32A-138 (7) SYSTEM BATTERIES:
Are system batteries free of leaks or corrosion? Y
Are battery-enarging systems operating correctly and in the state of charge? Y
Are system batteries within manufactures replacement dates and/or proper current or voltage recommendations? Y
SYSTEM COMPONETS:
smoke detectors been checked for sensitivity at the proper intervals? NA
Are the smoke detectors sensitivity test results within the devices marked range or 4%obscuration light gray smoke? NA
Are all alarm notification appliances free of damage and operate per manufacture specifications? Y
Have all magnetic door holders been tested, and found to be operating satisfactory? NA
System annunciators are identified and operating correctly? NA
SYSTEM SUPERVISION AND MONITORING'
Did the supervision station receive the correct initiating device within 90 seconds? NA
Did the fire department receive a signal from the communicator or city box? Y
Location Device Type Device# Zone* Results
1st Floor
Front Entry Pull Station OK
Front Entry Horn Strobe OK
Store Front Smoke Detector OK
Rear Horn Strobe OK
M/W Rear Strobe OK
Rear Smoke Detector OK
Rear Hall Pull Station OK
Rear Hall Horn Strobe OK
Rest Room Strobe OK
Rest Room Smoke Detector OK
Basement
Front at Stairwell Smoke Detector OK
Center Horn Strobe OK
Center Smoke Detector OK
Rear Smoke Detector OK
Comments:
1) No deficincies noted at this inspection
If you would like the deficiencies above repaired on a time and material basis please initial next to the repairs you would like
corrected,then print,sign,and date below. Request for repairs can be faxed or emailed to our office
RE:The foundry Building
Customer Printed Name: Authorized Signature: Date:
.3 IA 136
Page 2 of 2
MA#1452
itait
ALARM SYSTEMS, INC.
845 Airport Industrial Park Road
Westfield, MA 01086 3a,11 , 1
cr Phone 413-568-3547
Fire Alarm Inspection &Test Report
Customer: The Foundry Building
Address: 24 Main Street, Northampton, MA
Date of Inspection: 4/8/2013
Inspector: David Schenna INicet# 198375
Customer Contact: Sally Noble
Location Phone Number:` 732-233-3599(Cell)
System Normal Upon Departure: YES
Panel Location:
Panel Model: SK51O4OB
System Type:
Monitoring Company:
Fire Department Northampton Fire Department
Zones: 4
Zone Type: B
Smoke Detector Style:
Heat Detector Type
Pull Station Type/Style Fire Lite BG 12
Smoke Detector Type: System Sensor 2B
Main Power:
Disconnect Location:
Auxiliary Power: (1) 12V 7 AN 2/4/10
Condition: Feb-10
Battery Voltage:
Battery Drain Voltage Before:
Battery Drain Test Voltage After:
Remote Annunciator:
Signals Received
Zone 1-1st Floor;Zone 2-Basement;Zone 3-Second Floor;Zone 4-Third Floor
NFPA 72 2002 Edition Annual Requirements YIN NA
Y=Satisfactory N=Unsatisfactory N/A=Not Applicable
FIRE ALA MCO TROL PANEL:
Are all the alarm zones labeled at the control panel? Y
Do all control panel lamps and LEDs illuminate? 4 Y
Are control panel terminations secure? Y
Does an open wiring on initiating or indicating circuits cause panel to go into trouble? Y
Does the earth ground detection work properly? Y
Is the location of breaker feeding the alarm panel been identified? Y
Does the control panel go into trouble with loss of AC feed, or loss of battery power? _ Y
Page 1 of 2