.
The sounder bases will activate locally to each apartment upon local smoke/Co detectors. The heat dete
sounder bases and horn/strobe throughout the building.
The common area pull stations and smoke detectors will activate all sounder bases and horn/strobes throughout the
building.
The sounder bases in the bedrooms will be low frequ
The fire alarm system will communicate all alarm, supervisory, and trouble signals through a 3
that will notify the fire department of any alarm
System Description:
Alarm initiation will be accomplished by any of the following;
• Pull stations located at all exit’s and entrances.
• Smoke detectors at the following locations:
o Bedrooms
o At the fire alarm control panel, and power supply location.
o Common hallways
o Basement
o Outside bedrooms
• Heat detectors in kitchens
• Waterflow switches on the automatic sprinkler system.
Supervisory signal initiation will be accomplished by any of the following:
• Tamper switches on the automatic sprinkler system control valve.
• Co detectors in bedrooms and outside bedrooms
Standards and Codes:
• Building Code of Massachusetts,
• Existing Building Code of Massachusetts,
• Mechanical Code of Massachusetts,
• Fire Code of Massachusetts, 2009
• NFPA 70-National Electrical Code, 2011 Edition
• NFPA-72 National Fire Alarm Code, 2010 Edition
• NFPA-101-Life Safety Code, 2012 Edition
E-Mail colin@its-control.com
Website www.its-control.com
5 Pomeroy Terrace Corner House Shaw Hotel Fire Alarm Installation.
The fire alarm system will provide addressable fire detection and control throughout the building, using the Gam
The fire alarm system will provide building-wide notification that is zoned in accordance with all initiating devices.
The smoke/CO detectors in the apartments will be a supervisory signal upon activation; the heat detectors with be an alarm
The sounder bases will activate locally to each apartment upon local smoke/Co detectors. The heat dete
sounder bases and horn/strobe throughout the building.
The common area pull stations and smoke detectors will activate all sounder bases and horn/strobes throughout the
The sounder bases in the bedrooms will be low frequency type.
The fire alarm system will communicate all alarm, supervisory, and trouble signals through a 3rd party monitoring company
that will notify the fire department of any alarm condition, supervisory and trouble signals.
initiation will be accomplished by any of the following;
Pull stations located at all exit’s and entrances.
Smoke detectors at the following locations:
At the fire alarm control panel, and power supply location.
Waterflow switches on the automatic sprinkler system.
Supervisory signal initiation will be accomplished by any of the following:
Tamper switches on the automatic sprinkler system control valve.
bedrooms and outside bedrooms
Building Code of Massachusetts, 2009 Edition
Existing Building Code of Massachusetts, 2009 Edition
Mechanical Code of Massachusetts, 2009 Edition
2009 Edition
ional Electrical Code, 2011 Edition
72 National Fire Alarm Code, 2010 Edition
Life Safety Code, 2012 Edition
Telephone 413-568-1427
Fax 413-568-4573
using the Gamewell S3
ng devices.
The smoke/CO detectors in the apartments will be a supervisory signal upon activation; the heat detectors with be an alarm
The sounder bases will activate locally to each apartment upon local smoke/Co detectors. The heat detectors will activate all
The common area pull stations and smoke detectors will activate all sounder bases and horn/strobes throughout the
party monitoring company