Date of Test 10/10/11
Builder /Homeowner Christian Marks
Address 150 Prospect Ave
Test completed by Matt Turcotte
Test no11
Conditioned Floor Area 2261.4 Jsq ft Number of Stories L 2
Duct System 1 Duct System 2 (if installed)
Air Handler Installed? yes Air Handler Installed? 0
Duct Flow in CFM25 135 Duct Flow in CFM25 0
Pass or Fail? PASS Pass or Fail? 0
RESULTS of Rough-In Duct Leakage Test
Rough In Total Leakage Test at 25 Pascals
Total Leakage Test 5.97 CFM per 100 sq ft of conditioned floor area
Notes on Area Tested and /or Testing Conditions:
0
2009 IECC Minimum Requirements
Rough In Test with Air Handler Installed < 6 CFM per 100 sq ft of conditioned floor area
Rough In Test with NO Air Handler Installed < 4 CFM per 100 sq ft of conditioned floor area