SECTION 086200 -UNIT SKYLIGHTS
PART 1 -GENERAL
1.1 RELATED DOCUMENTS
A.Drawings and general provisions of the Contract, including General and
Supplementary Conditions and Division 01 Specification Sections, apply to this
Section.
1.2 SUMMARY
A.Section Includes:
1.Self-flashing unit skylights with integral curb.
B.Related Sections:
1.Division 06 Section " Miscellaneous Rough Carpentry" for wood framing and
blocking at unit skylights.
1.3 SUBMITTALS
A.Product Data: For each type of unit skylight indicated. Include construction details,
material descriptions, dimensions of individual components and profiles, and finishes
for unit skylights.
B.Shop Drawings: For unit skylight work. Include plans, elevations, sections, details,
and connections to supporting structure and other adjoining work.
C.Product Test Reports: Based on evaluation of comprehensive tests performed by a
qualified testing agency for each type and size of unit skylight.
D.Field quality-control reports.
E.Maintenance Data: For unit skylights to include in maintenance manuals.
F.Warranty: Sample of special warranty.
1.4 QUALITY ASSURANCE
A.Manufacturer Qualifications: A manufacturer capable of fabricating unit skylights that
meet or exceed performance requirements indicated and of documenting this
performance by inclusion in lists and by labels, test reports, and calculations.
Roofing Replacement May 14, 2015
South Street Apartments
086200 UNIT SKYLIGHTS
Page 2 of 6
B.Installer Qualifications: An installer acceptable to unit skylight manufacturer for
installation of units required for this Project.
C.Source Limitations: Obtain unit skylights from single source from single manufacturer.
D.Surface-Burning Characteristics of Plastic Glazing: Provide plastic glazing sheets
identical to those tested for fire-exposure behavior per test method indicated below by
a testing and inspecting agency acceptable to authorities having jurisdiction. Identify
materials with appropriate markings of applicable testing and inspecting agency.
1.Self-Ignition Temperature: 650 deg F (343 deg C)or more for plastic sheets in
thickness indicated when tested per ASTM D 1929.
2.Smoke-Production Characteristics: Comply with either requirement below:
a.Smoke-Developed Index: 450 or less when tested per ASTM E 84 on
plastic sheets in manner indicated for use.
b.Smoke Density: 75 or less when tested per ASTM D 2843 on plastic
sheets in thickness indicated for use.
3.Burning Characteristics: Tested per ASTM D 635.
a.Acrylic Glazing: Class CC2, burning rate of 2-1/2 inches (64 mm)per
minute or less for nominal thickness of 0.060 inch (1.5 mm)or thickness
indicated for use.
b.Polycarbonate Glazing: Class CC1, burning extent of 1 inch (25 mm)or
less for nominal thickness of 0.060 inch (1.5 mm)or thickness indicated for
use.
c.Polycarbonate-Insulating-Panel Glazing: Class CC2, burning rate of 2-1/2
inches (64 mm)per minute or less for nominal thickness of 0.060 inch (1.5
mm)or thickness indicated for use.
E.Unit Skylight Standard: Comply with AAMA/WDMA 101/I.S.2/NAFS, "North American
Fenestration Standard Voluntary Performance Specification for Windows, Skylights
and Glass Doors," for minimum standards of performance, materials, components,
accessories, and fabrication. Comply with more stringent requirements if indicated.
F.Structural Loads: Comply with requirements of AAMA publication, “Voluntary Uniform
Structural Load Standard for Plastic Domed Skylights” (AAMA 1606-82) requiring
acrylic sheets of adequate thickness to withstand positive or negative test pressure of
60 PSF.
1.5 COORDINATION
A.Coordinate unit skylight flashing requirements with roofing system.
B.Provide anchors and inserts to be placed in adjacent construction in proper sequence
so as not to delay the Work.
Roofing Replacement May 14, 2015
South Street Apartments
086200 UNIT SKYLIGHTS
Page 3 of 6
1.6 WARRANTY
A.Special Warranty: Manufacturer's standard form in which manufacturer agrees to
repair or replace components of unit skylights that fail in materials or workmanship
within specified warranty period.
1.Failures include, but are not limited to, the following:
a.Uncontrolled water leakage.
b.Deterioration of metals, metal finishes, and other materials beyond normal
weathering.
c.Breakage of polycarbonate glazing.
d.Deterioration of insulating-glass hermetic seal.
2.Warranty Period: Five years from date of Substantial Completion.
PART 2 -PRODUCTS
2.1 MANUFACTURERS
A.Basis-of-Design Product: Subject to compliance with requirements, provide Wasco
Products, Inc.;DDAP3 Model 2828 or comparable product by one of the following:
1.American Skylites.
2.Bristolite Skylights.
3.Naturalite Skylight Systems; Vistawall Group (The).
2.2 MATERIALS
A.Aluminum Components:
1.Sheets: ASTM B 209 (ASTM B 209M), alloy and temper to suit forming
operations and finish requirements but with not less than the strength and
durability of alclad Alloy 3005-H25.
2.Extruded Shapes: ASTM B 221 (ASTM B 221M), alloy and temper to suit
structural and finish requirements but with not less than the strength and
durability of Alloy 6063-T52.
B.Fasteners: Same metal as metal being fastened, nonmagnetic stainless steel, or other
noncorrosive metal as recommended by manufacturer. Finish exposed fasteners to
match material being fastened.
1.Where removal of exterior exposed fasteners might allow access to building,
provide nonremovable fastener heads.
Roofing Replacement May 14, 2015
South Street Apartments
086200 UNIT SKYLIGHTS
Page 4 of 6
2.3 GLAZING
A.Polycarbonate Glazing: Thermoformable, extruded monolithic sheets, UV resistant,
burglar-resistance rated per UL 972, and with average impact strength of 12 to 16 ft-
lb/in.(640 to 854 J/m)of width when tested per ASTM D 256, Test Method A (Izod).
1.Double-Glazing Profile: Dome, 25 percent rise.
a.Thicknesses: Not less than thicknesses required to exceed performance
requirements.
b.Inner Glazing Color: Transparent.
c.Outer Glazing Color: Transparent.
B.Glazing Gaskets: Manufacturer's standard.
2.4 INSTALLATION MATERIALS
A.Joint Sealants: As specified in Division 07 Section "Joint Sealants."
B.Mastic Sealant: Polyisobutylene; nonhardening, nonskinning, nondrying, nonmigrating
sealant.
2.5 UNIT SKYLIGHTS
A.General: Provide factory-assembled unit skylights that include glazing, extruded-
aluminum glazing retainers, gaskets, and inner frames and that are capable of
withstanding performance requirements indicated.
B.Integral Curb: Extruded-aluminum, self-flashing type.
1.Height: 9 inches (225 mm).
2.Construction: Double wall.
3.Insulation: Manufacturer's standard rigid or semirigid type.
C.Unit Shape and Size: Square, 25-by-25-inch (1016-by-1016-mm)outside curb.
D.Condensation Control: Fabricate unit skylights with integral internal gutters and
nonclogging weeps to collect and drain condensation to the exterior.
E.Thermal Break: Fabricate unit skylights with thermal barrier separating exterior and
interior metal framing.
2.6 GENERAL FINISH REQUIREMENTS
A.Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products"
for recommendations for applying and designating finishes.
Roofing Replacement May 14, 2015
South Street Apartments
086200 UNIT SKYLIGHTS
Page 5 of 6
B.Appearance of Finished Work: Noticeable variations in same piece are not acceptable.
Variations in appearance of adjoining components are acceptable if they are within the
range of approved Samples and are assembled or installed to minimize contrast.
2.7 ALUMINUM FINISHES
A.Mill Finish: Manufacturer's standard.
PART 3 -EXECUTION
3.1 EXAMINATION
A.Examine openings, substrates, structural support, anchorage, and conditions, with
Installer present, for compliance with requirements for installation tolerances and other
conditions affecting performance of the Work.
B.Proceed with unit skylight installation only after unsatisfactory conditions have been
corrected.
3.2 INSTALLATION
A.Coordinate installation of unit skylight with installation of substrates, vapor retarders,
roof insulation, roofing membrane, and flashing as required to ensure that each
element of the Work performs properly and that combined elements are waterproof and
weathertight.
B.Comply with recommendations in AAMA 1607 and with manufacturer's written
instructions for installing unit skylights.
C.Install unit skylights level, plumb, and true to line, without distortion.
D.Anchor unit skylights securely to supporting substrates.
E.Where metal surfaces of unit skylights will contact incompatible metal or corrosive
substrates, including preservative-treated wood, apply bituminous coating on
concealed metal surfaces, or provide other permanent separation recommended in
writing by unit skylight manufacturer.
F.Set unit skylight flanges in thick bed of roofing cement to form a seal unless otherwise
indicated.
G.Where cap flashing is indicated, install to produce waterproof overlap with roofing or
roof flashing. Seal with thick bead of mastic sealant except where overlap is indicated
to be left open for ventilation.
Roofing Replacement May 14, 2015
South Street Apartments
086200 UNIT SKYLIGHTS
Page 6 of 6
3.3 FIELD QUALITY CONTROL
A.After completion of installation and nominal curing of sealant and glazing compounds
but before installation of interior finishes, test for water leaks according to AAMA 501.2.
B.Perform test for total area of each unit skylight.
C.Work will be considered defective if it does not pass tests and inspections.
D.Additional testing and inspections, at Contractor's expense, will be performed to
determine compliance of replaced or additional work with specified requirements.
3.4 CLEANING
A.Clean exposed unit skylight surfaces according to manufacturer's written instructions.
Touch up damaged metal coatings and finishes.
B.Remove excess sealants, glazing materials, dirt, and other substances.
C.Remove and replace glazing that has been broken, chipped, cracked, abraded, or
damaged during construction period.
D.Protect unit skylight surfaces from contact with contaminating substances resulting
from construction operations.
END OF SECTION 086200