18C-058 (3) CENTER FOR — 05F EcoTechnology we make green make sense sense Coristrtictiori Pe ac y `" s tirlg Doctirnerltatibri Date of Test 10/10/11 Builder /Homeowner Christian Marks Address 150 Prospect Ave Test completed by Matt Turcotte Test no11 Conditioned Floor Area 2261.4 Jsq ft Number of Stories L 2 Duct System 1 Duct System 2 (if installed) Air Handler Installed? yes Air Handler Installed? 0 Duct Flow in CFM25 135 Duct Flow in CFM25 0 Pass or Fail? PASS Pass or Fail? 0 RESULTS of Rough-In Duct Leakage Test Rough In Total Leakage Test at 25 Pascals Total Leakage Test 5.97 CFM per 100 sq ft of conditioned floor area Notes on Area Tested and /or Testing Conditions: 0 2009 IECC Minimum Requirements Rough In Test with Air Handler Installed < 6 CFM per 100 sq ft of conditioned floor area Rough In Test with NO Air Handler Installed < 4 CFM per 100 sq ft of conditioned floor area Questions about this Report? Contact Megan McDonough - Phone: 413 - 586 -7350 x221 - E -Mail: MeganM @cetonline.org