37-022 (7) sovereign builders 12- 4 -12
� 1:3Spm
R 4 S E B U R G
37, _ �' 1 of 1
®a.600c
laritteamDigine 4.600s
Materials Database 1373
Member Data
Description: Member Type: Beam Application: Floor
Top Lateral Bracing: Continuous
Bottom Lateral Bracing: None
Standard Load: Moisture Condition: Dry Building Code: SBC
Live Load: 40 PLF Deflection Criteria: U360 live, Lf240 total
Dead Load: 10 PLF Deck Connection: Nailed Member Weight 12.5 PLF
Filename: KYB1
Other Loads
Type Trib. Other Dead
(Description) Side Begin End Width Start End Start End Category
Replacement Uniform (PSF) Top 0' 0.00" 12' 9.00" 13' 0.00" 30 10 Live
l 'Tl fl‘ 1
1290
O o
1290
Bearings and Reactions
Input Min Gravity Gravity
Location Type Material Length Required Reaction Uplift
1 0' 0.000" Wal Steel 3.500" 1.500" 3278# --
2 12' 9.000" Wal Steel 3.500" 1.500° 3278# --
Maximum Load Case Reactions
Used for applyng point loads (or line loads) to canting members
Live Dead
1 2401# 877#
2 2401# 877#
Design spans
12' 3.750"
Product: 2.0 RigidLam LVL 1 -3/4 x 9-1/2 3 ply PASSES DESIGN CHECKS
Design assumes continuous lateral bracing along the top chord.
Design assumes no lateral bracing along the bottom chord.
A llowable Stress Design
Actual Allowable Capacity Location Loading
Positive Moment 10091.'# 20436.'# 49% 6.38' Total Load D +L
Shear 2857.# 9476.# 30% 0.23' Total Load D +L
Max. Reaction 3278.# 13781.# 23% 0' Total Load D +L
TL Deflection 0.3670" 0.6156" U402 6.38' Total Load D +L
LL Deflection 0.2688" 0.4104" U549 6.38' Total Load L
Control: LL Deflection
DQLs: Live =100% Srow =115% Roof = 125% Wirxt =160%
Design assumes a repetitive member use increase in bending stress: 4 %
Manufacturer's installation guide MUST be consulted for multi -ply connection details and alternatives
All product names are trademarks of their respective °"Hers
K evin 13 ark C°pyight (C) 1987 -2012 byKeymadc Enterprises, LLC. ALL RIGHTS RESERVED.
"Passing is defined as when the member, fioorjs st, beam or girder( shown on this drawing meets applicable design criteria for Loads, Loading Conditions, and Spans listed on this sheet.
The desk must be reviewed a • alifieddesi. er or de i.n • • as re• iced fora, • al. This desi • assumes •mduct installationaccordn . tothemanufactumrss• cifcadons.