22B-043 (12) • The FD connection for sprinkler system is to be 4" Storz connection with an attached chain, in addition a sign reading "Fire Department Connection" in 3" white letters on a red background is to be mounted above the connection. Also an electric bell, which activates upon water flow, must be located above this sign. • Page 2 a Northampton Fire Department Memorandum To: Tony Patillo From: Duane Nichols Date: September 21, 2009 CC: Brian Duggan Re: 296 Nonotuck St. Nonotuck Mills Secondary to a review of the plans submitted to me for review, I concur with the issuance of a building permit subject to the following conditions: • Fire alarm and fire suppression work permits shall be obtained for the project. The C/O inspection fee needs to be paid prior approval of any fire alarm or sprinkler plan. • A graphic representation of the structure must be installed at the Fire Alarm Control Panel (FACP) and /or Fire Alarm Annunciator and /or Communicator. This must be current with on -going renovations • 5 lb ABC Fire extinguishers are needed located at exits. This shall be in compliance with NFPA relative to maximum travel distance. Appropriate signage in compliance with ADA should be located above • Pull stations and horn /strobes shall be installed in renovated area by exits. • Pull Stations shall be double action type. • Page 1