32A-138 (7) SYSTEM BATTERIES: Are system batteries free of leaks or corrosion? Y Are battery-enarging systems operating correctly and in the state of charge? Y Are system batteries within manufactures replacement dates and/or proper current or voltage recommendations? Y SYSTEM COMPONETS: smoke detectors been checked for sensitivity at the proper intervals? NA Are the smoke detectors sensitivity test results within the devices marked range or 4%obscuration light gray smoke? NA Are all alarm notification appliances free of damage and operate per manufacture specifications? Y Have all magnetic door holders been tested, and found to be operating satisfactory? NA System annunciators are identified and operating correctly? NA SYSTEM SUPERVISION AND MONITORING' Did the supervision station receive the correct initiating device within 90 seconds? NA Did the fire department receive a signal from the communicator or city box? Y Location Device Type Device# Zone* Results 1st Floor Front Entry Pull Station OK Front Entry Horn Strobe OK Store Front Smoke Detector OK Rear Horn Strobe OK M/W Rear Strobe OK Rear Smoke Detector OK Rear Hall Pull Station OK Rear Hall Horn Strobe OK Rest Room Strobe OK Rest Room Smoke Detector OK Basement Front at Stairwell Smoke Detector OK Center Horn Strobe OK Center Smoke Detector OK Rear Smoke Detector OK Comments: 1) No deficincies noted at this inspection If you would like the deficiencies above repaired on a time and material basis please initial next to the repairs you would like corrected,then print,sign,and date below. Request for repairs can be faxed or emailed to our office RE:The foundry Building Customer Printed Name: Authorized Signature: Date: .3 IA 136 Page 2 of 2 MA#1452 itait ALARM SYSTEMS, INC. 845 Airport Industrial Park Road Westfield, MA 01086 3a,11 , 1 cr Phone 413-568-3547 Fire Alarm Inspection &Test Report Customer: The Foundry Building Address: 24 Main Street, Northampton, MA Date of Inspection: 4/8/2013 Inspector: David Schenna INicet# 198375 Customer Contact: Sally Noble Location Phone Number:` 732-233-3599(Cell) System Normal Upon Departure: YES Panel Location: Panel Model: SK51O4OB System Type: Monitoring Company: Fire Department Northampton Fire Department Zones: 4 Zone Type: B Smoke Detector Style: Heat Detector Type Pull Station Type/Style Fire Lite BG 12 Smoke Detector Type: System Sensor 2B Main Power: Disconnect Location: Auxiliary Power: (1) 12V 7 AN 2/4/10 Condition: Feb-10 Battery Voltage: Battery Drain Voltage Before: Battery Drain Test Voltage After: Remote Annunciator: Signals Received Zone 1-1st Floor;Zone 2-Basement;Zone 3-Second Floor;Zone 4-Third Floor NFPA 72 2002 Edition Annual Requirements YIN NA Y=Satisfactory N=Unsatisfactory N/A=Not Applicable FIRE ALA MCO TROL PANEL: Are all the alarm zones labeled at the control panel? Y Do all control panel lamps and LEDs illuminate? 4 Y Are control panel terminations secure? Y Does an open wiring on initiating or indicating circuits cause panel to go into trouble? Y Does the earth ground detection work properly? Y Is the location of breaker feeding the alarm panel been identified? Y Does the control panel go into trouble with loss of AC feed, or loss of battery power? _ Y Page 1 of 2