38B-032 (2) • Panel" and /or "Fire Alarm Annunciator". Also engraved signage listing all fire alarm zone locations installed near panels. • A graphic representation of the structure must be installed at the Fire Alarm Control Panel (FACP) and /or Fire Alarm Annunciator and /or Communicator. • Pull Stations shall be double action type located by the exits. • 5 lb ABC Fire extinguishers are needed located at exits. This shall be in compliance with NFPA relative to maximum travel distance. Appropriate signage in compliance with ADA should be located above. • Alarm verification must be active on all smoke detection zones. • Page 2 Northampton Fire Department Memorandum To: Louis Hasbrouck From: Duane Nichols Date: July 29, 2010 CC: Larry Therrien Re: 139 South St Secondary to a review of the plans submitted to me for review, I concur with the issuance of a building permit subject to the following conditions: • Fire alarm work permits shall be obtained for the project. The C/O inspection fee needs to be paid prior to approval of any fire alarm plan. • Fire Department will need documentation that the current fire alarm control equipment is compatible with new equipment. • A Fire Department Emergency Access Key Box on the exterior of the structure needs to be relocated near the entrance to control equipment, along with a red 120 - candela strobe light that actuates upon an alarm condition is required above the Emergency Access Key Box. This needs to be visible from the street. • Engraved key tags are required for the keys in Emergency Access Key Box. • The Fire Alarm Control Panel and Fire Alarm Annunciator must be labeled with red engraved signage with one -inch white lettering "Fire Alarm Control • Page 1 ARCHIMETRICS DESIGN STUDIO EN 28 NORTH MAPLE UNIT B ,• FLORENCE, MA 01062 July 15, 2010 To: Louis Hasbrouck, Building Commissioner From: Peter Lapointe, Architect RE: Northampton Community Music Center (NCMC) 139 South Street Northampton, MA 01060 Chapter 34 Review NCMC is located in a two story brick bearing wall structure with wood framed floors. The gross square footage of the entire building is including the basement level is 11,400 square feet (3 x 3800). For building code purposes the type of construction is 3B and the Use Group is B. There is no intended change is use. The scope of work is renovation of 3,000 square feet of building area located entirely on the lower level. The work includes removal of obsolete and /or abandoned utilities and plumbing fixtures, thermal envelope improvements (windows and building insulation) and creation of four new spaces for programmed activities to include a piano lab, teaching lab, recording studio and small recital space (30 people). Since there is no change in use, the provisions of 3404 apply to the building renovation. The scope of work does not change the number or capacity of existing exits. The exit enclosures are being modified to allow new egress doors to be placed in new construction and to separate the exit stair from niches that have been identified for use as storage. Newly constructed partitions of the stair enclosures will be 1 hour construction. 1 hour rated ceilings will be provided throughout as part of the replacement of existing plaster ceilings even though rated floors are not required. All of the provisions of 3404 are being met or were met when the building was renovated in 1997 and 2003( + / -). The building is has an accessible entrance and all levels are served by two lifts. Staff and student bathrooms are fully accessible and the entire renovation will be fully accessible. PETER LAPOINTE, ARCHITECT PH 413 582 -9100 FAX 413 582 -9101 www.archimetrics.net ARCHIMETRICS DESIGN STUDIO EN 28 NORTH MAPLE UNIT B c_ FLORENCE, MA 01062 The state wide adoption of MGL 148 / 26G affects this building because it is over 7,500 square feet. The Fire Safety Commission's Automatic Sprinkler Appeals Board issued an advisory that discusses the application of the law including work that constitutes substantial renovation. The rule of thumb placed this threshold at 33 percent or one third of the building. In this case, one third of the building would constitute a single floor. The proposed renovations involve 80 percent of the lower level or 27 percent of the building area. The scope of work does meet the description of the types of work that constitute substantial renovations, but, the building area is less than one third of the entire gross square footage. Using these guidelines the applicability of 3404.12 as it related to MGL 148 / 26G would not apply to the scope of this project. Similarly, the threshold for substantial renovation as defined in 780 CMR 3401 and referenced in 3404.12 is not reached by the scope of this renovation. Respectf ub,,•' d, Peter Lapointe PETER LAPOINTE, ARCHITECT PH 413 582 -9100 FAX 413 582 -9101 www.archimetrics.net 3.2 APPROVAL REQUIREMENTS a. The following documentation shall be submitted to the Code Official along with a request to schedule a final fire alarm acceptance test. • Fire Detection Systems, div of Cebula Electronics Corp. certification of project completion in accordance with 780 CMR 907.16 with attached pre- acceptance test reports. b. Final Acceptance Test Documentation • Confirmation of the final acceptance test date shall be coordinated by the Code Official and installing professional verbally or in writing at the discretion of the Code Official. • Should all systems satisfy operational code compliance requirements to the satisfaction of the Code Official at the time of the final acceptance tests, the Code Official shall indicate approval of the installation in writing. • Should any system or portion of a system fail to satisfy code compliance requirements to the satisfaction of the Code Official at the time of the final acceptance test, at the discretion of the Code Official, the deficiency shall be corrected and retested during the test or the testing shall be rescheduled and repeated to the extent deemed necessary by the Code Official. An order to reschedule the testing shall be made in writing by the Code Official. The order shall indicate the code deficiencies that must be corrected. each exit. A smoke detector will be installed over the fire panel. Horn /strobes will be installed for notification and evacuation of employees, patrons and tenants. c. Method of Future Testing • Maintenance, inspection, and testing shall be provided as per NFPA 72. Proper testing and maintenance of the systems is the responsibility of the owner. SECTION 2 - SEQUENCE OF OPERATION 2.1 FIRE ALARM SYSTEM a. Upon manual activation of a pull station or automatic operation of a smoke or heat detector, the following intended functions will be performed. The sequence intended to initiate total building evacuation and notify the Northampton Fire Department. • Indicate alarm condition on the Fire Alarm Panel located in the front entrance. • Initiate building evacuation via fire alarm system notification appliances. • Notify Northampton Fire Department through Central Station monitoring station. SECTION 3 TESTING CRITERIA 3.1 TESTING CRITERIA a. The installing contractor shall develop and administer the testing schedule and will coordinate notification of appropriate parties. b. System will undergo a functional pre- acceptance fire alarm test which will be conducted by the installing contractor. Documentation of the testing results will be copied to the Code Official. c. Upon successful completion of the fire alarm pre- acceptance testing, the tests will be repeated at the discretion of the Code Official during a scheduled final acceptance test to be witnessed by the Code Official. e. Construction of Building: Masonry and Wood. f. Hazardous Material Storage: None g. High Piled Storage: None h. Site Access • Fire Department apparatus may access the site from South Street. 1.2 APPLICABLE LAWS, REGULATIONS & STANDARDS a. 780 CMR - Massachusetts State Building Code, 7th edition • Chapter 9 "Fire Protection and Life Safety Systems" b. 527 CMR 24.00 - Board of Fire Prevention Regulations c. NFPA Standards • NFPA 72 - National Fire Alarm Code (2007) • NFPA 70 - National Electrical Code with MA Amendments (2008) 1.3 DESIGN RESPONSIBILITIES a. Engineer of Record • Design - Build, the installing fire alarm contractor completely designs and specifies the fire alarm system. The installing contractor installs the system and certifies the system installation for code compliance at completion. There may be a professional engineer involved but not necessarily. (MGL C. 112 S. 81R) 1.4 FIRE PROTECTION SYSTEM a. There is no sprinkler system b. Fire Alarm System • The building is protected by an existing fire detection and alarm system in accordance with NFPA 72. Pull stations are located at • Information provided in this narrative is pursuant to the 7th edition of the Massachusetts Building Code 780 CMR 907.0 Building Owner City of Northampton 212 Main Street Northampton, MA 01060 Designer of Record of the Fire Alarm Fire Detection Systems Div Cebula Electronics Corp. 66 Main Street Chicopee, MA 01020 P: 413-594-7710 F: 413 - 594 -9866 MA 1194C Installer of the Fire Alarm Fire Detection Systems Div Cebula Electronics Corp. 66 Main Street Chicopee, MA 01020 P: 413-594-7710 F: 413 - 594 -9866 MA 1194C Date of Submittal: July 21, 2010 SECTION 1- BUILDING DESCRIPTION 1.1 BUILDING DESCRIPTION: a. General: • This is a two story building being used as a school. Renovations are to the basement only. b. Building Use Group • Use Group B. d. Area of the Building: 3800 SF. Per Floor • NARRATIVE REPORT FOR THE FIRE ALARM SYSTEM at Northampton Community Music Center 139 South Street Northampton, MA 01060 July 21, 2010 City of Northampton 4'�' r +,: "e Massachusetts f ' Z • r 4 ti t : . ' e LT a3XTMENI OF BUILDING INSPEC1IQlrS ? ' I ;= e W� rM 212 Main Street • Municipal Building vj t` ""� ' Northampton, MA 01060 rs i -D � C INSPECTOR Louis Hasbrouck Fax: 413 - 587 -1272 Building Commissioner Phone: 413- 587 -1240 Assistant Commissioner CONSTRUCTION CONTROL DOCUMENT (For professional Engineers/Architects responsible for Entire Project) Project Title: N CM,C' tower j.P eR(10 .7k Date: r t 1 Iq II r � Project Location:. i. ,.LL., cr. ., n . n . `c Qn .,r_. Map: Parcel: Zone: l V Scope of Project: I k L w+ retroa ob t� sei?Wrnb►-, le¢mMial 9'41[:1. I►rf�.riar .Par t�D�" ` Sv,tS In accordance with the sixth edition Massachusetts State Building Code, 780 CMR Section 116.0: I, ? €� E. Lfts7cyt ''1 Mass. Registration # tQ -S21 t , being a registered professional Engineer /Architect hereby CERTIFY that I have prepared or directly supervised the preparation of all design plans, computations and specifications concerning: ENTIRE PROJECT for the above named project and that to the best of my knowledge, such plans, computations and specifications meet the applicable provisions of the Massachusetts State Building Code, all acceptable engineering practices and all applicable Laws for the proposed project. Furthermore, I understand and AGREE that I shall perform the necessary professional services to determine that the above mentioned portions of the work proceed in accordance with the documents approved for the building permit and shall be responsible for the following as specified in Section 116.2.2: 1. Review of shop drawings, samples and other submittals of the contractor as required by the construction documents as submitted for the building permit, and approval for the conformance to the design concept. 2. Review and approval of the quality control procedures for all code required controlled materials. 3. Be present at intervals appropriate to the stage of construction to become generally familiar with The progress and quality of the work and to determine, in general, if the work is being performed In a matter consistent with the construction documents. I shall submit periodically, in a form acceptable to the building official, a progress report together with pertinent comments. Upon completion of the work, I shall submit to the building official a final report as to the satisfactory completion and readiness of the project for occupancy. \ ow) ARey Signatur e- 4 of Regi ed Professional c., s . t.A„ r A 7. f At. 0-6A e . a No. 5291`" shelbure Falk � y I 1 Day of J tJtry 20 tO ' Au �' (seal) o yke 4i rH of 0.- COOIj ZLZTLSSGCTt XVd 6C:TT OTOZ /OT/90 Versionl.7 Commercial Building Permit May 15, 2000 SECTION 10- STRUCTURAL PEER REVIEW (780 CMR 110.11) Independent Structural Engineering Structural Peer Review Required Yes 0 No SECTION 11 - OWNER AUTHORIZATION - TO BE COMPLETED WHEN OWNERS AGENT OR CONTRACTOR APPLIES FOR BUILDING PERMIT I, . / ►_ 0 1 G � - ���' C'' , as Owner of the subject property • hereby authorize �I 4 6 4 [ 1 to act on my behalf, in all ma ative to work authorized by this building permit application. jam- X85 — © o0 / Signature of Owner Date I, 4J - ' ( ( 4 , 4 . r " 7 , as Owner Authorized ) gent ereby declare that the statements and information on the foregoing application are true and accurate, to the best of my knowledge nd belief. Signed under the pains and penalties of perjury. IQ 6 g U zz 4 1 Print Nam 7 Sig of Owner /Agent Date SECTION 12;- CONSTRUCTION SERVICES / f.--1- :1--. ' 10.1 Licensed Construction Supervisor: n(�Not Applicable 0 Name of License Holder : IPI C' •1�A �ll "' w `�� "L-= License ber /b Addre -' Expirati n Date isix k 7 /5 — 7/ di4 ., ,e(9 Signature Telephone SECTION 13 -WORKERS' COMPENSATION INSURANCE AFFIDAVIT (M.G.L. c. 152, § 25C(6)) Workers Compensation Insurance affidavit must be completed and submitted with this application. Failure to provide this affidavit will result in the denial of the issuance of the bu permit. IP Signed Affidavit Attached Yes v.4 No 0 Versionl.7 Commercial Building Permit May 15, 2000 SECTION 9- PROFESSIONAL DESIGN AND CONSTRUCTION SERVICES - FOR BUILDINGS AND STRUCTURES SUBJECT TO CONSTRUCTION CONTROL PURSUANT TO 780 CMR 116 (CONTAINING MORE THAN 35,000 C.F. OF ENCLOSED SPACE) 9.1 Regiis_tere Architect: QT p a n Not Applicable s ❑ � { Name (Registrant): Ag- S 1 � `_ (� � 1 � r �� D �� � Registration Number Ad /��p Qi 20) Q � Q @ � -(,i 10 Expiration Date Signature V C Telephone 9.2 Registered Professional Engineer(s): Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date Name Area of Responsibility Address Registration Number Signature Telephone Expiration Date 9.3 General Contractor Not Applicable ❑ Company Name: Responsible In Charge of Construction / /1� `t A sT • N e le' -,'A -, -r N I o 1 d S 7 / r 73 j A /1 A � ' � � kg ; Signature ( ((J/ /') / J°OQ Telephone 9 _ ku , NL / *04, ( w" iH flTht t rr Versionl.7 Commercial Building Pe it May 15, 2000 8. NORTHAMPTON ZONING of K-r Q 14,M Existing Proposed Required by Zoni This column t b e d in by Building D ment Lot Size Frontage Setbacks Front Side L: R: L: R: Rear Building Height Bldg. Square Footage Open Space Footage (Lot area minus bldg & paved parking) # of Parking .. ces Fi . olume & Location) A. Has a Special Permit /Variance /Findin ever been issued for /on the site? NO 0 DONT KNOW YES Q IF YES, date issued: IF YES: Was the permit recorded at the Registry of Deeds? NO 0 DONT KNOW 0 YES 0 IF YES: enter Book Page and /or Document # B. Does the site contain a brook, body of water or wetlands? NO DONT KNOW Q YES 0 IF YES, has a permit been or need to be obtained from the Conservation Commission? Needs to be obtained 0 Obtained , Date Issued: C. Do any signs exist on the property? YES NO IF YES, describe size, type and location: D. Are there any proposed changes to or additions of signs intended for the property ? YES Q NO 8r IF YES, describe size, type and location: E. Will the construction activity disturb (clearing, grading ex ation, or filling) over 1 acre or is it part of a common plan that will disturb over 1 acre? YES Q NO IF YES, then a Northampton Storm Water Management Permit from the DPW is required. Versionl.7 Commercial Building Permit May 15, 2000 SECTION 4- CONSTRUCTION SERVICES FOR PROJECTS LESS THAN 35,000 CUBIC FEET OF ENCLOSED SPACE Interior Alterations ❑ Existing Wall Signs ❑ Demolition ❑ Repairs ❑ Additions ❑ Accessory Building ❑ Exterior Alteration ❑ Existing Ground Sign ❑ New Signs ❑ Roofing Change of Use ❑ Other CE' Brief Description ! W « i eq _bbl --Ptun b Of Proposed Work: pr 1(� 1 m�-- ec17s �^ �yy- ►�-.0 J ors ,.. fR„ 1^ v� 41' SECTION 5 - USE GROUP AND CONSTRUCTION TYPE USE GROUP (Check as applicable) CONSTRUCTION TYPE A Assembly ❑ A -1 ❑ A -2 ❑ A -3 ❑ 1 A I ❑ A -4 ❑ A -5 ❑ 1 B ❑ B Business ❑ 2A ❑ E Educational Nr 2B I ❑ F Factory ❑ F -1 ❑ F -2 ❑ 2C ❑ H High Hazard ❑ 3A ❑ I Institutional ❑ I -1 ❑ 1 -2 ❑ 1 -3 ❑ 3B ❑ M Mercantile ❑ 4 ❑ R Residential ❑ R -1 ❑ R -2 ❑ R -3 ❑ 5A ❑ S Storage ❑ S i - ❑ S-2 ❑ 5B U Utility ❑ Specify: M Mixed Use ❑ Specify: S Special Use ❑ Specify: COMPLETE THIS SECTION IF EXISTING BUILDING UNDERGOING RENOVATIONS, ADDITIONS AND /OR CHANGE IN USE p Existing Use Group: US/ G ' P roposed Use Group: T G Existing Hazard Index 780 CMR 34): Proposed Hazard Index 780 CMR 34): SECTION 6 BUILDING HEIGHT AND AREA BUILDING AREA EXISTING PROPOSED NEW CONSTRUCTION OFFICE USE ONLY Floor Area per Floor (sf) I A' N fpr 1st 1St 2 nd 2 nd 3rd 3r d 4 th 4th Total Area (sf) Total Proposed New Construction (sf) Total Height (ft) Total Height ft 7. Wat upply (M.G.L. c. 40, § 54) 7.1 Flood Zone Information: 7.3 Sewa•e r 'sposal System: Public Private ❑ Zone Outside Flood Zone Municipal ;.i On site disposal system • Version1.7 Commercial Building May 15, 2000 t City of Northampton Status of e L L U v 5 , ' r \ Building Department Curbcstiipriveway Permit 212 Main Street n tic Av I t Sew . er* i Room 100 Wat'Avail Si y ' Northampton, MA 01060 Two ets of plans phone 413- 587 -1240 Fax 413- 587 -1272 Plot/ itit Plar "' r , I °. s. � "; %5 Othel.$pfar -ify ' r : „ �; APPLICATION TO CONSTRUCT, REPAIR, RENOVATE, CHANGE THE USE OR OCCUPANCY OF, OR DEMOLISH ANY BUILDING OTHER THAN A ONE OR TWO FAMILY DWELLING SECTION 1 SITE INFORMATION This section to be completed by office 1.1 Property Address: ,�I IVO 1 n P� trill U 1`� ( Ma p" Lot Unit 7 6 , 0 /14 115'/'(' Zone Overlay District 139 Cery c* -4 ' Elm St. District CB District SECTION 2'- PROPERTY OWNERSHIP /AUTHORIZED AGENT 2.1 Owner of Record: deb 0 - 1 4 ° - - gX• .t► . le-e ciro t I3') $-oUDr Sr., _ N 0 R- - t, J Name (Print) Current Mailing Address: S • 400 / Signature Telephone 2.2 Authorized Agent: Vie^6 - )t-r Clituf /e6z- BUv (ft Bi± L%s sT.1 tv6F" ioleTot- Name (Print) Current Mailing Address —,) 1 , y ii , / )r it ) G,� r Signature / / I Telephone SECTIONS - ESTIMATED CONSTRUCTION COSTS Item Estimated Cost (Dollars) to be Official Use Only completed by permit applicant 1. Building i i 41t cc (a) Building Permit Fee 2. Electrical (b Estimated Total Cost of c��j . 0 0 v Construction from (6) 3. Plumbing -- Z) f w Bu Perm Fee 4. Mechanical (HVAC) 'j ' /0 000 r,. 5. Fire Protection / "..**--e) r �,. 6. Total = ( ' 2 + 3 • •� , Af Q 3 CC. sO Check Number " ..**-- e ) isiection For Official Use Only Bu' rig Permit Number Date Issued Signature; Building Commissioner /Inspector of Buildings Date pi Ce File # BP- 2011 -0060 APPLICANT /CONTACT PERSON f'LAt1s FD P SON WRIGHT BUILDERS ADDRESS/PHONE 48 Bates St NORTHAMPTON (413) 586 -8287 OK PROPERTY LOCATION SOUTH ST MAP 38B PARCEL 032 001 ZONE THIS SECTION FOR OFFICIAL USE ONLY: PERMIT APPLICATION CHECKLIST ENCLOSED REQUIRED DATE ZONING FORM FILLED OUT Fee Paid Building Permit Filled out 676 C) Fee Paid Typeof Construction: INSTALL REPLACEMENT WINDOWS,REMOVE INT PARTITIONS/DOORS,NEW FINISHES New Construction Non Structural interior renovations Addition to Existing Accessory Structure Building Plans Included: Owner/ Statement or License 84280 J 3 sets of Plans / Plot Plan THE FOLLOWING ACTION HAS BEEN TAKEN ON THIS APPLICATION BASED ON INF ATION PRESENTED: Approved Additional permits required (see below) PLANNING BOARD PERMIT REQUIRED UNDER:§ Intermediate Project: Site Plan AND /OR Special Permit With Site Plan Major Project: Site Plan AND /OR Special Permit With Site Plan ZONING BOARD PERMIT REQUIRED UNDER: § Finding Special Permit Variance* Received & Recorded at Registry of Deeds Proof Enclosed Other Permits Required: Curb Cut from DPW Water Availability Sewer Availability Septic Approval Board of Health Well Water Potability Board of Health Permit from Conservation Commission Permit from CB Architecture Committee Permit from Elm Street Commission Permit DPW Storm Water Management Demolition Delay 2-61 1 Signature of Building Official Date Note: Issuance of a Zoning permit does not relieve a applicant's burden to comply with all zoning requirements and obtain all required permits from Board of Health, Conservation Commission, Department of public works and other applicable permit granting authorities. * Variances are granted only to those applicants who meet the strict standards of MGL 40A. Contact Office of Planning & Development for more information.