23A-281 (16) MAIN DRAIN TEST System starting supply static pressure reading? 13.2.5.1 85 System residual pressure reading? 13.2.5.1 70 System static pressure reading after drain test? 13.2.5.1 80 System main drain test results within 10%of previously performed test? 13.2.5.2 Y FIRE DEPARTMENT CONNECTIONS Are FDC visible and accessible? 13.7.1 Y Are FDC couplings or swivels free of damage and rotate smoothly? 13.7.1 Y Are FDC plugs or caps in place and free of damage? 13.7.1 Y Are FDC gaskets in place and in good condition? 13.7.1 Y Are FDC identification signs in place? 13.7.1 Y Are FDC checks free of leakage? 13.7.1 Y Are FDC automatic drain/ball drips in place and operating properly? 13.7.1 Y Are FDC clappers in place and operating properly? 13.7.1 Y NFPA 25 00• Y/N Y=Satisfactory N=Unsatisfactory N/A=Not Applicable, Readings=PSI NA SYSTEM RISER/CHECK VALVES System water gauge reading. 13.4.1.1 85 System supply gauge indicating normal supply water pressure is being maintained? 13.4.1.1 Y Valves free of physical damage? 13.4.1.1 Y The retard chamber or alarm drains are not leaking? 13.4.1.1 Y NFPA 25 2008 Requirements Y=Satisfactory N=Unsatisfactory N/A=Not Applicable CONTROL VALVES 13.3.2.2 Location Area Controlled Size Type Sign Secured Leak Free Open Accessible Sprinkler closet Supply DCVA 1.5" Ball Y Y Y Y Sprinkler closet Discharge DCVA 1.5" Ball Y Y Y Y Deficiencies per NFPA 25: Impairments: None Critical: 1) Sprinkler heads are covered with factory protective cases that obstruct the spray pattern of the sprinkler head; building still under construction. Need to remove covers and install escutcheons. Noncritical: 1) No signs/identification for the control valves, drains, or inspector's test valve. Recommendations/Notes: 1) Partially sprinkled building 2nd floor only (Units A, B, &Q. Inn er+uic112 r OUP PO Box 1244,Belchertown,MA 01007 Phone:413-668-9100 Fax: 413-213-6567 www.fireservicegroup.com -2- Ire eruice r+oup Fire Protection Testing&Maintenance Provider 1240 Park Street Palmer, MA 01069 MA License#SC 145974 PO Box 1244 Belche/town, MA 01007 CT License#FRP 0041132-F1 225 Nonotuck Street Inspection Date: 4/11/14 Florence, MA Performed By: Michael Haluch Annual Fire Sprinkler Inspection Report: Page 1 of 2 NFPA 25 00: Edition 5 Year Requirements Y/N Y=Satisfactory N=Unsatisfactory N/A=Not Applicable NA ENTIRE SYSTEM Gauges been checked for proper calibration or have been replaced within the last(5)years?5.3.2 Y Check valves been internally inspected within the last(5) years? 12.4.2.1 Y Strainers, filters, restricted orifices, and diaphragm chambers been internal inspected within (5)years? 13.4.3.1.8 Y NFPA 25 00: -. p Y=Satisfactory N=Unsatisfactory N/A=Not Applicable BUILDING Adequate heat in areas with wet piping?5.2.5 Y PIPING AND FITTINGS Is piping and fittings in good condition and free of mechanical damage, leakage, or corrosion?5.2.2.1 Y Is piping free of external loads? 5.2.2.2 Y HANGERS AND SEISMIC BRACES Are visible pipe hangers and seismic braces not damaged or loose?5.2.3.1 Y SPRINKLERS Are sprinklers free of signs of leakage, corrosion, foreign materials, paint, physical damage and install in the proper Y orientation?5.2.1.1.1 Is the proper clearance maintained between the sprinkler deflector and obstructions? 5.2.1.2 Y Are sprinklers of proper age and not required to be sample tested or replaced?5.3.1.1 Y CONTROL VALVES Were all valves operated through its full range and returned to its normal position? 13.3.3.1 Y NFPA 25 2008 Edition Quarterly Requirements Y/N Y=Satisfactory N=Unsatisfactory N/A=Not Applicable NA ALARM DEVICES Are all alarm devices free of physical damage?5.2.6 Y Do local alarm devices(water motor gong, electric bell) operate? 5.3.3.1 Y Do vane type and pressure switch type flow switches initiate a signal? 5.3.3.2 (Semi-annually) Y Do the water flow alarm devices on the wet system(s)activate via inspectors test connection?5.3.3.3 Y 1-888-279-8590 Tel: 413-668-9100 Fax: 413-213-6567 www. 1r(2 QrU1CQ rOUP.com n NFPA' �. ... O W y AG W A � n CA O '� Cr4 •D .•. fD ?), n U) m O m QO o C9 A m O � � O rt � � �• ^ � f�D n. y A rt O CL Lo tD O f1 N y ` n CD 8D �. N CA (D m ro tti0 p UO rD rD CD n CD tt '.�. y � ° L N L. J � n `n 0 o O rt ~ N y CD _ /}� (� n —• rt fD O `y y c (D O rt N• Cp cno rt N b A rD M /. CD O Cr4 n n CD rAt `D M �. A Z• CD rt •; CV CD CD rD rD ro CD " O CD ft rD z O lD �Q CD c0 CD rD L D � O ,•-r f1. �D• rQ rQ A CD rt p G Op I n N CD (D n .n W y � � 1-10 - _. A� CAD ro N .. a• rD O 00 0 0 A Z 'i 3f W