37-011 (3) 211-42 CHIMNEYS,FIREPLACES,VENTS,AND SOLID FUEL–BURNING APPLIANCES Table 13.6.1 Standard Clearances for Solid Fuel–Burning Appliances Above Top of Casing or Appliance;Above Top and Sides of Furnace Plenum or Bonnet From Front From Back' From Sides' Type of Appliance in. mm in. mm in. mm in. mm Residential Appliances 6 152 48 1219 6" 152" 6" 152" Steam boilers—15 psi (103 kPa) Water boilers—250°F(121°C) max. Water boilers—200°F(93°C) max. All water walled or jacketed appliances Furnaces Gravity and forced air` 18 457 48 1219 18 457 18 457 Room Heaters,Fireplace Stoves, 36 914 36 914 36 914 36 914 Room Heater/Fireplace Stove Combinations, Ranges Firing Side Opposite Side Lined fire chamber 30" 762" 36 914 24 610 18 457 Unlined fire chamber 30" 762" 36 914 36 914 18 457 'Provisions for fuel storage must be located at least 36 in. (914 mm) from any side of the appliance. "Adequate clearance for cleaning and maintenance must be provided. For clearances from air ducts,see NFPA 90B,Standard for the Installation of Warm Air Heating and Air-Conditioning Systems. `Clearance to combustible material or metal cabinets.If the underside of such combustible material or metal cabinet is protected with sheet metal of not less than 24 gauge[0.024 in. (0.61 mm)],spaced out 1 in. (25 mm),the distance is permitted to be reduced to not less than 24 in. (610 mm). Table 13.6.2.1 Reduction of Appliance Clearance with Specified Forms of Protection Maximum Allowable Minimum Clearance Reduction in Clearance Reduction Applied to and Covering Clearance(%) As Wall Protector As Ceiling Protector All Combustible Surfaces Within the Distance Specified as Required Clearance As Wall As Ceiling with No Protection* Protector Protector in. mm in. mm (a) 31/2 in. (90 mm) thick masonry wall 33 — 24 610 — — without ventilated air space (b) / in. (13 mm) thick noncombustible 50 33 18 457 24 610 insulation board over 1 in. (25 mm) glass fiber or mineral wool batts without ventilated air space (c) 0.024 in. (0.61 mm),24 gauge sheet metal 66 50 12 305 18 457 over 1 in. (25 mm)glass fiber or mineral wool batts reinforced with wire or equivalent on rear face with ventilated air space (d) 31/2 in. (90 mm)thick masonry wall with 66 — 12 305 — — ventilated air space (e) 0.024 in. (0.61 mm),24 gauge sheet metal 66 50 12 305 18 457 with ventilated air space (f) 12 in.(13 mm) thick noncombustible 66 50 12 305 18 457 insulation board with ventilated air space (g) 0.024 in. (0.61 mm),24 gauge sheet metal 66 50 12 305 18 457 with ventilated air space over 0.024 in. (0.61 mm),24 gauge sheet metal with ventilated air space (h) 1 in.(25 mm)glass fiber or mineral wool 66 50 12 305 18 457 batts sandwiched between two sheets 0.024 in.(0.61 mm),24 gauge sheet metal with ventilated air space Notes: (1)All clearances and thicknesses are minimums;larger clearances and thicknesses are permitted. (2) To calculate the minimum allowable clearance, the following formula can be used: C1,,= C,,„ x [1 – (R/100)], where Ci,,.is the minimum allowable clearance,C„„is the required clearance with no protection,and R is the maximum allowable reduction in clearance. (3)Refer to Figure 13.6.2.1(e) and Figure 13.6.2.1(f)for other reduced clearances using materials found in this table. *See 13.6.1 through 13.6.1.3. 2013 Edition McKenney Electrical Co., Inc. 100 Northampton Street Holyoke, MA 01040 (Tel) 413.536.5551 To: City of Northampton Building Inspector Re: Clearance reduction on wood insert. Three areas on install that do not meet minimum clearance to combustibles. Copy of page 32 from install manual. (B) Fuel door to mantel, required 29". Measured at 25-1/2". (C) Fuel door to top trim, required 22". Measured at 13" (E) Hearth Extension, required 16", Measured at 13-1/2" Solution: Install a metal heat shield on top of insert surround. Heat shield will extend at a 45 deg angle outward. Extending 8" out from brick. To calculate minimum allowable clearance. Table 13.6.2.1, NFPA 211. Note 2. Cpr = Cun x [ 1-(R/100)]. Cpr: minimum allowable clearance Cun: required clearance without protection. R: Maximum reduction in clearance: 50% (B) 29[1-(50/100) = 14.5", measured at 25-1/2" (C) 22[1-(50/100) = 11", measured at 13" (E) remove wood flooring 4" +. Install non-combustible material. All other clearances are beyond minimum requirements. VOYAGEUR Wood Insert 0U,JDRA- mnE B. Clearances to Combustibles, United States and Canada (UL and ULC) A B C D NOTE: All measurements are from the fuel Masonry,Heat Circulating& 20.5 in. 29 in. 22 in. 10.5 in. loading door opening. J Factory-Built Fireplace (521 mm) (736mm) (559mm) (267mm) USA CANADA / HEARTH EXTENSION E F E F Maximum Mantel Depth-12 inch(305mm) / 16 in. 8 in. 18 in. 12-1/4 in. / /i' /; (457mm) (318mm) 2 Mantel / / EMBER PROTECTION I Required on all installations for USA and Canada B Fascia or Tr' I D Hearth Extension ! // 1! —'I * Maximum 1-1/2 inch (389mm)Top Trim Depth (,��� �e9e,,.e ** Maximum 3-1/2 inch (89mm) Side Trim Depth �� S apro -. \\ 499e fe°f! Ns \ Sf00, On NOTE: Keep Ashlip o,? ''-,� Clear of Ashes �� /i „, Mantel I Figure 32.2 \\kiwi ■ I NOTE: Hearth Rug may be used in Suggested Area 1 29 in.(736mm) Ii Minimum from Top of Fuel Loading IFI Door Opening A WARNNG Fire Risk.• Comply with all minimum clearances to combustibles as specified. • Failure to comply may cause house fire. Il NOTE: Clearances may only be reduced by means approved by the regulatory authority having juris- .... diction Figure 32.1 -Mantel Clearance Page 32 7063-173D November 22, 2011 City of Northampton — l' , REn EIVE s lr a r DEP -TMENT OF BUILDING INSPECTIONS , ; =.': V 1 2 2013 Municipal g & 21- Main Street • Munici al Buildin ' Northampton, MA 01060,}` DEPT.OF BUILDING INSPECTIONS NORTHAMPTON,MA 01060 I SINGLE OR TWO FAMILY SOLID FUEL APPLIANCE PERMIT APPLICATION FOR WOOD, COAL, PELLET, CORN, STRAW OR SIMILAR STOVES, OR FIREPLACE INSERTS Permit Fee: $25.00 Check # 5-07‘0 �7 PLEASE TYPE OR PRINT ALL INFORMAT N 1 PROPERTY ADORE 6 2^7 �(,Z).(�/ C �/ I ,� ril,4--11-e4')/� f\ 1. Name of Applicant: � 0/fi t 06 !n, Co i-r- Zd _gU ., ci,� 'II ` ?e-6 3c)-b Address: k �-�� Telephone: 2. Owner of Property: f f ` - 1-( �o� ti o S To U >( Address: (.0 k Q A,( 0, Rb Telephone: " g O I f0A;1 1-k MI:TO 3. Status of Applicant: Owner ;,Contractor l 4. Type or Brand of Stove: a v r P AU C 1 f ,--- Contractor's Name: 7.? ) , S co S l Contractor's Address: -,--0 17 U LL,4(1/.,_ /40 y t 7 Contractor's Phone: ' 2 6 .7 b b Construction Supervisor's License Number: S -3 ( 0 ' Expiration Date: D - f V" / / l <- n ~ / / Home Improvement Contractor Registration Number: / 'O 0 6 9 Expiration Date: � ` 6 All Applicants must complete a Workers Compensation Insurance Affidavit before we can issue a permit 5. Certification: I hereby certify that the information contained herein is true and accurate to the best of my knowledge. DATE: 6 -/ ' f 3 APPLICANT'S SIGNATURE /-24"/ 2 jh (S- '44-- DATE: 6 r/42 `) ,5 HOMEOWNER'S SIGNATURE 46-€ 1k114,____ ' APPROVED DATE: BUILDING OFFICIAL 629 FLORENCE RD BP-2013-1192 GIS#: COMMONWEALTH OF MASSACHUSETTS Map:Block: 37-011 CITY OF NORTHAMPTON Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A) Category: woodstove BUILDING PERMIT Permit# BP-2013-1192 Project# JS-2013-001962 Est. Cost: Fee: $25.00 PERMISSION IS HEREBY GRANTED TO: Const. Class: Contractor: License: Use Group: RICHARD SCOTT 83108 Lot Size(sq. ft.): 27007.20 Owner: DASTOLI ANTHONY A Zoning: Applicant: RICHARD SCOTT AT: 629 FLORENCE RD Applicant Address: Phone: Insurance: 20 BULLARD AVE (413) 533-6340 HOLYOKEMA01040 ISSUED ON:6/12/2013 0:00:00 TO PERFORM THE FOLLOWING WORK:INSTALL QUADRO FIRE WOODSTOVE INSERT POST THIS CARD SO IT IS VISIBLE FROM THE STREET Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector Underground: Service: Meter: Footings: Rough: Rough: House# Foundation: Driveway Final: Final: Final: Rough Frame: Gas: Fire Department Fireplace/Chimney: Rough: Oil: Insulation: Final: Smoke: Final: THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF ANY OF ITS RULES AND REGULATIONS. Certificate of Occupancy Signature: FeeType: Date Paid: Amount: Building 6/12/2013 0:00:00 $25.00 212 Main Street,Phone(413)587-1240,Fax: (413)587-1272 Louis Hasbrouck—Building Commissioner