22B-043 (12) • The FD connection for sprinkler system is to be 4" Storz connection with an
attached chain, in addition a sign reading "Fire Department Connection" in 3"
white letters on a red background is to be mounted above the connection.
Also an electric bell, which activates upon water flow, must be located above
this sign.
• Page 2
a
Northampton Fire
Department
Memorandum
To: Tony Patillo
From: Duane Nichols
Date: September 21, 2009
CC: Brian Duggan
Re: 296 Nonotuck St. Nonotuck Mills
Secondary to a review of the plans submitted to me for review, I concur with the
issuance of a building permit subject to the following conditions:
• Fire alarm and fire suppression work permits shall be obtained for the project.
The C/O inspection fee needs to be paid prior approval of any fire alarm or
sprinkler plan.
• A graphic representation of the structure must be installed at the Fire Alarm
Control Panel (FACP) and /or Fire Alarm Annunciator and /or Communicator.
This must be current with on -going renovations
• 5 lb ABC Fire extinguishers are needed located at exits. This shall be in
compliance with NFPA relative to maximum travel distance. Appropriate
signage in compliance with ADA should be located above
• Pull stations and horn /strobes shall be installed in renovated area by exits.
• Pull Stations shall be double action type.