38B-234 (4) Thank you f• y• r ooperation on these matters.
dr,
Chuck Miller
City of Northampton
Assistant Commissioner and Zoning Enforcement
26. Dryer duct maximum equivalent length is 25' less 5' per 90°elbow or per manufacturer's specs.780
CMR M1502.4.4.1, no screwed connections.
27. Markup air is required for any exhaust hood of 400 CFM or more. 780 CMR M1503.4
28. Fireplaces require all combustion air be provided from the exterior and below the firebox, duct work
maintaining 1" clearance for 5'from the duct outlet for all fireplaces and airtight doors. 2009 IECC
402.4.3
29. Fire and draft stopping shall be completed before rough inspection.Typical locations,top (ceiling) and
bottom (floor) plates, soffits,and every 10'within enclosed cavities.780 CMR R302.
30. Ignition barriers in place before final.780 CMR R316.
31. Dwelling/Garage fire separation.An attached garage(within 3'of main structure) is required to have 1/2"
drywall on the garage side of the separation wall and if there is a finished space above the garage all
walls must have%" drywall and the ceiling 5/8" drywall.780 CMR R302.6
32. Energy aspects shall comply with the stretch energy code.780 CMR Appendix 115AA or 2009 IECC.
a. An initial HERS evaluation is required including insulation levels anticipated.
b. A final HERS evaluation confirming code requirements have been met including duct testing.
c. A signed copy of the Thermal Bypass Checklist.
d. Energy information including mechanical equipment posted on the electric panel.
e. Remodeling and Additions can be completed in accordance with IECC 2009 with Energy Star
Windows and the Thermal Bypass Checklist. Duct blast testing when practicable.
f. All band joist insulation must be enclosed within an air tight cavity,which you must create.
33. Vapor retarders.Although these are still in the code have exceptions,one must understand that there is
a difference between'a vapor retarder or barrier and an air barrier.An air barrier is intended to stop air
flow(convection)a vapor retarder or barrier is intended to stop molecular moisture transfer(diffusion).
A vapor retarder or barrier is effective even if there are some holes or gaps, however an air barrier has
to be absolute and complete. If air can leak through an electrical device or through a crack it follows the
path of least resistance and carries 99%of the moisture in a structure.This is evident every time one
exposes fiberglass insulation and finds black insulation,which is dirt filter out of the air moving through
the insulation. 780 CMR R601.2 for vapor retarders and Table N1102.4.2 for air sealing requirements.
34. Unvented attic assemblies. Hot roofs are allowed, but have specific requirements 780 CMR R806.4.
35. Deck ledgers and post must be appropriately attached, bolts or lags.780 CMR R502.2.2.1 Note:ThruLoks
are engineered for post attachment supporting a railing.
36. Smoke and CO detectors as required.780 CMR R314 and R315.
a. Smokes in each bedroom,within 10'of a bedroom door.
b. CO within 10'of bedroom doors,at each level, at the bottom of a stair leading to a finished floor
above,for every 1500 sqft, (plumbing code in the mechanical room) Except if there are no fossil
burning fuels.
c. Heat detector in attached garage,and other large unfinished unconditioned spaces.
37. Closets beneath stair which have doors must be drywalled with%2".780 CMR R302.7
38. If there is mechanical equipment or a combustible roof,30 sqft of space, and 30" measured from top of
ceiling joist to bottom of rafters an attic access of minimum RO of 22"x 30" is required to be located in
an accessible place. It must be insulated,gasketed, and secured in place.
Relevant items must be submitted to the building department for approvals before inspections and or
Certificates of Occupancy can be issued.
Feel free to call if you have any questions. My telephone number is 587-1240 and office hours are Monday
through Friday,8:30 am to 4:30 pm, excepting we close for walk-ins at 12:00 noon on Wednesdays. My email
address is: cmiller(a�northamptonma.gov
13. All framing materials which are not code prescriptive must have stamped engineering.
a. LVLs
b. I-joist and or Floor Truss
c. Roof truss
14. A braced wall plan identifying appropriate braced wall areas where required (R301.1) and braced wall
method being used. 780 CMR 602.10.
a. Garage corners and large corner window/door layout may require special solutions.
b. All corners must be appropriately attached to the foundation.
c. When using PFH (R602.10.3.3)or PFG (R602.10.3.4)the nailing requirement is 4" and 3"
respectively using 8d common nails or galvanized box nails. NOT PNEUMATIC NAILS
15. When nailing sheathing make sure your pneumatic nailers' pressure is properly set. Nails set too deep
perforate the sheathing weakening it and contribute to building damage in high wind events.
16. Ceiling heights minimum 7'for habitable spaces, 6'8"for bathrooms includes tub/shower area if a
shower head is used, 6'8"for basements,6'4" at beams/ducts.780 CMR R305.1. MA amended
17. Hazardous glazing locations,within 24" of a door,or within 60"of a stair,or across from hot tubs,spas,
bathtubs within 60" if not 60" above the walking surface, and other locations.780 CMR R308.4
18. Windows over 72"above grade with the opening less than 24 above the finished floor shall meet the 4"
sphere rule.Order restrictors. 780 CMR R612.2
19. Egress and emergency escape requirements shall be strictly met.
a. Basements, habitable attics, and all sleeping rooms require emergency escape.780 CMR R310
b. Windows within 44" of floor, DH 3.3 sqft min window size,Casement 20"x41" exception 5 sqft
at 1s`floor. Minimum clear opening 20"x24"or 24"x20".780 CMR R310.1.1
c. Two doors remote as possible at the normal level of travel,opening measured from the face of
the slab to the stop with door at 90 degrees,one 32" and one 28" minimum 78" high.780 CMR
R311.2
d. Landing at each door 36"out and the width of the door minimum 36", maximum step 7 3/4"from
the top of the threshold and only in-swinging doors. 780 CMR R311.3
20. Stairs have critical standards, make sure you know the floor finishes when planning. Minimum tread 9",
maximum riser 8'4", maximum overall variance for the run is 3/8",4"sphere rule on risers except where
the total rise is 30"or less 780 CMR R311.7.4.3 Exception,4 3/8"on balustrade, 6" in the triangle.
Graspable rail 11A" minimum and 2" maximum rail, height minimum 34" maximum 38", required for 4 or
more risers. Landing to landing constitutes a new run. Minimum 6'8" ceiling height from nosing.780
CMR R311.7.
21. Guards 36" minimum height above walking surface, a bench is a walking surface, required for more than
30"above floor or grade within 36",4"sphere rule.780 CMR R312.1.
22. Educate the plumber and electrician about maximum notch and hole sizes, and placement.780 CMR
R502.8 and R602.6. In bearing studs holes not larger than 40%of a stud no closer than 5/8 to the edge,
In interior non-bearing studs holes not larger than 60%of a stud no closer than 5/8 to the edge, or holes
in joist are a maximum 1/3 the depth not closer than 2"from the top or bottom or to any other hole.
Notches are different.
23. Drilling or notching of more than 50%of the wall plate width of an exterior wall or load bearing partition
requires a 16 GA 1%" strap across the area and 6" beyond each side with 8- 10nd nails. 780 CMR
R602.6.1
24. Dryer ducts must terminate outside of the building, have a backdraft damper,cannot include a screen,
and require 3' clearance from windows. 780 CMR M1502.3
25. Dryer duct transition is limited to 8'of aluminum flex, must be exposed, and the proper UL listing.780
CMR M1502.4.3
City of Northampton
4''
Massachusetts
( 4 .1 'Y Vii'.
� . DEPARTMENT OF BUILDING INSPECTIONS
212 Main Street • Municipal Building bg 'A
Northampton, MA 01060 f "ti�!
INSPECTOR
Mr.Stokes May 03, 2013
20 Turkey Hill Road
Westhampton, MA 01027
Subject Location: 52 Olive Street
Map Block: 38B-234
Mr.Stokes,
Your building permit application and plans dated 7-29-12 have been approved as drawn and per this memo.
All work must meet all applicable codes whether noted or not included within this memo.
Please follow up on the following items:
These items will need to be accomplished as the project moves forward and before rough inspections;
1. Braced wall detailing at the garage door.
2. Copy of building plans in electronic format.
3. Stamped engineering for all non prescriptive materials and or systems.
4. HERS initial and final ratings,duct blast results,and a signed Thermal Bypass Checklist.
5. A smoke/CO in the 2"d floor hall.
As of August 4th 2011 the 8th Edition MA code is the 2009 IRC with MA amendments.
In the following are some generic requirements which seem to be problematic.
This is not intended to be comprehensive, nor is it a substitute for purchasing and reading the MA codes.
Read only international codes are available on line at http://pub licecodes.cvberregs.com/icod/one
must also consider the MA amendments to these codes which can be found at www.mass.gov/dps/bbrs
The current relevant building codes are:
2009 IBC, 2009 IEBC,2009 IMC, 2009 IRC,2009 IECC,AA115, MA amendments.
1. Structures shall conform to 780 CMR 8th Edition 1 and 2 family building codes with MA amendments.
2. Grading plan for structures being constructed required.780 CMR R401.3 for drainage requirements.
3. A basement drainage system is required in all basements 780 CMR R405.2.3.except those in group I
soils(table R405.1)
4. Foundations that retain earth and enclose interior space require damp proofing 780 CMR R406.1.
5. Through wall form ties must be removed from both faces and patched with hydraulic cement.780 CMR
R406.2 of amendments.
6. Foundation anchor bolts must be%2" and be embedded a minimum of 7" into the concrete. 10" bolts!
780 CMR R403.1.6
7. CMU foundations require 3/8" parging before damp proofing.780 CMR R406.1 see exceptions.
8. Emergency escape is required out of every basement whether habitable or not. 780 CMR R310.1
9. Ceiling joist are intended to prevent spread, once raised above the wall plate they become rafters ties
and may require up sizing of rafters and increased nailing for example with a 4" slope 8-16nd common
are required at each connection. 780 CMR R802.3.1. When there is neither of these a structural ridge is
required with a load path to the foundation.
10. Steel straps over the ridge or 1x4 minimum collar ties are required 4' OC in the upper 1/3rd 780 CMR
R802.3.1
11. Ridge boards must be the full depth of the cut. 780 CMR R802.3.
12. A complete window and header schedule is required. 780 CMR Table R502.5 for header sizing and
number of jack studs required.
Window 14:Wood Frame:Double Pane with Low-E 4 0.290 1
Wall 7:Wood Frame,16"o.c. 270 21.0 0.0 13
Window 15:Wood Frame:Double Pane with Low-E 3 0.290 1
Door 4:Glass 47 0.300 14
Wall 8:Wood Frame,16"o.c. 640 21.0 0.0 26
Window 16:Wood Frame:Double Pane with Low-E 22 0.300 7
Window 17:Vinyl Frame:Double Pane with Low-E 22 0.300 7
Door 5:Glass 66 0.300 20
Door 6:Glass 66 0.300 20
Wall 9:Wood Frame,16"o.c. 233 21.0 0.0 10
Door 7:Glass 56 0.300 17
Wall 10:Wood Frame,16"o.c. 185 21.0 0.0 10
Window 18:Wood Frame:Double Pane with Low-E 2 0.290 1
Window 19:Wood Frame:Double Pane with Low-E 2 0.290 1
Basement Wall 1:Solid Concrete or Masonry 960 0.0 13.0 49
Wall height:8.0'
Depth below grade:7.0'
Insulation depth:8.0'
Basement Wall 2:Solid Concrete or Masonry 624 0.0 13.0 36
Wall height:4.8'
Depth below grade:4.0'
Insulation depth:4.8'
Compliance Statement: The proposed building design described here is consistent with the building plans,specifications,and other
calculations submitted with the permit application.The proposed building has been designed to meet the 2009 IECC requirements in
REScheck Version 4.4.3 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Name-Title Signature Date
Project Title: Rahm/Cruikshank Residence Report date:03/14/13
Data filename: R:C.rck Page 2 of 2
REScheck Software Version 4.4.3
Compliance Certificate
Project Title: Rahm/Cruikshank Residence
Energy Code: 2009 IECC
Location: Northampton,Massachusetts
Construction Type: Single Family
Project Type: Addition/Alteration
Heating Degree Days: 6404
Climate Zone: 5
Construction Site: Owner/Agent: Designer/Contractor:
52 Olive St. Linda Rahm Tim Stokes
Northampton,MA 01060 52 Olive St. ACME Building Arts
Northampton,MA 01060 20 Turkey Hill Road
413-210-1566 Westhampton,MA 01027
413-695-2264
acmearc @comcast.net
Compliance:9.4%Better Than Code Maximum UA:508 Your UA:460
The%Better or Worse Than Code index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Gross Cavity Cont. Glazing UA
Assembly Area or R-Value R-Value or Door
Perimeter U-Factor
Ceiling 1:Cathedral Ceiling 504 50.0 0.0 11
Ceiling 2:Cathedral Ceiling 900 50.0 0.0 19
Ceiling 3:Cathedral Ceiling 525 50.0 0.0 11
Ceiling 4:Cathedral Ceiling 55 50.0 0.0 1
Skylight 1:Wood Frame:Double Pane with Low-E 7 0.510 4
Skylight 2:Wood Frame:Double Pane with Low-E 7 0.510 4
Skylight 3:Vinyl Frame:Double Pane with Low-E 11 0.500 6
Wall 1:Wood Frame,16"o.c. 170 21.0 0.0 9
Window 1:Wood Frame:Double Pane with Low-E 8 0.290 2
Window 2:Wood Frame:Double Pane with Low-E 8 0.290 2
Wall 2:Wood Frame,16"o.c. 100 21.0 0.0 5
Door 1:Glass 8 0.300 2
Wall 3:Wood Frame,16"o.c. 200 21.0 0.0 11
Window 3:Wood Frame:Double Pane with Low-E 2 0.290 1
Wall 4:Wood Frame,16"o.c. 1058 21.0 0.0 59
Window 4:Vinyl Frame:Double Pane with Low-E 5 0.290 1
Window 5:Wood Frame:Double Pane with Low-E 5 0.290 1
Window 6:Vinyl Frame:Double Pane with Low-E 5 0.290 1
Window 7:Wood Frame:Double Pane with Low-E 3 0.290 1
Window 8:Wood Frame:Double Pane with Low-E 2 0.290 1
Window 9:Wood Frame:Double Pane with Low-E 2 0.290 1
Window 10:Wood Frame:Double Pane with Low-E 2 0.290 1
Wall 5:Wood Frame,16"o.c. 860 21.0 0.0 48
Door 2:Glass 8 0.300 2
Door 3:Glass 8 0.300 2
Wall 6:Wood Frame,16"o.c. 333 21.0 0.0 18
Window 11:Wood Frame:Double Pane with Low-E 3 0.290 1
Window 12:Wood Frame:Double Pane with Low-E 3 0.290 1
Window 13:Vinyl Frame:Double Pane with Low-E 4 0.290 1
Project Title: Rahm/Cruikshank Residence Report date:03/14/13
Data filename: R:C.rck Page 1 of 2
r:.
The Commonwealth of Massachusetts
;._� Department of Industrial Accidents
Office of Investigations
�tt 600 Washington Street
'='el= `` Boston,MA 02111
� �°°�� www.mass.gov/dia
'Workers' Compensation Insurance Affidavit: Builders/Contractors/Electricians/Plumbers
Applicant Information Please Print Legibly
Name (Business/Organization/Individual): 61.--(3 - CEtA)l∎GSA-t 4o-4 dam..,.
Address: S Z 0 v,\u,T Ste',
City/State/Zip: Phone#: Al? Z 10 is
Are you an employer?Check the appropriate box: Type of project(required): /
1.0 I am a employer with 4. DI am a general contractor and I
employees(full and/or part-time).* have hired the sub-contractors 6. ❑New construction
2.111 I am a sole proprietor or partner- listed on the attached sheet. 7. 0 Remodeling
ship and have no employees These sub-contractors have, 8. 0 Demolition
working for me in any capacity. employees and have workers'
g Y P tY. 9. 0 Building addition
[No workers'comp.insurance comp.insurance.:
required.] 5. 0 We are a corporation and its 10.0 Electrical repairs or additions
3.0 I am a homeowner doing all work officers have exercised their 11.0 Plumbing repairs or additions
myself. [No workers' comp. right of exemption per MGL 12.0 Roof repairs
insurance required.] t c. 152, §1(4),and we have no
employees. [No workers' 13.0 Other
comp.insurance required.]
*Any applicant that checks box#1 must also fill out the section below showing their workers'compensation policy information.
t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such.
(Contractors that check this box must attached an additional sheet showing the name of the sub-contractors and state whether or not those entities have
employees. If the sub-contractors have employees,they must provide their workers'comp.policy number.
I am an employer that is providing workers'compensation insurance for my employees. Below is the policy and job site
information.
Insurance Company Name:
Policy#or Self-ins.Lic. #: Expiration Date:-
Job Site Address: City/State/Zip:'
Attach a copy of the workers'compensation policy declaration page(showing the policy number and expiration date).
Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of a
fine up to$1,500.00 and/or one-year imprisonment,as well as civil penalties in the form of a STOP WORK ORDER and a fine
of up to$250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of
Investigations of the DL A for insurance coverage verification.
I do hereby certify under the 'aim and p'realties of perjury that the information provided above is true and correct
Signature: pN P.,(A,■L A.AA-ltI_ Date: 23/`7//3
Phone#: k(—S Z'.O . IS- s--- k
Official use only. Do not write in this area,to be completed by city or town official'
City or Town: Permit/License#
Issuing Authority(circle one):
1.Board of Health 2.Building Department 3.City/Town Clerk 4.Electrical Inspector 5.Plumbing Inspector
6.Other ' '
Contact Person: Phone#:
City of Northampton
fe
1 Massachusetts
DEPARTMENT OF BUILDING INSPECTIONS ,
k" ' 212 Main Street • Municipal Building
,." Northampton, MA 01060 ar)\
INSPECTOR
Louis Hasbrouck Chuck Miller
Building Commissioner Assistant Commissioner
HOME OWNER EXEMPTION ACKNOWLEDGEMENT
The State of Massachusetts allows the homeowner the right under 780CMR 108.3.4 to act as his/her
construction supervisor. The state defines "Homeowner" as, " Person(s) who owns a parcel on which
he/she resides or intends to be, a one or two family dwelling, attached or detached structures
accessory to such use and/or farm structures. A person who constructs more than one home in a two-
year period shall not be considered a home owner."
The building department for the City of Northampton wants any person(s) who seek to use the home
owner exemption, to act as their own construction supervisor, to be aware that by doing so you
become responsible for compliance with state building codes and regulations. The inspection
process requires that the building department be called to inspect work at various stages, which include
foundation/footings (before backfill), sonotube holes (before pour), a rough building inspection
(before work is concealed), insulation inspection (if required) and a final building inspection.
The building department requires these inspections before the work is concealed, failure to secure
these inspections can result in failure to obtain a certificate of occupancy until the work can be
inspected.
If the homeowner hires other trades to perform work (electrical, plumbing & gas) the homeowner will be
responsible to make sure that the trades hired secure their proper permits in conjunction to the building
permit issued, and that they get their required inspections. Failure of the individual trades to secure
the permits and inspections as required can DELAY the project until such time as the proper permits
and inspections are made
I understand the above.
( ome owner/resident's signature requesting exemption)
I will call to schedule all required building inspections necessary for the building permit issued to me.
Date
Address of work location 5 Z C3. )
SECTION 8-CONSTRUCTION SERVICES
8.1 Licensed Construction Supervisor: Not Applicable ❑
Name of License Holder:
License Number
Address Expiration Date
Signature Telephone
9,Registered Home improvement Contractor: Not Applicable ❑
Company Name Registration Number
Address Expiration Date
Telephone
SECTION 10-WORKERS'COMPENSATION INSURANCE AFFIDAVIT(M.G.L.c.152,§25C(6))
Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result
in the denial of the issuance of the building permit.
Signed Affidavit Attached Yes ISO No ❑
11. - 'tome Owner Exemption
The current exemption for"homeowners"was extended to include Owner-occupied Dwellings of one(1) or two(2)families
and to allow such homeowner to engage an individual for hire who does not possess a license,provided that the owner acts
as supervisor.CMR 780, Sixth Edition Section 108.3.5.1.
Definition of Homeowner: Person(s)who own a parcel of land on which he/she resides or intends to reside,on which there
is,or is intended to be,a one or two family dwelling,attached or detached structures accessory to such use and/or farm
structures.A person who constructs more than one home in a two-year period shall not be considered a homeowner.
Such"homeowner"shall submit to the Building Official,on a form acceptable to the Building Official,that he/she shall be
responsible for all such work performed under the building permit.
As acting Construction Supervisor your presence on the job site will be required from time to time,during and upon
completion of the work for which this permit is issued.
Also be advised that with reference to Chapter 152(Workers' Compensation) and Chapter 153(Liability of Employers to
Employees for injuries not resulting in Death)of the Massachusetts General Laws Annotated,you may be liable for person(s)
you hire to perform work for you under this permit.
The undersigned"homeowner"certifies and assumes responsibility for compliance with the State Building Code,City of
Northampton Ordinances,State and Local Zoning Laws and State of Massachusetts General Laws Annotated.
Ch;tejtill
Homeowner Signature
icnikl"----e.. .
S+
SECTION 5-DESCRIPTION OF PROPOSED WORK(check all applicable)
New House ❑ Addition ja Replacement Windows Alteration(s) n Roofing n
Or Doors 0
Accessory Bldg. ❑ Demolition ❑ New Signs [D] Decks [El Siding[D] Other[D]
Brief Description of Proposed
Work: CO J(X 1 c.rr( V-F EXI c'T■rFt, 0;115-- ^'1[try 'Tr) 'rwi.,- F t-n
Alteration of existing bedroom Yes No Adding new bedroom Yes No
Attached Narrative Renovating unfinished basement Yes No
Plans Attached Roll -Sheet
6a. If New house and or addition to existing housing, complete the following:
a. Use of building :One Family Two Family Other
b. Number of rooms in each family unit: 1 2
Number of Bathrooms -)
c. Is there a garage attached? Jt.
d. Proposed Square footage of new construction. e-- G Dimensions ' r``,
e. Number of stories? j,
f. Method of heating? liVI L Fireplaces or Woodstoves — Number of each
g. Energy Conservation Compliance. Masscheck Energy Compliance form attached?
h. Type of construction (^)f.: t1 ti
i. Is construction within 100 ft.of wetlands? Yes \, No. Is construction within 100 yr. floodplain Yes ' No
j. Depth of basement or cellar floor below finished grade
k. Will building conform to the Building and Zoning regulations? L Yes No .
I. Septic Tank City Sewer 6' Private well City water Supply L''
SECTION 7a-OWNER AUTHORIZATION-TO BE COMPLETED WHEN
OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT
, as Owner of the subject
property
hereby authorize ,1 t v"--- ( `T j
to;t on my beha all matters relative to work authorized by this building permit application.
1-7/13
Signature of Owner ate
I ¶ o V---C 5 ,as Owner/Authorized
Agent hereby declare that the statements and information on the foregoing application are true and accurate,to the best of my knowledge
and belief.
Signed under the pains and penalties of perjury.
_rte \CC)
Print Name A 3//1---s
Signature of Own-
Dat
Section 4. ZONING All Information Must Be Completed. Permit Can Be Denied Due To Incomplete Information
Existing Proposed Required by Zoning
This column to be filled in by
�-�// Z Building Department
Lot Size , 3� Z /C ' / „ Z.7G!
Frontage k1 z.-c.� "l 7
Setbacks Front f"1.''t /
rAt i J
Side L: R: L: f R:_ ("Cl
i 1 .
. `
� �
Rear .f
Building Height kli %f
Bldg. Square Footage ei7/ 1 °' 2 ;j' r
Open Space Footage f / % f
(Lot area minus bldg&paved 'tt(7 8 ts�- . 20!O .
parking)
#of Parking Spaces
Fill:
(volume&Location)
A. Has a Special Permit/Variance/Finding ever been issued for/on the site?
NO 0 DON'T KNOW 0 YES 0
IF YES, date issued:
IF YES: Was the permit recorded at the Registry of Deeds?
NO 0 DON'T KNOW 0 YES
IF YES: enter Book t 1 /0 j Page \GI% and/or Document#
B. Does the site contain a brook, body of water or wetlands? NO DON'T KNOW 0 YES
IF YES, has a permit been or need to be obtained from the Conservation Commission?
Needs to be obtained 0 Obtained Date Issued:
C. Do any signs exist on the property? YES NO
IF YES, describe size, type and location:
D. Are there any proposed changes to or additions of signs intended for the property? YES 0 NO le-
IF YES, describe size, type and location:
E. Will the construction activity disturb(clearing,grading,excavation,or filling)over 1 acre or is it part of a common plan
that will disturb over 1 acre? YES 0 NO
IF YES,then a Northampton Storm Water Management Permit from the DPW is required.
,
i F.-. ,- _ Department use only
City of Northampton Status of Permit '
2 2013 Building Department Curb Cut/Driveway Permit
212 Main Street Sewer/Septic Availability
} Room 100 Water/well Availability
DEPT.O[' � r, � ��ct;TIONS
NORTHAMPTON rv�„o,oso I Northampton, MA 01060 Two Sets of Structural Plans
phone 413-587-1240 Fax 413-587-1272 Plot/Site Plans
Other Specify
APPLICATION TO CONSTRUCT,ALTER,REPAIR,RENOVATE OR DEMOLISH A ONE OR TWO FAMILY DWELLING
SECTION 1 -SITE INFORMATION
This section to be completed by office
1.1 Property Address:
5 Z a 0 U(5 _ Map Lot Unit
lOTC V4 ..lT� t r r
Zone Overlay District
/0 66
Elm St.District CB District
SECTION 2-PROPERTY OWNERSHIP/AUTHORIZED AGENT
2.1 Owner of Record:
Name(Print) �� Current Mailing Address:
,41- �N ��{.� ep 1°3 z a
Telephone
Signature
2.2 Authorized Agent:
Name(Prin ' Current Bailing Addr s:
Signature Telephone
SECTION 3-ESTIMATED CONSTRUCTION COSTS
Item Estimated Cost(Dollars)to be Official Use Only
completed by permit applicant
1. Building (a)Building Permit Fee
2. Electrical (b)Estimated Total Cost of
Construction from(6)
3. Plumbing Building Permit Fee
4. Mechanical(HVAC)
5. Fire Protection , I` /) ' 2.c Check Number
This Section For Official Use Only
Date
Building Permit Number: Issued:
Signatu -. —, i�%1►.rLi!��/h.L�tf�
Building Commissioner/Inspector of Buildings Date
File#BP-2013-0845 -E' �'S
APPLICANT/CONTACT PERSON TIMOTHY STOKES L t cc 4
ADDRESS/PHONE 20 TURKEY HILL RD WESTHAMPTON (413)695-2264 0 1i1O' ` vtf2
PROPERTY LOCATION 52 OLIVE ST ,
MAP 38B PARCEL 234 001 ZONE URB(100)/ 'e
_ J\
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST ' ,I
ENCLOSED REQUIRED DATE C)\(:-.
Ca N
ZONING FORM FILLED OUT
Fee Paid o0
Building Permit Filled out 95
Fee Paid Wi J / ` ��'
Typeof Construction: CONVERT SINGLE TO TWO FAMILY \J
New Construction
Non Structural interior renovations
Addition to Existing
Accessory Structure
Building Plans Included:
Owner/Statement or License 083602
3 sets of Plans/Plot Plan
THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INF RMATION PRESENTED:
Approved Additional permits required(see below)
PLANNING BOARD PERMIT REQUIRED UNDER:§
Intermediate Project: Site Plan AND/OR Special Permit With Site Plan
Major Project: Site Plan AND/OR Special Permit With Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received&Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
Permit from Elm Street Commission Permit DPW Storm Water Management
e ition Delay
il
Signature of Building C ic': Date
Note:Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health,Conservation Commission,Department
of public works and other applicable permit granting authorities.
*Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of
Planning&Development for more information.
52 OLIVE ST BP-2013-0845
GIS#: COMMONWEALTH OF MASSACHUSETTS
Map:Block: 38B-234 CITY OF NORTHAMPTON
Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS
Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A)
Category:Zoning Permit BUILDING PERMIT
Permit# BP-2013-0845
Project# JS-2013-000110
Est. Cost: $320000.00
Fee: $1925.00 PERMISSION IS HEREBY GRANTED TO:
Const.Class: Contractor: License:
Use Group: TIMOTHY STOKES 083602
Lot Size(sq.ft.): 13242.24 Owner: RAHM LINDA K&BARBARA R CRUIKSHANK
Zoning:URB(100)/ Applicant: TIMOTHY STOKES
AT: 52 OLIVE ST
Applicant Address: Phone: Insurance:
20 TURKEY HILL RD (413) 695-2264 O
W ESTHAMPTONMA01027 ISSUED ON:5/7/2013 0:00:00
TO PERFORM THE FOLLOWING WORK:CONVERT SINGLE TO TWO FAMILY
POST THIS CARD SO IT IS VISIBLE FROM THE STREET
Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector
Underground: Service: Meter:
Footings:
Rough: Rough: House# Foundation:
Driveway Final:
Final: Final:
Rough Frame:
Gas: Fire Department Fireplace/Chimney:
Rough: Oil: Insulation:
Final: Smoke: Final:
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Certificate of Occupancy Signature:
FeeType: Date Paid: Amount:
Building 5/7/2013 0:00:00 $1925.00
212 Main Street,Phone(413)587-1240,Fax: (413)587-1272
Louis Hasbrouck—Building Commissioner