1. Introduction
Hazardous material sampling and analysis was conducted at the RK Finn School in
Northampton, MA to support designer services for a roof replacement. The objective was
to inspect constructs, finishes and materials that may be affected by the project and may
contain asbestos. All materials, which were to be disturbed by future renovation, were
inspected.
2. Sampling
Kenneth Menzies, PEER Consultants (MA Inspector License AI052108) surveyed the
suspect asbestos containing building materials (ACBM) on October 17, 2014. Locations
were selected with the guidance of Raymond Design Associates, Inc. (RDA) design
engineers to facilitate the sampling of suspect building materials that will be disturbed by
the future roof replacement. Therefore, all suspect hazardous building materials in the
building were not necessarily sampled. Multiple samples of suspect materials were
collected to meet the requirements of EPA and OSHA regulations.
Suspect ACBM, which were identified, included roofing materials and roof penetration
sealants. Samples were labeled, and appropriate chain-of-custody documentation was
completed. The ACBM bulk samples were sent to AMA Analytical Services Inc. for
laboratory analysis.
3. Analysis
Bulk asbestos samples were analyzed using Polarized Light Microscopy (PLM) coupled
with dispersion staining in accordance with the Environmental Protection Agency's
(EPA) "Method for the Determination of Asbestos in Bulk Building Materials"
(EPA/600/R-93/116, July 1993). AMA is accredited under the National Institute of
Standards and Technology (NIST), National Voluntary Laboratory Accreditation
Program (NVLAP), American Industrial Hygiene Association (AIHA), and the
Commonwealth of Massachusetts (DOS).
4. Findings
Visual inspection of selected materials indicated the presence of suspect asbestos
containing building materials (ACBM) including roofing materials and roof sealants.
The ACBM analytical data is provided in Appendix A. Samples are identified on a
sample log (Appendix A). A summary of the ACBM results is provided in Table 1. An
ACBM contains more than 1% asbestos and is regulated by the EPA and OSHA.
PEER Consultants Page 2 11/13/2014
rda northampton rk finn asbestos inspection 2014-10-31.docx
Table 1
Suspect ACBM on Northampton RK Finn School Roof
Location Item Material Sample ID Asbestos
(%)
Main Roof Edge Flashing Sealant S1-1,2 NAD
Wall Flashing Sealant S2-1,2 NAD
Vent Sealant S3-1,2 NAD
Wall Flashing
Screw
Sealant S4-1,2 NAD
Duct Vent Sealant S5-1,2 NAD
Exterior Wall Control Joint Sealant, hard white S6-1,2 NAD
Sealant, soft white S7-1,2 NAD
Sealant, black S8-1,2 NAD
Interior Main Hall Ceiling Drain Bowl
Insulation
D1-1,2 30
Interior Addition
Hall
Ceiling Drain Bowl
Insulation
D2-1,2 NAD
Interior Entry Ceiling Plaster C1-1,2 NAD
Roof (Test Cut 1) Edge Membrane RK1-A NAD
Fiberboard RK1-B NAD
Fiberboard Paper RK1-C NAD
Isocyanurate RK1-D NAD
Iso Paper RK1-E NAD
Asphalt RK1-F NAD
Concrete RK1-G NAD
Roof (Test Cut 2) Wall Membrane RK2-A NAD
Fiberboard RK2-B NAD
Fiberboard Paper RK2-C NAD
Fiberboard Asphalt RK2-D NAD
Isocyanurate RK2-E NAD
Iso Paper RK2-F NAD
Roof (Test Cut 4) Expansion Joint Membrane, black RK4-A NAD
Fiberboard RK4-B NAD
Asphalt RK4-C NAD
Roof (Test Cut 6) Upper Roof
Edge
Membrane RK6-A NAD
Fiberboard RK6-B NAD
Fiberboard Paper RK6-C NAD
Isocyanurate RK6-D NAD
Iso Paper RK6-E NAD
BUR RK6-F NAD
Fiberboard RK6-G NAD
Interior Hall Ceiling Ceiling Tile -- Known
Negative
PEER Consultants Page 3 11/13/2014
rda northampton rk finn asbestos inspection 2014-10-31.docx
Notes: NAD=No Asbestos Detected
TR=Trace of asbestos (<1%)
NA=Not analyzed
5. Conclusions
Asbestos was found only in the Drain Bowl Insulation present in the Main School and not
in the Addition. No asbestos was found in the roofing materials or sealants.