35-069 (2) Florence 2
KeyBeam Florence 10:
KeyBeam®4.600d
lanBeamEngine 4.6026
Materials Database 1472
Member Data
Description: Member Type: Beam Application: Floor
Top Lateral Bracing: Continuous
Bottom Lateral Bracing:Continuous
Standard Load: Moisture Condition: Dry Building Code: IBC/IRC
Live Load: 40 PLF Deflection Criteria: U360 live, U240 total 1.250"max. LL
Dead Load: 10 PLF Deck Connection: Nailed Member Weight: 9.4 PLF
Filename: KYB1
Other Loads
Type Trib. Other Dead
(Description) Side Begin End Width Start End Start End catE
Replacement Uniform(PSF) Top 0' 0.00" 14' 0.00" 13' 0.00" 0 10
Additional Uniform PLF Top 0' 0.00" 14' 0.00" 184 0
0 1400
14 0 0
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650psi) 3.500" 1.500" 2193# —
2 14' 0.000" Wall SPF#3/Stud 2x or 4x End-Grain(650 psi) 3.500" 1.500" 2193# —
Maximum Load Case Reactions
Used for applying point loads(or line loads)to carrying members
Live Dead
1 1248# 945#
2 1248# 945#
Design spans
13' 6.750"
Product: 1-3/4x9-1/2 VERSA-LAM 2.0 3100 SP 2 ply PASSES DESIGN CHECKS
Connect members with 2 rows of 16d common nails at 12.0"oc
Design assumes continuous lateral bracing along the top chord.
Design assumes continuous lateral bracing along the bottom chord.
Allowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 7436.'# 13958.# 53% 7' Total Load D+L
Shear 19371 63174 30% 13.1' Total Load D+L
Max.Reaction 2193.# 79621 27% 0' Total Load D+L
TL Deflection 0.4923" 0.6781" U330 7' Total Load D+L
LL Deflection 0.2801" 0".4521 U581 T Total Load L
Control: TL Deflection
DOLs: Live=100% Snow--115% Roof--125% Wind=160%
b
All product names are trademarks of their respective owners
Copyright(C)2013 by Simpson Strong-Tie Company Inc.ALL RIGHTS RESERVED.
"Passing is defined as when the member.Floor joist,beam or girder,shown on this it ng meets applicable design criteria for Loads,Loading Conditions,and Spans listed on this sheet.
The design must be reviewed a qualified designer or design professional as uiretl for ii roval.This de n assumes rodud installation according to the manufacturers specifications.