24C-069 (2) 26. Vapor retarders. Although these are still in the code have exceptions, one must understand that there is
a difference between a vapor retarder or barrier and an air barrier. An air barrier is intended to stop air
flow (convection) a vapor retarder or barrier is intended to stop molecular moisture transfer (diffusion).
A vapor retarder or barrier is effective even if there are some holes or gaps, however an air barrier has
to be absolute and complete. If air can leak through an electrical device or through a crack it follows the
path of least resistance and carries 99% of the moisture in a structure. This is evident every time one
exposes fiberglass insulation and finds black insulation, which is dirt filter out of the air moving through
the insulation. 780 CMR R601.2 for vapor retarders and Table N1102.4.2 for air sealing requirements.
27. Unvented attic assemblies. Hot roofs are allowed, but have specific requirements 780 CMR R806.4.
28. Deck ledgers and post must be appropriately attached, bolts or lags. 780 CMR R502.2.2.1 Note: ThruLoks
are engineered for post attachment supporting a railing.
29. Smoke and CO detectors as required. 780 CMR R314 and R315.
30. Closets beneath stair which have doors must be drywalled with %z ". 780 CMR R302.7
Relevant items must be submitted to the building department for approvals before inspections and or CO can be
signed. Other items are intended to avoid costly issues at inspections.
Feel free to call if you have any questions. My telephone number is 587 -1240 and office hours are Monday
through Friday, 8:30 am to 4:30 pm, excepting we close for walk -ins at 12:00 noon on Wednesdays. My email
address is: cmiller(cr�northamptonma.gov
Thank you • our coop- -tion on these matters.
•
Chuck Miller
City of Northampton
Assistant Commissioner and Zoning Enforcement
a. Garage corners and large corner window /door layout may require special solutions.
b. All corners must be appropriately attached to the foundation.
11. Ceiling heights minimum 7' for habitable spaces, 6'8" for bathrooms includes tub /shower area if a
shower head is used, 6'8" for basements, 6'4" at beams /ducts. 780 CMR R305.1. MA amended
12. Hazardous glazing locations, within 24" of a door, or within 60" of a stair, or across from hot tubs, spas,
bathtubs within 60" if not 60" above the walking surface, and other locations. 780 CMR R308.4
13. Windows over 72" above grade with the opening less than 24 above the finished floor shall meet the 4"
sphere rule. Order restrictors. 780 CMR R612.2
14. Egress and emergency escape requirements shall be strictly met.
a. Basements, habitable attics, and all sleeping rooms require emergency escape. 780 CMR R310
b. Windows within 44" of floor, DH 3.3 sqft min window size, Casement 20 "x41" exception 5 sqft
at ft floor. Minimum clear opening 20 "x24" or 24 "x20 ". 780 CMR R310.1.1
c. Two doors remote as possible at the normal level of travel, opening measured from the face of
the slab to the stop with door at 90 degrees, one 32" and one 28" minimum 78" high. 780 CMR
R311.2
d. Landing at each door 36" out and the width of the door minimum 36 ", maximum step 7 3/4" from
the top of the threshold and only in- swinging doors. 780 CMR R311.3
15. Stairs have critical standards, make sure you know the floor finishes when planning. Minimum tread 9 ",
maximum riser 8 3 ", maximum overall variance for the run is 3/8 ", 4" sphere rule on risers except where
the total rise is 30" or less 780 CMR R311.7.4.3 Exception, 4 3/8" on balustrade, 6" in the triangle.
Graspable rail 1 'A" minimum and 2" maximum rail, height minimum 34" maximum 38 ", required for 4 or
more risers. Landing to landing constitutes a new run. Minimum 6'8" ceiling height from nosing. 780
CMR R311.7.
16. Guards 36" minimum height above walking surface, a bench is a walking surface, required for more than
30" above floor or grade within 36 ", 4" sphere rule. 780 CMR R312.1.
17. Educate the plumber and electrician about maximum notch and hole sizes, and placement. 780 CMR
R502.8 and R602.6. In bearing studs holes not larger than 40% of a stud no closer than 5/8 to the edge,
In interior non - bearing studs holes not larger than 60% of a stud no closer than 5/8 to the edge, in
bearing walls if more than 50% of a plate is cut or notched a 1 Y2 16ga. strap must extend a minimum of
6" past the cut both directions and be nailed with 8 -10d per side, or holes in joist are a maximum 1/3
the depth not closer than 2" from the top or bottom. Notches are different.
18. Dryer duct transition is limited to 8' of aluminum flex and must be exposed. 780 CMR M1502.4.3
19. Dryer duct maximum equivalent length is 25' including the transition section or per manufacturer's
specs. 780 CMR M1502.4.4.1, no screwed connections.
20. Concealed dryer ducts are required to have a label within 6' of the dryer connection stating the
equivalent length and risk of fire. See CMR 780 M1502.4.5
21. Markup air is required for any exhaust hood of 400 CFM or more. 780 CMR M1503.4
22. Fireplaces require all combustion air be provided from the exterior and below the firebox, duct work
maintaining 1" clearance for 5' from the duct outlet for all fireplaces
23. Fire and draft stopping shall be completed before rough inspection. 780 CMR R302.
24. Ignition barriers in place before final. 780 CMR R316.
25. Energy aspects shall comply with the stretch energy code. 780 CMR Appendix 115AA or 2009 IECC.
a. An initial HERS evaluation is required including insulation levels anticipated.
b. A final HERS evaluation confirming code requirements have been met including duct testing.
c. Energy information including mechanical equipment posted on the electric panel.
d. Remodeling a nd Additions can he comp!etPd in accordance with IECC 2009 with Energy Star
Building Option Package.
City of Northampton
SA S IG
Massachusetts rr�
t of . ".r"
t a' DEPARTMENT OF BUILDING INSPECTIONS:
j i
* 212 Main Street • Municipal Building ?
Northampton, MA 01060 �syje- g,
INSPECTOR
Ed Lennihan May 22, 2012
76 Bancroft Road
Northampton, MA 01060
Subject Location: 66 Massasoit Street
Map Block: 24C - 069
Mr. Lennihan,
The following items are code requirements which need to be addressed:
1. Stamped engineering for any none prescriptive structural members, Trusses, I- Joist, and LVLs.
2. Explanation or plan for braced wall construction at the Sun Room walls.
3. Smokes and CO detectors throughout hard wired or approved wireless system.
a. There needs to be one added or relocated on the 2 " floor to be in the immediate area of
the bedrooms (within 10')
4. Window restrictors as required.
5. Several location require tempered glazing. Entry bench, stairway ?, next to doors or floors.
6. Make sure there is a continuous air barrier behind the tub and shower before it goes in.
7. 4" sphere rule at ballaustrade.
8. 10' fire stopping at sleeper /floor system.
9. Electronic copy of drawings.
As of August 4 2011 the 8 Edition MA code is the 2009 IRC with MA amendments.
In the following are some generic requirements which seem to be problematic.
This is not a substitute for purchasing and reading the MA codes.
1. Structures shall conform to 780 CMR 8 Edition 1 and 2 family building codes with MA amendments.
2. Grading plan for structures being constructed required. 780 CMR R401.3 for drainage requirements.
3. A basement drainage system is required in all basements 780 CMR R405.2.3. except those in group 1
soils (table R405.1)
4. Foundations that retain earth and enclose interior space require damp proofing 780 CMR R406.1.
5. Ceiling joist are intended to prevent spread, once raised above the wall plate they become rafters ties
and may require up sizing of rafters and increased nailing for example with a 4" slope 8 -16nd common
are required at each connection. 780 CMR R802.3.1.
6. Steel straps over the ridge or 1x4 minimum collar ties are required 4' OC in the upper 1 / 3rd 780 CMR
R802.3.1
7. Ridge boards must be the full depth of the cut. 780 CMR R802.3.
8. A complete window and header schedule is required. 780 CMR Table R502.5 for header sizing and
number of jack studs required.
9. All framing materials which are not code prescriptive must have stamped engineering.
a. LVLs
b. I -joist and or Floor Truss
c. Roof truss
10. A braced wall plan identifying appropriate braced wall areas and braced wall method being used. 780
CMR 602.10.
•
.� SEE TAX MAP No. 24C
o
cr
Li_ U) i
W 0 -k r e" \ ,v ..s.
G C , I� 7
�� / 4� �- 4'
�9 s
\ 2
,Coo" R dci, -,0
•
", t Qa,, lI�\
. 'fr J ° r"•> 1 4Ac • cur w,, & 4 1.--
L
RECOMMEND FULL s� \ �ra1�5 O �
BOUNDARY SURVEY �,, /� a � Of-
F � � o ). J
v J
. q 4,,, $..
METALIC READING
UNDER DRIVEWAY
SEE PLAN (DEED) BOOK 265, "AGE 171.
SEE DEED BOOK 6309, PAGE 109.
SEE FEMA MAP No. 250167 0002 A, DATED APRIL 3, 1978.
MORTGAGE INSPECTION PLAN
CERTIFIED TO — PEOPLES BANK AND
FIRST AMERICAN TITLE INSURANCE COMPANY
To the best of my knowledge, information and belief, I hereby report that I have examined the premises and that
this inspection plat shows the buildings as located on the premises described, that the buildings are entirely within
lot lines, and that there are no encroachments upon the premises described by buildings or any adjoining premises,
except as indicated. I further report that, to the best of my knowledge, there are no easements of record affecting
the tract shown hereon, except as noted. I further certify that this property is not located in the established flood
hazard area (100 Year Storm Event) as scaled from the Federal Emergency Management Agency (F.E.M.A.) Map.
This is a Mortgage Loan Inspection Survey and is not to be used for establishing property lines, hedges, fences,
building improvements, or for any other purpose other than a mortgage inspection. A full boundary survey , as per
CMR 250 Regulations, should be performed prior to any physical improvement(s) made on said property.
P1 �H PLAN OF LAND IN THE CITY OF
�
W . NORTHAMPTON, MASSACHUSETTS
a' I HAMPSHIRE COUNTY — "OWNER" OF RECORD
N ,M N
WILLIAM D. L INSMAN & PAULA M. PANICH
� P � ' DURKEE, WHITE, TOWNE AND CHAPDELAINE
<i J CIVIL ENGINEERS AND LAND SURVEYORS
356 FRONT STREET — CHICOPEE, MASS.
F AUGUST 13, 2010 N SCALE ) 1 " = 40' / DRWG.106 -6235
VDAC
• ��, THIS IS A QUOTE, NOT A POLICY
TRAVELERS J WORKERS COMPENSATION
AND —
EMPLOYERS LIABILITY POLICY
QUOTE PROFILE – VERSION 01
POLICY NUMBER: (7PJUB- 0545N1 3 -1 -1 2 )
RENEWAL OF (7PJUB- 0545N1 3 -1 -1 1 )
—
INSURED'S NAME AND ADDRESS
WORKERS COMPENSATION
DELONG CONSTRUCTION LLC INSURANCE PLAN
76 BANCROFT ROAD
A/R (WCIP) # MA
NORTHAMPTON MA 01060
POLICY PERIOD FROM: 05 -26 -12 TO 05 -26 -13
TOTAL ESTIMATED ANNUAL STANDARD PREMIUM $ 3408
PREMIUM DISCOUNT NONE
0900 -20 EXPENSE CONSTANT 338
TERRORISM 12
TOTAL ESTIMATED PREMIUM 3758
TAXES AND SURCHARGES 197
DEPOSIT AMOUNT DUE 3955MP
Employer's Liability BI Limit: $ 1000000 Each Accident
1 000000 Policy Limit
1000000 Each Employee
INSURER: TRAVELERS PROPERTY CASUALTY COMPANY OF AMERICA
Adjustments of Premiums shall be made ANNUALLY
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * ** Deposit Amount Due: $ 3955 * * * * * * * * * * * * * * * * * * * * * * * * * * * * **
POLICY NUMBER: (7PJUB 0545N1 3 - 1 - 12 )
DATE OF ISSUE: 04 - 12 - 12 CP ST ASSIGN: MA
OFFICE: DIRECT ASSIGNMENT701
PRODUCER: WHALEN INS AGCY 28LKF
City of Northampton
Massachusetts 4 . .. ,?
it DEPARTMENT OF BUILDING INSPECTIONS r
212 Main Street • Municipal Building
Northampton, MA 01060 �'t$
INSPECTOR
Louis Hasbrouck Chuck Miller
Building Commissioner Assistant Commissioner
HOME OWNER EXEMPTION ACKNOWLEDGEMENT
The State of Massachusetts allows the homeowner the right under 780CMR 108.3.4 to act as his /her
construction supervisor. The state defines "Homeowner" as, " Person(s) who owns a parcel on which
he /she resides or intends to be, a one or two family dwelling, attached or detached structures
accessory to such use and /or farm structures. A person who constructs more than one home in a two-
year period shall not be considered a home owner."
The building department for the City of Northampton wants any person(s) who seek to use the home
owner exemption, to act as their own construction supervisor, to be aware that by doing so you
become responsible for compliance with state building codes and regulations. The inspection
process requires that the building department be called to inspect work at various stages, which include
foundation /footings (before backfill), sonotube holes (before pour), a rough building inspection
(before work is concealed), insulation inspection (if required) and a final building inspection.
The building department requires these inspections before the work is concealed, failure to secure
these inspections can result in failure to obtain a certificate of occupancy until the work can be
inspected.
If the homeowner hires other trades to perform work (electrical, plumbing & gas) the homeowner will be
responsible to make sure that the trades hired secure their proper permits in conjunction to the building
permit issued, and that they get their required inspections. Failure of the individual trades to secure
the permits and inspections as required can DELAY the project until such time as the proper permits
and inspections are made
understand the above.
(Home owner /resident's signature requesting exemption)
I will call to schedule all required building inspections necessary for the building permit issued to me.
Date
Address of work location
•
The Commonwealth of Massachusetts
Department of Industrial Accidents
_ , Office of Investigations
600 Washington Street
it NA" Boston, MA 02111
www.mass.gov/dia
Workers' Compensation Insurance Affidavit: Builders /Contractors /Electricians /Plumbers
Applicant Information Please Print Legibly
Name (Business /Organization/Individual): 7Ft't r ( xvefroti! , L C
Address: 7& Bibirei orr-
City /State /Zip: ,'7;iion 77 At o ia'v Phone #: '/l3 - 3 ? 7 ` o/ 7
Are you an employer? Check the appropriate box: Type of project (required):
1. El I am a employer with 2- 4. ❑ I am a general contractor and I 6. ❑New construction
employees (full and/or part- time).* have hired the sub - contractors
listed on the attached sheet. 7. g Remodeling al
2. ❑ I am a sole proprietor or partner -
ship and have no employees These sub - contractors have 8. ❑ Demolition
working for me in any capacity. employees and have workers' 9. 14 Building addition
[No workers' comp. insurance comp. insurance.
required.] 5. n We are a corporation and its 10.0 Electrical repairs or additions
3. ❑ I am a homeowner doing all work officers have exercised their 11.17 Plumbing repairs or additions
myself. [No workers' comp. right of exemption per MGL 12.0 Roof repairs
insurance required.] t c. 152, § 1(4), and we have no
employees. [No workers' 13.0 Other
comp. insurance required.]
*Any applicant that checks box #1 must also fill out the section below showing their workers' compensation policy information.
t Homeowners who submit this affidavit indicating they are doing all work and then hire outside contractors must submit a new affidavit indicating such.
1 Contractors that check this box must attached an additional sheet showing the name of the sub - contractors and state whether or not those entities have
employees. If the sub - contractors have employees, they must provide their workers' comp. policy number.
I am an employer that is providing workers' compensation insurance for my employees. Below is the policy and job site
information.
Insurance Company Name: ✓&__ AeS
Policy # or Self -ins. Lic. #: 7 `PT(/ , o S `[ S iN? 1 1 IL Expiration Date: 0S z o 1
Job Site Address: && PrS5 A'S* T S T, City/State /Zip: le'rl- tomPrrao M4 - 0 I aO3
Attach a copy of the workers' compensation policy declaration page (showing the policy number and expiration date).
Failure to secure coverage as required under Section 25A of MGL c. 152 can lead to the imposition of criminal penalties of l..
fine up to $1,500.00 and/or one -year imprisonment, as well as civil penalties in the form of a STOP WORK ORDER and a fine
of up to $250.00 a day against the violator. Be advised that a copy of this statement may be forwarded to the Office of
Investigations of the DIA for insurance coverage verification.
I do hereby certify under the pains and penalties of perjury that the information provided above is true and correct
Signature: i- C Date: S/ 6 /Z v )/_
Phone #: L1 5 3 7
Official use only. Do not write in this area, to be completed by city or town official
City or Town: Permit/License #
Issuing Authority (circle one):
1. Board of Health 2. Building Department 3. City/Town Clerk 4. Electrical Inspector 5. Plumbing Inspector
6. Other
Contact Person: Phone #:
•
SECTION 8 - CONSTRUCTION SERVICES
8.1 Licensed Construction Supervisor: Not Applicable ❑
Name of License Holder : , dA4 VV d ) ' L C eV 1.104 ✓ C5 0 yL coe
License Number
76 3,a c,zo . nA - o i'6o 03 /is LoIy
Address Expiration Date
--e � . el/ 3 • Se7.043
Signature Telephone
J e _ rstere • A ' °M et ni • rovemen ontraeto ''''.;;Y;r:-' Not Applicable ❑
e04.14- .,6axue -, %
,E ,te LC 1s
Company Name Registration Number
/t° lc /
Address Expiration Date
A6/2774,4214 P -T-v4/ , 4 /06,0 Telephone q /& 'Sd' 7 aq 37
SECTION 10- WORKERS' 'COMPENSATION INSURANCE AF FIDAVIT (M G L c 152, § 25C(6))
Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result
in the denial of the issuance of the building permit.
Signed Affidavit Attached Yes rZ(, No ❑
11 - om wnerOixemption
The current exemption for "homeowners" was extended to include Owner- occupied Dwellings of one (1) or two(2) families
and to allow such homeowner to engage an individual for hire who does not possess a license, provided that the owner acts
as supervisor. CMR 780, Sixth Edition Section 108.3.5.1.
Definition of Homeowner: Person (s) who own a parcel of land on which he /she resides or intends to reside, on which there
is, or is intended to be, a one or two family dwelling, attached or detached structures accessory to such use and/ or farm
structures. A person who constructs more than one home in a two -year period shall not be considered a homeowner.
Such "homeowner" shall submit to the Building Offrcial,' on a form acceptable to'the Building Official, that he /she shall be
responsible for all such work performed under the building permit.
As acting Construction Supervisor your presence on the job site will be required from time to time, during and upon
completion of the work for which this permit is issued.
Also be advised that with reference to Chapter 152 (Workers' Compensation) and Chapter 153 (Liability of Employers to
Employees for injuries not resulting in Death).df the Massachusetts General Laws Annotated, you may be liable for person(s)
you hire to perform work for you under this permit.
The undersigned "homeowner" certifies and assumes responsibility for compliance with the State Building Code, City of
Northampton Ordinances, State and Local Zoning Laws and State of Massachusetts General Laws Annotated.
Homeowner Signature
•
• . ,
SECTION 5- DESCRIPTION OF PROPOSED WORK (check all applicable) 0
New House ❑ Addition IX Replacement Windows Alteration(s) (71 Roofing KI
Or Doors CI
Accessory Bldg. ❑ Demolition ❑ New Signs [O] Decks [D] Siding [0] Other [O]
Brief Description of Proposed /a X / 7
Work: C',:9 ,4 i.4ukd 4 At, 4444 / /p a», Add .5Ceeered 730 , ) 4(7 ' i3ed. w Ad
1) /N.' , it 7,1,3,1
Alteration of existing bedroom X Yes No Adding new bedroom Yes X No
Attached Narra ' Renovating unfinished basement Yes X No
Plans Attach Roll )Sheet
s itre ause~an dindditi a iii7eii ist ng = oiistnq co mplete the'foi airl`n:ej:
a. Use of building : One Family v 7 Two Family Other
b. Number of rooms in each family unit: / Number of Bathrooms 2. s eX4,'S "
/
c. Is there a garage attached? AO y r6 �'� /2 r''1 /EV ar + /= pcie.u7
d. Proposed Square footage of new construction. 2 �'cl - • Dimensions 4' X 20 `I S '° 4/ "a u,
e. Number of stories? 2- o
f. Method of heating? 4= A/YDk'' 4 r) C Fireplaces or Woodstoves Number of each '
g. Energy Conservation Compliance. Masscheck Energy Compliance form attached?
h. Type of construction <✓aa GdAme
E Is construction within 100 ft. of wetlands? Yes X No. Is construction within 100 yr. floodplain Yes X No
j. Depth of basement or cellar floor below finished grade do ''J " '"-S , 134L. 0 i F2 05-7- , ,F acc C" 4� 51 /A<<
/
k. Will building conform to the Building and Zoning regulations? t! Yes No .
I. Septic Tank City Sewer Private well City water Supply
SECTION 7a - OWNER .AUTHORIZATION TO BE COMPLETED WHEN
OWNERS AG.ENT'OR CONTRACTORAPPLIES`FORBUILDING "PERMIT
I, \&Ara- 4".41) 4 S LAC'"oA S 1 - i _J , as Owner of the subject
property
hereby authorize �c1 1L/'J dJ �. L E w// -04,)
to act of y behalf, inall matters rel .tive to work authoriz-d by this building permit application.
4 a ' \!.. / 6 PSI/ 2--
Signa of Owner , r Date
I, Ea LE.i /#Q,/ , as9wrier /Authorized
Agent hereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge
and belief.
Signed under the pains and penalties of perjury.
Ci / / T r
rkirTVC V • 4.K ., /417 v
Print Name
C e---- 7 # -- p.,,?..---- S /fy1
Signature of nsr /Agent Date
..____.. _ -... ....
.4 .
.4
i
Section 4. ZONING Alt Information Must Be Completed. Permit Can Be Denied Due To Incomplete Information
b
Existing Proposed Required by'Lonin
This column to be $ iiii
Building Department
Lot Size i 13 F I (ASS' i j i ` i
Frontage (O to ' ,
Setbacks Front 2.5-il j Z S' '
t+ r
Side L:` R:i L:! i R: i 1 I
Rear 12 I �'
Building Height ; •� I I ��
Bldg. Square Foota ii j 23 1 % i z ��,�
Open Space Footage % r _ --�
(Lot area minus bldg & paved { t0 Z. 8d' 1 Z g i I'°* r l 7 7 !
parking)
I y, 1 I i
# of Parking Spaces
Fill: 4- /\
At 11 (• iel „ _._ _ •
(volume & Location)
A. Has a Special Permit /Variance /Finding ever been issued for /on the site?
NO 0 DONT KNOW ® YES 0
IF YES, date issued:;
IF YES: Was the permit recorded at the Registry of Deeds?
NO 0 DONT KNOW 0 YES 0
IF YES: enter Book Page, # and /or Document #
B. Does the site contain a brook, body of water or wetlands? NO e DONT KNOW 0 YES 0
IF YES, has a permit been or need to be obtained from the Conservation Commission?
Needs to be obtained Obtained ® , Date Issued:
C. Do any signs exist on the property? YES 0 NO AC
3 -
IF YES, describe size, type and location:
D. Are there any proposed changes to or additions of signs intended for the property ? YES 0 NO ID
IF YES, describe size, type and location:
E. Will the construction activity disturb (clearing, grading, excavation, or filling) over 1 acre or is it part of a common plan
that will disturb over 1 acre? YES Q NO e
IF YES, then a Northampton Storm Water Management Permit from the DPW is required.
4 --CI F � _ � Depactrrte t use on t - " I RECEVE[ y of Northampton Status x
B ilding Department £ r *w 4 ° •i
Y�1► ' 12 Main Street • Se * e e p tc yai a
WO 1 6 2012 Room 100 ate 7::.:41., a �e� �; :
ort ampton, MA 0 Iwo a :
r._rB _. 3 -5:7 -1240 Fax 1272 plc), �
DELI BU =, x
NORTHAM °, a N MA 01060
APPLICATION TO CONSTRUCT, ALTER, REPAIR, RENOVATE OR DEMOLISH A ONE OR TWO FAMILY DWELLING
S ECTION 1 :SITE INFORMATION
1.1 Property Address: , This section to be completed by offi ce k .
)� 1l %45SASv. r 5,-. SMap k i_ot U It
L M �`�`5**�', �: ��.T � 7 `fix _ �"am.+�. ^3 �'C r+ax�+j *4;?��'.�„M,�'"' c# .�+^+'. M1 ,# �.� ;.
/ Y( 7+2 7H A.7713' ' GL� . Ones a OYei�IS/ DIStrICt * x n >
n E lrn S t CiIstn - . x .z. s CB Distric *
SECTIO 2 PR OPERTY OWNE RSHIP %AUTHORIZED AGENT
2.1 Owner of Record: ! / / /
S�4 Ear( 6 .i - i�� e d _A
.3"; 1 /tc d-j>.�i (/j r�J /,1415,1'Sa; i 5.7.... - �/ a �y "-('1 . 3' Cc�
Na a (Print) Current Mailing Address:
//3 - </S'�+ - f 1 /3
\ � ∎ o.%� ` Telephone
ignature / A
2.2 Authorized Agent:
E L E-v.. v. 7b 3 �I��eo , c ,- ,�/�,� -p r r, A • •
Name (Print) Current Mailing Address: ��
C Lam_ - GSS -3662
Signature Telephone
SECTION 3..ESTIMATED CONSTRUCTION COSTS
Item Estimated Cost ( Dollars) to be Official Use Only
completed by permit applic
1. Building y ��� d) (a) Building Permit Fee
2. Electrical eP (b) Estimated Total Cost of
) 0 , 00 0 . Construction from (6)
3. Plumbing Building P Fee
,70 0. —
4. Mechanical (HVAC) cc)
5. Fire Protection
Z2,
O�
6. Total - (1 + 2 + 3 + 4 + 5) Z�Ja, Check Number p 1,
This Sect For Official Use Only -
` Date
Building Permit Number: Issued:
Signature:
Bu ilding Commissioner /Inspe of Buildings ! Date
File # BP- 2012 -1007
APPLICANT /CONTACT PERSON ED LENNIHAN
ADDRESS/PHONE 76 Bancroft Road Northampton 587 -0437
24C PARCEL 069 A 9
MAP 2 001 ZONE URB(00)/ u� �( %)
P
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST
ENCLOSED REQUIRED DATE
ZONING FORM FILLED OUT
Fee Paid
Building Permit Filled out
Fee Paid ,5 a 4 6 gob
Typeof Construction: CONVERT GARAGE TO FAM RM,ADD 10 X 17 PORCH,EXTEND BEDRM & DIN RM
& ADD SUNROOM(9 X 20)
New Construction
Non Structural interior renovations
Addition to Existing,,
Accessory Structure
Building Plans Included:
Owner/ Statement or License 042506
3 sets of Plans / Plot Plan Ageell2
THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INF ATION PRESENTED:
Approved Additional permits required (see below)
PLANNING BOARD PERMIT REQUIRED UNDER:§
Intermediate Project: Site Plan AND /OR Special Permit With Site Plan
Major Project: Site Plan AND /OR Special Permit With Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received & Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
Permit from Elm Street Commission Permit DPW Storm Water Management
1 - olition Delay ,.���" ,.
igifature of Building Official Date L . 5 - - /P Oil? s -
Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health, Conservation Commission, Department
of public works and other applicable permit granting authorities.
* Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of
Planning & Development for more information.
66 MASSASOIT ST BP- 2012 -1007
GIS #: COMMONWEALTH OF MASSACHUSETTS
Map:Block: 24C - 069 CITY OF NORTHAMPTON
Lot: -001 PERSONS CONTRACTING WITH UNREGISTERED CONTRACTORS
Permit: Building DO NOT HAVE ACCESS TO THE GUARANTY FUND (MGL c.142A)
Category: ADDITION BUILDING PERMIT
Permit # BP- 2012 -1007
Project # JS- 2012 - 001740
Est. Cost: $200000.00
Fee: $1200.00 PERMISSION IS HEREBY GRANTED TO:
Const. Class: Contractor: License:
Use Group: ED LENNIHAN 042506
Lot Size(sq. ft.): 13068.00 Owner: STRANFORD SHARON A & JANICE A HUDGINGS
Zoning: URB(100)/ Applicant: ED LENNIHAN
AT: 66 MASSASOIT ST
Applicant Address: Phone: Insurance:
76 Bancroft Road 587 -0437 WC
NorthamptonMA01060 ISSUED ON:5/23/2012 0:00:00
TO PERFORM THE FOLLOWING WORK:CONVERT GARAGE TO FAM RM,ADD 10 X 17
PORCH,EXTEND BEDRM & DIN RM & ADD SUNROOM(9 X 20)
POST THIS CARD SO IT IS VISIBLE FROM THE STREET
Inspector of Plumbing Inspector of Wiring D.P.W. Building Inspector
Underground: Service: Meter:
Footings:
Rough: Rough: House # Foundation:
Driveway Final:
Final: Final:
Rough Frame:
Gas: Fire Department Fireplace /Chimney:
Rough: Oil: Insulation:
Final: Smoke: Final:
THIS PERMIT MAY BE REVOKED BY THE CITY OF NORTHAMPTON UPON VIOLATION OF
ANY OF ITS RULES AND REGULATIONS.
Certificate of Occupancy Signature:
FeeType: Date Paid: Amount:
Building 5/23/2012 0:00:00 $1200.00
212 Main Street, Phone (413) 587 -1240, Fax: (413) 587 -1272
Louis Hasbrouck — Building Commissioner
1'1 IUUUI.CU CS Y AN HU 1 UUCJI'\ CUU1..H 1 IUIVHL 1 KVUU.• 1
12 6f :
2 �
b
3thin•
�a
vi_
4 x 6 Header Typ.
0 0
n 0
o c
O n
cr IT
a 0
Q 4x6 Brace@ CC
ZZ
0 corners Typ. D
Z
~ D
O C
D
O C
w 0
Y im CA
w
O m
4/.a“ cS = 0
8 x 8 Post in Corner
T c
Q 3- f: yp D
Z
a a
2
m r
w '�
U �
2 x 4 Horizontal Bracing 2' O.C. 0
0 C 0
o CI CI
a
/ 4 Floor Sheathing
— Double 2 x 6 PT 14'
Span 2 x 6 PT Rim Joist 10' Span
i1R
�CRL\
1')nao?Jd 1VNOlivnna3 vs9aolnV NV Ag 03O11fO21d
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT
0
3 " c c
D n
i' - _J 1 1 1 1 I of
. v
-J C
Q -<
O z
Q _ _ D
D / C
W 2 x 8 PT 16'0.0 C
TYP (0 n
3
w /
D n
o _ _c
D c
a - _i
z c
>- i
at `] ( r
V 1 1 1 111 1 11 1 1 1 7
0 c
C
0
Lt
a
1Of1002ld 1VNOild3flO3 )4S3001ltl NY AB 03011002id
PRODUCED BY AN AUTODESK EDUCATIONAL PRODUCT
t ------ i h/ — 7� o
v
0 C rn
L co
J CC
-<
Z D
Z
D
C
j C
1J R
3 L1 C
II I ► c
5 D
Q - z
Q
>- I 1 1 1 1 1 2
M r
W 7
✓ c
3 C
O C
O Gel 10100 seI6w4S llneydsy C
x
n.
lnnanNei - 1VN011tVnnaq 'Is9ao1nv NV IR 090110021d
SEE TAX MAP No. 24C
0
Ch
Li_ i o A \
_J V) II ,/ t - \
<V) � �"
U Q
(�4 �P, tk `P TO 0 P >>� K c � '.5 ' In
\ ,3\ .,9t, l '� °ms s
Ci
k.4 h, F ,
G �
F�F\ C3- ' Rol � V
N. < ` 1r ::. � '9, o Q O .
N. "J o " "' T'/ I �F • GUY WI R S' ��
L
-
O
RECOMMEND FULL Fs `r � � \ Q �o �
BOUNDARY SURVEY �,� o ` c 6 )
O cF F iq � 4 . Dc �p��• vl �
q ,;(</, $ • •
METALIC READING
UNDER DRIVEWAY
SEE PLAN (DEED) BOOK 265, 'AGE 171.
SEE DEED BOOK 6309, PAGE 109.
SEE FEMA MAP No. 250167 0002 A, DATED APRIL 3, 1978.
MORTGAGE INSPECTION PLAN
CERTIFIED TO — PEOPLES BANK AND
FIRST AMERICAN TITLE INSURANCE COMPANY
To the best of my knowledge, information and belief, I hereby report that I have examined the premises and that
this inspection plat shows the buildings as located on the premises described, that the buildings are entirely within
lot lines, and that there are no encroachments upon the premises described by buildings or any adjoining premises,
except as indicated. I further report that, to the best of my knowledge, there are no easements of record affecting
the tract shown hereon, except as noted. I further certify that this property is not located in the established flood
hazard area (100 Year Storm Event) as scaled from the Federal Emergency Management Agency (F.E.M.A.) Map.
This is a Mortgage Loan Inspection Survey and is not to be used for establishing property lines, hedges, fences,
building improvements, or for any other purpose other than a mortgage inspection. A full boundary survey , as per
CMR 250 Regulations, should be performed prior to any physical improvement(s) made on said property.
N ON PLAN OF LAND IN THE CITY OF
mW ., NO MASSACHUSETTS
HAMPSHIRE COUNTY — "OWNER" OF RECORD
W '` - �',' N WILLIAM D. LINSMAN & PAULA M. PANICH
DURKEE, WHITE, TOWNE AND CHAPDELAINE
< , CIVIL ENGINEERS AND LAND SURVEYORS
356 FRONT STREET — CHICOPEE, MASS.
• G'-( FAUGUST 13, 2010 N SCALE ) 40' / DRWG.106 -6235
•
9. ALL INFORMATION MUST BE COMPLETED; PERMIT CAN BE DENIED DUE TO LACK OF INFORMATION.
This column to be filled in by
the Building Department.
Existing Proposed Required by
Zoning
/
Lot Size
!3,
Frontage N/A N/A N/A
Front:
Setbacks:
Side: L: R: L: R:
Rear:
Height 70 C
% Open Space:
(Lot area minus bldg and
Paved parking)
10. Certification: I hereby certify that the information contained herein is true and accurate to the best
of my knowledge.
DATE: e / - 512 ` t APPLICANT'S SIGNATURE "D
NOTE: Issuance of a permit does not relieve an applicant's burden to comply with all zoning requirements
and obtain all required permits from the Conservation Commission, Department of Public Works and other
applicable permit granting authorities.
City of Northampton
F' s EC '. " ---- Massachusetts n .
' D PAR 1 NT OF BUILDING INSPECTIONS
w y •12 -in Street • Municipal Building
2 Northampton, MA 01060 14:‘
INSPECTO' DEPT OF BUILDING ASPECTioNS
NORTHAMPTON MA 0'060
ACCESSORY STRUCTURE PERMIT APPLICATION
(For freestanding structures Tess than 200 sq. ft., at (east 5 feet from any other structure)
Permit Fee: $25.00 Check # �� a
PLEASE TYPE OR PRINT ALL INFORMATION
1. Name of Applicant: 1- rnnv ' i-/ A
Address: '7 6 { 41L 0 r it "J°,2 " Telephone: 413 S S - 3 6 E L
2. Owner of Property: 5 / ea- 57
Address: 66 /74 4-55A5� ' 5 / - /� /,� r-iJ 4.4 7>T-0 .-:// Telephone: q7i3 - ' ' - / 7
3. Status of Applicant: Owner X Contractor
hi a 4. Structure Location: ,` l2 o F j/eo { ?�` / - A/• AI (in C ✓w , ` 2 -1., 5 0 c R
Parcel ID: Zoning Map # Parcel # District(s)
(TO BE FILLED IN BY THE BUILDING DEPARTMENT)
5. Use of Property: Single or Two Family: X Multifamily: Commercial:
6. Description of Proposed Structure:
Shed under 200 sq. ft. v Freestanding Deck under 200 sq. ft. Other (describe)
/b *ft/
7. Attached Plans: Sketch Plan c/ Site Plan (7 Plot Plan
8. Does the site contain a brook, body of water or wetlands? NO DON'T KNOW YES
IF YES: Has a permit been, or need to be, obtained from the Conservation Commission?
Needs to be obtained Obtained , Date issued
CONTINUED ON NEXT PAGE
File # MP- 2012 -0117
APPLICANT /CONTACT PERSON ED LENNIHAN
ADDRESS/PHONE 76 Bancroft Road 587 -0437
PROPERTY LOCATION 66 MASSASOIT ST
MAP 24C PARCEL 069 001 ZONE URB(100)/
THIS SECTION FOR OFFICIAL USE ONLY:
PERMIT APPLICATION CHECKLIST
ENCLOSED REQUIRED DATE
ZONING FORM FILLED OUT sa ;0-
Fee Paid `� ItaS
Building Permit Filled out
Fee Paid
Typeof Construction: ZPA - 10 X 14 SHED
New Construction
Non Structural interior renovations
Addition to Existing
Accessory Structure
Building Plans Included:
Owner/ Statement or License
3 sets of Plans / Plot Plan
THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON
INFOd2MATION PRESENTED:
Approved Additional permits required (see below)
PLANNING BOARD PERMIT REQUIRED UNDER : §
Intermediate Project : Site Plan AND /OR Special Permit with Site Plan
Major Project: Site Plan AND /OR Special Permit with Site Plan
ZONING BOARD PERMIT REQUIRED UNDER: §
Finding Special Permit Variance*
Received & Recorded at Registry of Deeds Proof Enclosed
Other Permits Required:
Curb Cut from DPW Water Availability Sewer Availability
Septic Approval Board of Health Well Water Potability Board of Health
Permit from Conservation Commission Permit from CB Architecture Committee
Permit from Elm Street Commission Permit DPW Storm Water Management
— 7 /2. 41/ 1--
Signature of Building Official Date
Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning
requirements and obtain all required permits from Board of Health, Conservation Commission, Department
of public works and other applicable permit granting authorities.
* Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact the Office of
Planning & Development for more information.