WATER system master plan update (2)CITY ®NORTHAMPTON
WATER SYSTEM
MASTER PLAN UPDATE
Prepared for:
The City of Northampton
Board of Public Works
By Dewberry, Inc.
July 2005
Edited by DPW Staff:
October 2005
TABLE OF CONTENTS PAGE
INTRODUCTION
GOAL OF THE REPORT
SCOPE OF WORK
WATER SYSTEM DEMANDS
GENERAL
POPULATION PROJECTIONS
WATER DEMAND PROJECTIONS
AVERAGE DAY DEMANDS
UNACCOUNTED FOR WATER
HISTORICAL PER CAPITA DAY WATER CONSUMPTION
PROJECTED RESIDENTIAL AVERAGE DAY DEMANDS
ESTIMATING PROJECTED SYSTEM WATER SUPPLY DEMANDS
PROJECTED TOTAL AVERAGE DAY DEMANDS
ESTIMATING MAXIMUM DAY DEMANDS
HISTORICAL MAXIMUM DAY DEMANDS
PROJECTED MAXIMUM DAY DEMANDS
PEAK HOUR DEMANDS
WATER STORAGE REQUIRMENTS
GENERAL
WATER STORAGE REQUIREMENTS
EQUALIZATION STORAGE
FIRE FLOW STORAGE
EMERGENCY STORAGE
ADEQUACY OF MAIN SERVICE STORAGE FACILITIES
CALCULATION OF EQUALIZATION STORAGE
CALCULATION OF FIRE FLOW STORAGE
ADDITIONAL STORAGE/SYSTEM REDUNDANCY DURING PEAK HOUR DEMANDS
SYSTEM STORAGE RELATIVE TO SYSTEM NEEDS AND HYDRAULICS
ADDITIONAL STORAGE/SYSTEM REDUNDANCY FOR MAXIMUM DAY AND
FIRE FLOW
LEEDS VILLAGE HIGH PRESSURE SYSTEM STORAGE REQUIREMENTS
ADEQUACY OF THE EXISTING DISTRIBUTION SYSTEM
GENERAL
RECOMMENDED FIRE FLOWS
HYDRANT FLOW TESTS
COMPUTER MODELING
HYDRAULIC ANAYLSIS
MAIN SERVICE SYSTEM
LEEDS VILLAGE HIGH PRESSURE SYSTEM
1
3
15
23
111 Dewberry TOC
RECOMMENDED IMPROVEMENTS
GENERAL
RECOMMENDED WATER STORAGE IMPROVEMENTS
RECOMMENDED PIPELINE IMPROVEMENTS
WATER MAIN CLEANING AND LINING
WATER MAIN REPLACEMENT
MISCELLANEOUS WATER MAIN REPLACEMENT
RESTRUCTURING OF MAIN SERVICE SYSTEM
RECOMMENDED IMPROVEMENTS TO LEEDS VILLAGE HIGH PRESSURE
SYSTEM
PHASED CAPITAL IMPROVEMENTS
GENERAL
CAPITAL IMPROVEMENTS
31
44
f Dewberry TOC
_ LIST OF TABLES
I PAGE_ .
2-1 PAST POPULATION
I~ 2-2 POPULATION PROJECTIONS
n 2-3 HISTORICAL AVERAGE DAY DEMAND BY USER CLASSIFICATION
`l
2-4 HISTORICAL PER CAPITA AVERAGE DAY DEMANDS
2-5 PROJECTED RESIDENTIAL AVERAGE DAY DEMANDS
2-6 PROJECTED TOTAL AVERAGE DAY DEMANDS
I_
2-7
HISTORICAL MAXIMUM DAY DEMANDS
2-8
PROJECTED MAXIMUM DAY DEMANDS
3-1
ESTIMATED FUTURE STORAGE REQUIREMENTS
4-1
2003 LARGE USERS
5-1
RECOMMENDED WATER MAIN CLEANING AND LINING
5-2
RECOMMENDED WATER MAIN REPLACEMENT
I] 5-3
RECOMMENDED CREATION OF LOW PRESSURE ZONE
6-1
J
INITIAL SYSTEM IMPROVEMENTS COST
6-2
PIPELINE IMPROVEMENT COSTS
U 6-3
I
MAIN SERVICE RESTRUCTURING IMPROVEMENTS COST
Dewberry
4
6
7
9
10
12
13
13
18
27
34
36
39
45
46
49
LOT
. Northampton, MA
SECTION I -INTRODUCTION
7/15/2005
In April 2004, the City of Northampton contracted with Dewberry-Goodkind, Inc. (Dewberry) to
update the City's existing WaterCAD Hydraulic Model and evaluate the Turkey Hill Tank and
related system improvements. These two tasks lent themselves to updating the City's Water
System Master Plan, which was previously completed in 1989. Dewberry has completed this
J update and the results of this task are presented in this report
t
GOAL OF THE REPORT.
lJl The goal of this report is to provide the City with the information necessary to implement a
phased program of improvements to its water system for a 20 year planning period by:
`J • Determining the adequacy of the City's existing water system to meet present and
projected domestic water demands, and
• Determining the Water System's ability to deliver required fire flows at adequate
f l pressures.
n To achieve these goals, Dewberry:
IJ - • Utilized an updated computer model to analyze and evaluate the City's existing water
system under various scenarios and demand conditions, including fire flows;
evaluated options to address immediate and future system deficiencies;
• Developed a prioritized plan of recommended improvements to eliminate these
r system deficiencies and
• Developed cost estimates for each recommended improvement.
j~ Scope of Work:
U 1. Review the water demand and population projections estimated in the 1989 Master
Plan and update the data for the next 20 year planning period using historical water
r 1 consumption data available from the City and the Regional Planning Commission.
r 2. Review system fire flow requirements estimated in the 1989 Master Plan and revise
data as necessary utilizing historical Insurance Services Offices data, industry
standards for fire protection and information provided by City officials such as the
Fire Chief.
Dewberry
Northampton, MA
7/15/2005
3. Impose updated present and future water demands on the calibrated model to
determine deficiencies in the distribution system during normal day-time demands,
peak-hour demands, night-time demands for refilling storage tanks, and maximum-
day demands with fire flows.
4. Conduct computer simulations using the calibrated model to evaluate alternatives to
improve the water distribution system and alleviate deficiencies previously identified
to meet both current and future water needs with respect to water supply, system
storage, and fire protection. This task will be a collaborative effort with the City to
ensure that all known concerns are addressed and that the necessary information to
develop practical recommendations for improving the water distribution system is
obtained.
5. Evaluate the adequacy of the existing water supply, distribution system and storage
facilities to meet future water demand requirements through the Year 2025.
6. Review the recommended improvements from the 1989 Master Plan with respect to
the City's water supply, distribution system and storage. Update and/or develop
alternative recommendations for the City to improve its water supply, distribution
system and storage, to alleviate deficiencies identified during the completion of the
hydraulic analysis and to meet present and future water demands through the Year
2025.
7. Develop recommendations to improve the existing operation and maintenance of the
City's water supply, storage and, distribution systems, to continue to meet water
demands through the year 2025.
8. Prepare cost estimates associated with the recommended improvements to the City's
water supply, storage, and distribution systems.
9. Prepare a prioritized, 20 year phased capital improvement program for the City to
implement the recommended improvements to its water supply and distribution
systems through the Year 2025. This program will be coordinated with the City's
fiscal budget.
1 Dewberry 2
L~
J
J
J
Northampton, MA
CTI®N II - WATER SYSTEM DEMANDS
7/15/2005
GENERAL
Water usage projections are utilized to assess the impact of future increases in water demands on
the supply, storage and distribution components of a system. The adequacy of a water system to
meet future water consumption needs is determinined by evaluating historic water consumption
data and projecting future system needs. This analysis establishes water usage trends which are
then used to estimate future water consumption based on population projections. The following
section presents an analysis of historic water consumption information and future water demands
based upon projected population and water usage through the study period of 2025.
U
d y
ti [l
Dewberry
3
Northampton, MA
POPULATION PROJECTIONS
7/15/2005
In order to develop a population projection for this report, the past population data for the City of
Northampton was reviewed. Past population figures for the last ten years, as reported by the
City, are shown in Table 2-1. The data shows a stable population with an actual reduction of
approximately 430 people over the last ten years.
TABLE 2-1
PAST POPULATION
Year
1993
Population
29,726
Pet-cent
_Change
N/A
1994
29,503
-0.76
1995
29,823
+1.07
1996
29,800
-0.10
1997
29,739
-0.21
1998
29,816
+0.25
1999
29,365
-1.54
2000
29,978
+2.04
2001
29,907
-0.24
2002
29,175
-2.50
2003
29,287
+0.40
12004
29,287
+0.00
With respect to future growth, both the Massachusetts Institute for Social and Economic
Research (MISER) and the U.S Census were contacted to assist in developing population
projections for the City. MISER and the U.S. Census have published similar population
projections for the City for the years 2010 and 2020 which are 29,118 and 29,136 persons,
respectively. These estimates do not anticipate any growth occuring in the the City over the next
20 years.
4 Dewberry j 4
Northampton, MA 7/15/2005
- According to the City's Office of Planning and Development, the Northampton State Hospital
has completed the permitting process and is proceeding with a redevelopment plan that will span
the next 15 years. Upon completion, as many as 300 residential units of varying size will be
added on the Hospital's grounds along with approximately 450,000 square feet of
commercial/retail space.
ii
D
11
J
Two additional developments well on their way to completion include Rocky Hill, a 32 unit
residential housing development, and Ice Pond, a 26 unit residential housing development. Both
are located near the intersection of Florence Road and Westhampton Road. The Oaks
development on Burts Pit Road, is another subdivision under construction, that must be
considered in determining the City's future water demand. Construction has just begun on this
development and, upon completion, will include 64 residential housing units. Of these 64, 12
will be on private wells due to fact that they are above an elevation of 320 feet.
In regard to future construction, the Office of Planning and Development has mentioned several
potential projects. The first is Bear Hill, a 55 year-old plus community housing development will
be comprised of 55 condominium type one and two floor units. This project is expected to enter
the construction phase in the near future. The second is Kensington Estates, a 12-15 unit
residential housing development located on Glendale Road. The developer is currently awaiting
a decision by the City as to whether the development will be supplied with City water or will
require the installation of private wells. The third is a 50 unit residential housing development,
under consideration, located near the intersection of Burts Pit Road and Florence Road.
}I' Dewberry
Northampton, MA
7/15/2005
Based on data published by MISER, for the year 2000, the average number of people per
household in the City of Northampton was 2.4. Assuming that the noted developments above are
completed within the study period to the extent planned, the City would experience an increase
of approximately 500 residential units and approximately 1,200 residents by 2025. Based on
current population figures, this would result in an overall growth of four percent. There are other
parcels of land available within the City which could support similar sized residential
developments in the future.
Considering the number of housing units currently planned to be completed, along with the
potential for additional residential developments to be completed within the study period, we
have projected a six percent total increase in the City's population to the year 2025. This
estimate results in a total population of approximately 31,044 people. A summary of the
projected population data is shown in Table 2-2. This percentage increase in poplation will be
used to project the fixture residential water demands as presented in the following section.
TABLE 2-2
POPULATION PROJECTIONS
Year
Projected
Population
2005(1)
29,287
2010
29,726
2015
30,165
2020
30,605
2025
31,044
(1) Year 2004 population of 29,287
assumed for year 2005.
10 Dewberry i 6
7/15/2005
Northampton, MA
WATER DEMAND PROJECTIONS
Average Day Demands
Average day demands are commonly defined as the total water supplied in one year divided by
365 days, expressed in millions of gallons per day (MGD). It includes water used for residential,
agricultural, commercial, and industrial consumption, as well as unaccounted-for water.
Historical average day water consumption data for the City of Northampton was obtained from
City records for years 1996 through 2004 and are presented in Table 2-3.
TABLE 2-3
HISTORICAL AVERAGE DAY DEMAND BY USER CLASSIFICATION
1996
3.22
0.16
0.04
0.02
0.19
3.64
1997
3.22
0.16
0.03
0.02
0.19
3.64
1998
3.25
0.17
0.04
0.02
0.19
3.67
1999
3.39
0.17
0.04
0.02
0.20
3.83
2000
3.24
0.16
0.04
0.02
0.19
3.66
2001
1.67
0.19
1.30
0.32
0.24
3.72
2002
1.62
0.22
1.25
0.09
0.19
3.37
2003
1.54
0.21
1.18
0.15
0.12
3.20
2004
1.55
0.21
1.19
0.15
0.12
3.22
(1) The user classification "Other" includes municipal, system flushing and miscellaneous usages.
!J As shown above, in Table 2-3, the total average day demand has decreased from the reported
1996 value of 3.64 MGD to the reported 2004 value of 3.22 MGD. The most significant
-l reduction was from the year 2001 to 2002 which can be attributed to a decrease in population,
and also an increase in water conservation due to a drought condition that occurred during this
period.
Table 2-3, also shows a considerable shift in residential, agricultural and industrial demand
usages that occurred after 2000 which can be attributed to changes in the accounting for the
residential, agricultural and industrial user classifications.
A review of historical records from 2000 to 2004 indicates:
That the combined industrial and agricultural water usage has remained relatively
consistent at approximately thirty-seven percent of the total average day demand;
Dewberry
7
Northampton, MA
7/15/2005
Commercial water usage has also remained quite constant over the same period
comprising approximately seven percent of the total average day demand.
Since 2000, the demands for the individal user classifications have been relatively stable with the
combined agricultural and industrial usage making up approximately thirty-seven percent of the
total average day demand, commercial usage making up approximately seven percent, and
residential usage making up approximately forty-eight percent. The remaining percentage of
usage includes municipal, system flushing, miscellaneous and unaccounted-for water usages.
The Northampton Water Department maintains individual meter reading records for all
residential, agricultural, industrial, and commercial water users in the City.
Unaccounted for Water
Unaccounted-for water within the system typically consists of water used for street cleaning,
hydrant flushing, leakage from the system, meter losses, and firefighting.
~n
The reported percentage of unaccounted-for water from 1996 to 2002 (inclusive) has been in the
range of 5 to 6.5 percent of the total water supplied and dropped to 3.7 percent of the total water
supplied to the system in 2003 and 2004. These percentages are considered very good when
compared to the generally accepted water works industry standard of 15 to 20 percent.
The City has undergone measures to reduce its unaccounted-for water including the completion
of a water audit to review record keeping and accounting methods, and the testing of large user
and source revenue meters, in 1994 and the subsequent completion of a leak detection survey of
the entire distribution system in 1995.
It is recommended that:
• The City consider continuing its efforts to reduce its unaccounted-for water such as
further leak detection efforts and customer meter replacement programs. This will be
of a higher priority when treatment of the City's water supply is implemented, since
the cost of water production per gallon will be higher.
4 Dewberry 8
-J
Northampton, MA
Historical Per Capita Day Water Consumption- - - - -
7/15/2005
The historical per capita day water consumption based on the noted approach of combining the
"Residential" and "Other" demand usages is shown in Table 2-4. The average per capita day
consumption for the years 1996 through 2001 was approximately 111 gallons per capita day
(gpcd). The average per capita day consumption for the years 2000 through 2004 was
approximately 91 gpcd. This reduction in per capita usages can be attributed to the previously
noted accounting changes made by the City with respect to residential, agricultural, and
industrial user classifications, and the water conservation methods implemented by the City to
address the drought condition that occurred during this period.
TABLE 2-4
HISTORICAL PER CAPITA AVERAGE DAY DEMANDS
0
0
0
1996
Residential
3.22
Other
0.02
1
Total
i i
3.24
Served
29,800
Consumption
1
108.7
1997
3.22
0.02
3.24
29,739
109.0
1998
3.25
0.02
3.27
29,816
109.7'-
1999
3.39
0.02
3.41
29,365
116.1
2000
3.24
0.02
3.26
28,907
112.5
2001
1.67
0.32
1.99
18,538(1)
107.3
2002
1.62
0.09
1.71
18,655(1)
91.7
2003
1.54
0.15
1.69
18,730(1)
90.2
2004
1.55
0.15
1.70
18,808(1)
90.4
(1) Base
d on number of residential service connections mul
tiplied by 2.5.
IJ
Water Usage Calculation Notes:
Changes to the method of calculating per capitamater consumption were made in
2001 based on DEP Policies with respect to the Water Management Act Program.
These changes are reflected in Table 3-4.
• There are a number of residents in Northampton who have private wells, and are not
connected to the City's water system. For this situation, where. a public water system
does not serve the entire commnunity, DEP allows such public water systems to
calculate per capita water consumption based on dividing the residential daily usage
by the number of residential service connections times a factor of 2.5 which
represents the DEP standard number of users per service connection. Since the City
falls within the noted category, calculations for per capita water consumption were
adjusted according to the allowable method.
9
01, Dewberry
Northampton, MA
7/15/2005
The estimates for the years previous to 2001 considered all of the City's residents to
be served by the water system which would tend to inflate the per capita consumption
value as well.
Public awareness of water conservation, for both economic and environmental
reasons, has increased in recent years due in part to efforts by municipalities and
regulatory agencies. For this reason, per capita water consumption should remain
relatively constant over the next twenty years. Therefore, for the purposes of
estimating future residential demands, we have assumed a value of 90 gpcd which
will remain constant throughout the study period.
Projected Residential Average Day Demands
To estimate fixture residential average day demands, a per capita day consumption based on past
water usage data is first determined. This amount is then multiplied by the projected population
served for a given year.
• For the purposes of this report, municipal, system flushing and miscellaneous water
usages, which were included as the user classification "Other" in Table 2-3 will be
added to the residential water usage to estimate per capita water consumption.
Based on previous population projections, the future residential average day demands for the
study period have been estimated and are presented in Table 2-5. As shown in Table 2-5, we
have applied the projected six-percent total growth in population to the current population served
for 2004 of 18,808 (as calculated based on the number of resident service connections times the
2.5 DEP factor). This will provide a more consistent and accurate estimate of residential
demands since it takes into consideration the fact that not all of the City's residents are connected
to the water system.
TABLE 2-5
PROJECTED RESIDENTIAL AVERAGE DAY DEMANDS
Projected
Per Capita([)
Projected
lZ
id
Year
Population
Consumption
es
ential
Served (2)
(G PC 1
(MGD)
2005
18,808
90
1.70
2010
19,090
90
1.72
2015
19,373
90
1.74
2020
19,655
90
1.77
2025
19,937
90
1.79
(1) Includes "Residential" and "Other" category demands.
(2) Based on applying projected growth to number of residential service
connections multiplied by 2.5 DEP factor.
Dewberry 10
l Northampton, MA 7/15/2005
Estimating Projected System Water Supply Demands
_I
To develop future water supply demand projections for the system, each component of the
^I average day demand including residential, commercial, industrial, agricultural, miscellaneous,
and unaccounted-for water usages is estimated through the study period.
i
As shown in Table 2-3, the unaccounted-for water usage over the past two years has been
approximately four percent of the total average daily water demand. Based on the City's past
efforts to address leak detection and the calibration of meters, and its on-going policies with
respect to water conservation, it is assumed that the unaccounted-for water will remain constant
throughout the study period at approximately five percent of the total water supplied.
Future commercial, industrial and agricultural average day demands will be estimated based on
past trends, and unaccounted-for demands will be estimated as a direct percentage of the total
residential, commercial, industrial and agricultural demands.
A major increase in industrial, agricultural and commercial demands is not anticipated to occur
through the study period given the current economic conditions and the fact that no specific
future developments are planned at this time. However, for the purposes of this report, we have
estimated that the combined industrial and agricultural demands as well as the commercial
demands will increase by approximately twenty-five percent of current demands by the year
2025. This will provide a conservative estimate for water supply planning and allow for some
potential growth within the commercial and industrial zones of the City.
401 Dewberry 11
Northampton, MA
7/15/2005
The future average day and maximum day demands estimated in this section will be used in the
following sections to evaluate the adequacy of the existing water system to meet future needs,
and to evaluate various improvements to the water system utilizing the City's computerized
hydraulic model which was updated as part of this study.
Projected Total Average Day Demands
Based on the projected residential water usage, and the criteria established for industrial,
agricultural, commercial, and unaccounted-for usages, the estimated total future average day
demands are as presented in Table 2-6.
TABLE 2-6
PROJECTED TOTAL AVERAGE DAY DEMANDS
!
Yea r
2005
Residential
1.70
Commercial
0.210
Agricultural/
Industrial
1.190
Unaccount 1-for
e(
0.120
Total
3.22
2010
1.72
0.223
1.264
0.160
3.37
2015
1.74
0.236
1.339
0.166
3.48
2020
1.77
0.249
1.413
0.172
3.60
2025
1.79
0.263
1.490
0.177
3.72
Estimating Maximum Day Demands
In determining the adequacy of the existing water distribution system, the available supply must
be capable of meeting the projected maximum day demands of the system. Maximum day
demand is defined as the highest one day demand which occurs during the year, and is
commonly expressed as a percentage of the average day demand.
2001 Maximum Daily Demand
Vs.
Permitted Daily Use &
Total Gallons Used for Year
Allowed: 4.77 million gal/day
24 hr record 2001: 5.34 million gal
Total use in 2001: 1.35 billion gal
1 Dewberry
12
Northampton, MA
7/15/2005
Historical Maximum Day Demands
Table 2-7 presents the reported historical maximum day water demands from 1996 through 2004.
1 As shown, historical maximum day demands have varied from 125 to 162 percent of the average
day demand, with an average maximum day/average day ratio of approximately 1.41.
1 TABLE 2-7
HISTORICAL MAXIMUM DAY DEMANDS
xi um Dav Maximum/
1996
3.63
lim"M
4.53
Vak
1.25
1997
3.64
5.35
1.47
1998
3.67
5.95
1.62
1999
3.83
5.62
1.47
2000
3.66
4.65
1.27
2001
3.72
5.34
1.44
2002
3.37
4.83
1.43
2003
3.20
4.70
1.47
2004
3.22
4.13
1.28
Projected Maximum Day Demands
For the purposes of this study, a maximum day/average day ratio of 1.50 was used to provide a
conservative estimate, and to ensure the City will be able to meet potentially high demand
periods. Based on this ratio, future maximum day demands have been estimated as shown in
Table 2-8.
TABLE 2-8
PROJECTED MAXIMUM DAY DEMANDS
Projected
Projected
te
Average Day
"
Day
Maximum Day
Year
e'
Demand
Demand
005
2
3.22
4.83
2010
r
3.37
5.05
015
2
3.48
5.22
2020
3.60
5.41
2025
3.72
5.58
Dewberry 13
Northampton, MA
Peak /lour Demands
7/15/2005
Peak hour demands are the highest hourly demands that occur during a 24-hour period and generally
occur in conjunction with the maximum day demand. Peak hour demands can vary anywhere from 1.5 to
6 times the average day demand, and therefore should be met through system storage. Consequently,
peak hour demands are considered when evaluating the adequacy of system storage and the ability of
system pipelines to deliver such demands.
Based on source meter records for the maximum day of usage from 2001 through 2004, the peak hour
demand was calculated to be approximately 1.3 times the maximum day demand. For the purposes of this
study, a peak hour demand/maximum day ratio of 1.50 was used to provide a conservative estimate for
evaluating system storage and capacity, and to ensure the City will be able to meet potentially high
demand periods. The impact of peak hour demands on system storage is discussed further in Section 3.
The impact of peak hour demands on the distribution system with respect to pipeline capacities is
discussed in Section 4.
111 Dewberry I 14
Northampton, MA
i
Q
n
I
SECTION 111 -'WATER STORAGE REQUIREMENTS
GENERAL
Distribution storage is provided to:
Meet peak demands of short duration;
7/15/2005
• Minimize pressure fluctuations during periods of demand changes in the distribtuion
system; and
• Furnish a reserve for fire fighting.
Storage may also serve to provide an emergency supply in case of temporary breakdown of
pumping facilities or major transmission main failure.
Required volumes of storage, denoted as "usable", are allocated at specific levels within a
storage facility to ensure the storage volume will be available at a hydraulic gradient adequate
for the intended purpose.
There are three components to consider when evaluating storage capacity:
The first is equalization storage. Equalization storage for meeting peak demands and hourly
demand flucuations should be provided at the top portion of the tank. The second, fire storage is
provided directly below. The third, emergency storage is a function of the system characteristics
and is allocated based on the assessed risk and need.
EQUALIZATION -
STORAGE LEVEL
FIRE --------------------------4
STORAGE LEVEL
EMERGENCY--------------- 4
STORAGE LEVEL
Example of how three components may be located in a
water storage tank
#1P Dewberry
15
Northampton, MA 7/15/2005
WATER STORAGE REQUIREMENTS
The following presents an analysis of the City's water storage requirements.
Equallzation Storage
Equalization storage is required to meet water system demands in excess of delivery capabilities
from pumping facilities. The volume of equalization storage needed depends on pump capacity,
transmission delivery, distribution system capacity, and system demand characteristics.
Equalization storage can be determined by developing a diurnal demand curve for the system
which identifies the duration of system demands in excess of maximum day demand and the
storage volume needed.
From the hourly demands recorded for the 2004 maximum day demand event, equalization
storage was calculated to be approximately 15 percent of the maximum day demand. Based on
our experience in designing and evaluating water system storage, we have estimated the future
equalization storage to be 20 percent of the maximum day demand projected for the system.
Using 20 percent, will provide a conservative estimate for planning and minimize the need to
operate pumping and/or treatment facilities above the maximum day demand for prolonged
periods of time. This will be particularly evident when the new water filtration plant is in service.
The City's current water system is fed via gravity whereby the source reservoirs provide supply
directly into the system. This provides a great amount of storage capacity for the City. With the
construction of the water filtration plant, this large source of storage will be reduced.
II Dewberry 16
Northampton, MA
Table 2-8; projected the City's maximum day demand for the year 2025 to be 5.58 MGD:- - -
Applying a factor of 20 percent, a volume of approximately 1.12 million gallons would be
required for equalization storage.
Fire Flow Storage
The amount of fire flow storage required, is based on recommedations of the Insurance Services
Office (ISO), which determines needed fire flows for insurance rating classifications of buildings
within the distribution system. Results of hydrant flow tests conducted by ISO in 1990 and more
recently in 2002 indicated needed fire flows ranging from 500 gpm for residential areas to 7,000
gpm for commercial areas.
According to the DEP, municipalities are only required to provide up to a maximum fire flow of
3,500 gpm for a three-hour duration. Any additional fire flow required is typically the
responsibility of the building owner. Therefore, based on a fire flow of 3,500 gpm at a duration
of three hours, a volume of approximately 630,000 gallons would be required for fire protection
L j 3,500 gpm x 60 minutes/hour x 3 hours).
Emergency Storage
Any storage provided within a tank beyond the volumes for equalization and fire flow storage is
~J considered emergency storage and would be available for pipeline breaks, equipment failures,
and other emergency situations. The volume required for emergency storage is a function of risk
with respect to an interruption of supply.
DEP guidelines recommend that municipalities provide emergency storage equal to the average
daily consumption if supply sources for a system are not equipped with sufficient standby power
nn to meet this consumption during a power failure, or lack system redundancy with respect to
Li pumps and/or pipelines. The previous 1989 report estimated the emergency storage volume
based .on this criteria which was appropriate considering the hydraulics of the existing water
J system at that time.
7/15/2005
For this report, we have estimated the future emergency storage to be 25 percent of the average
daily consumption. This will provide the City with some storage to offset the possible loss of
supplies and/or future pumping facilities without interrupting service for several hours.
Adequacy Of Main Service Storage Facilities
Based on the criteria presented for determining future storage needs, the estimated future storage
requirements for the City are shown in the Table 3-1.
441 Dewberry
17
Northampton, MA
TABLE 3-1
ESTIMATED FUTURE STORAGE REQUIREMENTS
MAIN SERVICE
7/15/2005
Under current operating conditions, with the continuous gravity feed from the Mountain Street
and Ryan Reservoirs, sufficient water is available to meet the storage requirements of the City.
As discussed above, upon construction of the new water filtration plant, the total combined
storage volume for the Main Service system will be approximately five million gallons (MG),
which includes the proposed clearwell/storage tank at the plant and the existing Turkey Hill tank.
However, all of this storage volume cannot be considered "usable".
Calculation of Equalization Storage
According to DEP Guidelines, equalization storage should be provided to customers under
domestic system demand conditions at a minimum pressure of 35 psi (81 feet of hydraulic head).
Thus, only the volume of water within a tank that will provide a pressure of 35 psi to the highest
service elevation can be considered usable equalization storage.
Based on the data utilized to develop the computerized system model, none of the Turkey Hill
tank's volume can be considered available for equalization. According to the City, the new
clearwell/storage tank's entire volume being available for equalization storage.
Calculation of Fire Flow Storage
For fire flow storage, DEP Guidelines define usable fire storage as the volume of water within a
storage tank that will provide a pressure of 20 psi (46 feet of hydraulic head) to the highest
service elevation in the system. Based on its diameter and overflow elevation, approximately
347,000 gallons are available within the Turkey Hill tank as usable fire storage.
Assuming that the required equalization storage will be entirely met by the proposed
clearwell/storage tank at the new treatment plant, approximately 56% of the total volume is
available for fire protection.
VI Dewberry 18
7/15/2005 ~
I 1 Northampton, MA
It appears that the City will have sufficient storage capacity to meet the projected
equalization, fire, and emergency storage volume.
j~ o However, system redundancy and its impact on supply can also affect the
LL available storage in the system, and need to be considered when evaluating
n storage.
Additional Storage/System Redundancy for Maximum Day and Fire Flow
J It is common practice to evaluate the adequacy of system storage together with supply to meet
anticipated maximum day and fire flow demands with the largest pump or source of supply, out
C of service. With both transmission mains in operation, adequate supply is available to satisfy
projected domestic and fire flow demands for the City's distribution system based on the
capacities of the mains. However, without both transmision mains in service, there may be a
n concern with respect to water supply. From conversations with City staff, one of the mains has
l been recently taken out of service for an extended period of time to conduct repairs so it is not
unreasonable to assume such an occurrence for planning.
The earlier 1989 study reported the capacity of one of the mains to be approximately 7.4 MGD
which accounted for it being cleaned and lined in 1958. Based on the scenario of meeting, the
j projected 2025 maximum day demand rate of 5.58 MGD in conjunction with the ISO fire flow
u requirement of 3500 gpm for three hours as established for the City, the total supply capacity
required would be approximately 10.6 MGD. This is approximately 3.2 MGD greater than the
capacity available through one of the mains, assuming that its capacity is still 7.4 MGD. For a
demand duration of three hours, a required usable storage volume of approximately 403,200
gallons would be required within the distribution system to compensate for the noted lack of
hydraulic capacity.
To supplement the transmission mains, the City also has two wells within the distribution
system, which are currently operated on a minimum basis. From discusions with City staff, it is
our understanding that these wells could potentially be used over a prolonged period of time to
compenstate for the loss of one of the transmission mains. The wells have rated production
capacities which would provide a combined capacity of approximately 1.9 MGD depending on
the system hydraulics and characteristics of the wells. For a three hour fire flow event, these
wells would supply an additional volume of approximately 234,000 gallons.
a • Considering the additional supply provided by the wells, the required usable storage
volume that is to be provided under the noted demand scenario would be reduced to
approximately 169,200 gallons.
0111 Dewberry
19
Northampton, MA 7/15/2005
Additional Storage/System Redundancy During Peak Hour Demands
The amount of distribution storage required to meet peak hour demands in a water system should
also be related to the maximum supply capacity of one of the mains. As disussed in Section 2,
for the purposes of evaluating storage needs with respect to supply capacity, the projected peak
hour demand has been estimated to be 1.5 times the maximum day rate. Based on the projected
maximum day demand for the year 2025 of 5.58 MGD, the estimated peak hour demand is
approximately 8.4 MGD which is 1.0 MGD greater than the available 7.4 MGD capacity of one
of the mains. For a peak hour demand period of two hours, the required usable storage to offset
the noted lack of capacity is approximately 84,000 gallons.
Coupled with the required usable storage volume of 169,200 previously estimated for the
maximum day demand with fire flow scenario, the total usable storage required to address the
loss of one of the transmission mains would be approximately 253,200 gallons. Considering the
347,000 gallons of available usable storage from the existing Turkey Hill Tank, the City would
not need any additional usable storage volume within the distribution system.
Based on system redundancy, it appears that the City has suffucient storage to
compensate for the loss of its major source of supply.
System Storage Relative to System Needs and Hydraulics
Another important factor to be considered when evaluating storage is its location with respect to
system needs and hydraulics. Based on the location of the new treatment plant clearwell/storage
facility, only partial benefits to the system with respect to equalization and/or stabilization of
pressure will be provided because of its distance from the point of major water usage, even with
both transmission mains in service.
Ideally, storage should be located at the extremities of a distribution system opposite
from supply sources.
Locating storage at the extremities of the distribution system would provide a more equalized
pressure distribution over the whole service area, and improve the coverage, or boundary of
service from each source of supply and storage. In addition, to be more effective, storage should
be located as close as possible to those service areas requiring high demand flows, preferably
within the proximity of large diameter water mains capable of delivering stored water during
peak demand and fire flow conditions.
Based on the criteria presented, Dewberry feels that the storage requirements for the
City's water system should be more evenly balanced between the future treatment
plant clearwell and another storage facility and/or facilities located within the
distribution system.
This approach will provide better pressure equalization for the system, and added operational
flexibility and redundancy for meeting peak hour and fire flow demands.
'1~ Dewberry ; 20
7/15/2005
~ Northampton, MA
As listed in Table 3-1, the City's future usable storage requirement for the year--2025 is estimated_
to be 2.68 MG. To provide a more balanced approach for system storage, and the additional
storage with respect to system redundancy and supply as discussed above:
At least 1.0 MG of usable storage should be provided directly within the distribution
system.
One alternative to address the estimated storage needs is to raise the overflow elevation of the
existing Turkey Hill tank. A detailed discussion on the hydraulics and impacts of this approach
to the system is presented in Section 5.
Leeds Village High Pressure System Storage requirements
i
The Leeds Village High Pressure System contains only one existing storage facility, an elevated
tank off Audubon Road.
n The Leeds Village High Pressure System is served via a pumping station, and not directly
connected to the storage facilities of the Main Service system, therefore, storage requirements for
the High Pressure System must be evaluated separately. The three components previously
discussed were used to determine the required usable storage.
0
Equalization
For equalization, using a value of twenty-five percent of the maximum day demand for the High
Pressure System (approximately six percent of total system maximum day demand), the required
usable equalization storage for the year 2025 is approximately 84,000 gallons
!J
4' Dewberry
Northampton, MA 7/15/2005
Based on the data utilized to develop the computerized system model, the highest service
elevation in the High Pressure System is approximately 460 feet NGVD which would require the
volume allocated for equalization storage to be provided above an elevation of 541 feet
• Since the overflow elevation for the Audubon tank is lower than the required
elevation of 541 feet, none of the tank's volume can be considered available for
equalization storage.
Fire Protection
For fire protection, the maximum required fire flow for the High Pressure System, as determined
by ISO in 1990, is 3,500 GPM for three hours at the Leeds Elementary School. This results in a
required usable storage for fire protection of approximately 630,000 gallons. Since the only
supply source, the booster pumping station, has no emergency power and relies solely on power
from utilities, emergency storage equal to the average daily consumption would be required for
the High Pressure System based on DEP guidelines.
For fire flow storage, with a maximum service elevation of 460 feet, the volume of water within
the tank required for fire protection should be above an elevation of 506 feet to be considered
usable.
Based on its dimension and overflow elevation, all of the tank's 200, 000 gallons is
available as usable fire storage.
With respect to supply, under current operating conditions, with no fire pump, a total volume of
54,000 gallons would be available from one of the two domestic service pumps at the booster
station for a three hour fire flow period.
It is our understanding that currently, to address the noted lack of fire protection, the fire
department may utilize a pumper truck to draw water from the Leeds Reservoir if needed.
Emergency Storage
The volume of emergency storage required for the year 2025 is approximately 223,000 gallons.
Therefore, the total usable storage required to meet the future needs of the High Pressure System
is estimated to be 937,000 gallons.
Considering the available storage from the existing Audubon Tank, the High
Pressure System would need an additional total usable storage of 683, 000 gallons.
Two alternatives to address the estimated storage deficit are:
• To upgrade the existing booster pump station with a larger capacity fire pump and an
emergency generator; or
To provide a fire loop connected off the Main Service system to serve the Leeds
Elementary School. A detailed discussion of this approach is presented in Section 5.
9.0 Dewberry i 22
il~
I~
ru
Northampton, MA 7/15/2005
SECTION IV - ADEQUACY OF THE EXISTING DISTRIBUTION
SYSTEM
GENERAL
To properly serve its residents, a water distribution system must be able to meet demands during
periods of peak consumption and provide adequate fire protection. Both peak demand conditions
and fire flows are typically met from system storage reserves and not by relying on supply
pumping.
The City's storage facilities have been assessed in the previous section with respect to storage
volume requirements and usable storage available. This section of the report will evaluate the
capability of the distribution system to deliver fire flows at adeqaute pressures for fire protection
during maximum day demands. This demand condition is considered to be the maximum amount
of water that a distribution system must realistically supply and has been established as a prime
criterion for the evaluation of water distribution systems. .
A hydraulic analysis was conducted utilizing the updated computerized distribution system
model completed by Dewberry as an earlier task, and available hydrant flow test results to''
evaluate the distribution system's ability to meet the above demand condition.
r.~
L J RECOMMENDED FIRE FLOWS
The Insurance Services Office Commercial Risk Services Inc. (ISO), has established certain
J standards by which the adequacy of a public water system to provide fire protection can be rated.
Fire flow requirements for a community are typically established for each type of development
within a community. The required flow rate and duration of flow for each type of development
are based on structural conditions, type of occupancy, and the congestion of buildings in the area
under consideration.
The largest fire flow demands generally occur in the major business and industrial districts of a
community. The ISO standards are used to set fire insurance rates within a community. In the
planning and design of a waterworks system, it is considered good practice to adhere to these
standards, not only to minimize fire insurance rates, but to reduce the risk of human casualties
and loss of property resulting from fires.
Based on ISO guidelines, recommended fire flows are defined as:
The required flow rate from a point in the system, while maintaining a minimum pressure
of 20 psi at all points in the distribution system.
• For one and two family residential areas, the ISO required fire flows range from
500 gpm to 1,500 gpm, depending on the spacing of the houses.
J
Il Dewberry
23
Northampton, MA
7/15/2005
For high-density residential, commercial, institutional, and industrial areas, the
maximum required fire flow to be sustained by the distribution system is 3,500
gpm.
• Individual site requirements greater than 3,500 gpm, which might exceed the
capacity of the distribution system, should be met through fire protection systems
provided by the property owner.
The ISO has also established time duration requirements for which fire flows should be
maintained to assess the adequacy of system storage. In general:
Required fire flows up to 2,500 gpm should be maintained for two (2) hours; and
Required fire flows up to the maximum 3,500 gpm should be maintianed for three
hours.
These ISO fire flow duration requirements were used in the previous section to evaluate the
adequacy of the City's storage systems to meet current and future storage needs.
HYDRANT FLOW TESTS
The ISO conducted hydrant flow tests in the City of Northampton to determine the water
system's ability to provide adequate fire protection in November 1990 and again in September
2002.
• It is apparent that portions of the existing distribution system are not capable of
providing adequate fire protection.
o It should be noted that improvements to the City's water system have been made
since the 1990 testing including the installation of a new transmission main which
has reduced the number of deficient areas as evident during the computer
analysis of the system.
o The City has conducted numerous hydrant flow tests, as recent as 2004, which reflect the
impacts of the system improvements made. The results of these tests were used in
conjunction with the ISO hydrantflow data to analyze the system and develop a balanced
computer model.
o Additional hydrant flow testing was conducted on the City's system on October 21, 2004
by Dewberry to further evaluate known problem areas and to collect needed data for the
purpose of analyzing, adjusting and calibrating the existing model. These tests were
conducted at night to minimize impacts to local residents.
V Dewberry 24
1 Northampton, MA 7/15/2005
i
~I
COMPUTER MODELING -
The computerized system model updated with the WaterCAD software program was used to
conduct hydraulic analyses of the distribution system. Various demand and operational
scenarios were simulated with the model to evaluate impacts to the existing system and develop
recommendations to alleviate deficiencies and meet future water needs. The existing computer
model and associated database was created as part of the Water System Plan in 1989 with the
KYPIPE software program. This computer model was based on a manually created schematic of
the distribution system and provided a somewhat skeletonized representation of the actual water
system.
The City recently began the process of converting this computer model into the WaterCAD
hydraulic software created by Heastad Methods, Inc. As part of this study, Dewberry completed
the population of the model database and integrated the new WaterCAD-based model into the
City's GIS program. The intent was to provide the City with a calibrated computerized model,
that is a true and accurate representation of the water system, which will serve as a much better
tool for evaluating existing and future needs.
Location of system components and pipe lengths were automatically configured and calculated
by the software during the creation of a map. Additional data that was-necessary for modeling
the water system was collected, tabulated, and manually input into the computer model.
Various sources were utilized to obtain the noted information for the computer model.
Information and reports on material composition of pipes, year of installation, and diameter was
provided by the City which was used to estimate the hydraulic capacity or roughness coefficient
I of the pipes in the system.
The roughness coefficient (C-value) for water main refers to the carrying capacity of the pipe
which varies with a pipe's age and material of construction, as well as its diameter. For example,
newer cement-lined ductile iron pipe has a smooth interior surface and tends to retain its original
capacity for many years where as older unlined cast-iron pipe is prone to corrosion and the
formation of turberculation over time. As a result, their carrying capacity tends to gradually
diminish over time.
Dewberry
25
Northampton, MA
New water pipe prior to installation
7/15/2005
c w
_ al y "'ry ~~t C+
Old water pipe removed from system
In addition, larger diameter mains tend to have higher carrying capacities than smaller diameter
mains since larger mains typically transmit greater volumes of flow and are well looped which
tends to prevent the buildup and accumulation of sediment and turberculation within the pipe's
interior.
Water demands were estimated using the 2004 average day demand of 3.22 MGD as shown in
Table 2-3 and assigned to junction nodes throughout the system. Large commercial, agricultural,
and industrial users were first identified, and their individual demands, as determined from City
meter records, were applied to the nearest node that best represents their actual locations within
the system. A list of these large users along with their representative nodes are shown in Table 4-
1.
The total large user demand was then subtracted from the average day demand. This remaining
demand was then distributed over the nodes throughout the system, taking into account the
population density and number of housing units at various locations along the pipe network.
HYDRAULIC ANALYSIS
As previously mentioned, hydrant flow tests have been conducted at various locations
throughout the distribution system by ISO, the DPW's Water Division, and Dewberry. The
results from the hydrant flow tests including static pressures, residual pressures, and flow were
simulated in the computer model. Adjustments to the computerized hydraulic model were made
until the results of the model simulations compared favorably to the hydraulic data collected
during the field tests.
At this point, the hydraulic model was considered to be calibrated and adequately representative
of the physical operating characteristics of the existing distribution system.
111 Dewberry 26
Northampton, MA
~I
n`
U
l
L~
(
_J
TABLE 4-1
2003 LARGE USERS
7/15/2005
User
Coca-Cola
MG/Yr
117.59
'Yo Usage
t~
I
9.55
GPM
223.73
Address
45 Industrial Dr.
Pro Corp. - PMC
33.49
2.72
63.72
11 Nonotuck St.
VA Medical Center
22.30
1.81
42.43
421 North Main
St.
Sunrise Care
7.44
0.60
14.16
548 Elm St.
Northampton Housing
Authority
6.66
0.54
12.67
81 Conz St.
Packaging Corp. of America
6.49
0.53
12.35
0 Island Rd.
Hampshire County Jail
6.19
0.50
11.78
205 205 Rocky Hill
Rd.
Old Way Leasing
5.90
0.48
11.23
23 Atwood Dr. .
Cooley Dickinson Hospital
5.36(2)
0.44
10.20
30 Locust St.
Hampton Ct. C/O Carmen Nie
5.17
0.42
9.84
20 Hampton Dr.
Star Northampton Inc.
4.85
0.39
9.23
36 King St.
Northampton School Dept.
4.56
0.37
8.68
380 Elm St.
Wastewater Treatment
4.25
0.35
8.09
33 Hockanum St.
Smith College
4.17,
0.34
7.93
0 Kensington St.
Perstorp Inc.
4.11
0.33
7.82
238 Nonotuck St.
(1) Percentages based on total consumption of 1,231,411,000 gallons in 2002.
(2) This usage was estimated from City billing records, prior to meters being installed.
After the calibration of the computerized hydraulic model, associated data to reflect estimated
water demands through the year 2025 was input into the model. The computer model was
subjected to various flow conditions to evaluate the adequacy of the distribution system to meet
future water requirements and to identify problem areas and system deficiencies.
Improvements to the distribution system were then made in the model to evaluate their impacts
and to develop recommendations for alleviating the noted deficiencies within the Main Service
and Leeds Village High Pressure Systems. The computer model was also used to assess the
operational alternative of creating a separate low pressure zone to reduce the high system
pressures being experienced in the downtown area, and to assess the hydraulic impacts of raising
the Turkey Hill tank as discussed in Section 5.
111 Dewberry
27
Northampton, MA
The overall results of the hydraulic analysis:
7/15/2005
Indicate that the system is adequate under average day and maximum day demands,
However:
There are several areas in the system which are unable to provide the required fire
flows as rated by the ISO, mainly due to the presence of undersized and/or unlined
mains that serve these areas; and
• The downtown portion of the system experiences pressures as high as 135 psi
which exceeds the DEP recommended range of 35 psi to 110 psi for distribition
systems.
These extreme pressures can result in:
• Excessive leaking/unaccounted-for water;
Water hammers; and
System surges, leading to water main breaks.
Improvements will be required to provide adequate fire protection for those areas found to be
deficient and to address the excessive system pressures. These will be discussed in more detail
in Section 5.
Main Service System
The Main Service system is capable of meeting:
Average day;
Maximum day; and
Peak hour demands.
However, under maximum day demands with imposed fire flows:
• The system is not capable of delivering the required ISO fire flows at the minimum 20
psi pressure to several residential and commercial districts as determined from the
computer model.
1111 Dewberry 1 28
Northampton, MA 7/15/2005
Areas of concern include the following:
• Upper end of North King Street
• Bridge Road from Chestnut Street to Damon Road
• The Lower end of Mt. Tom Road
• Elm Street at Green Street
• The End of Westhampton Road at Glendale Road.
These areas of concern, listed above, are served by unlined and inadequately sized cast-iron
mains which reportedly have low C-values and minimal carrying capacity. These mains are
hydraulically incapable of delivering the fire flows while maintaining the minimum pressure of
20 psi required for adequate fire protection.
• They should be cleaned and lined and/or replaced with larger transmission mains to
better serve these areas.
Another area of concern is the extreme system pressures maintained in the Main Service System.
Due to the varying topography being served, pressures range from as low as 28 psi at the upper
_ end of the system to as high as 135 psi in the lower lying downtown area. Fortunately, the
higher pressures being served are primarily concentrated within the eastern section of the City
and based on the physical characteristics of the system, can be isolated through installing
pressure-reducing valves to the create a separate pressure zone. The creation of a such a zone is
further discussed in Section 5.
Leeds Village High Pressure System
The Leeds Village High Pressure System is capable of meeting:
• Average day; and
• Maximum day demands.
However, under maximum day demands with imposed fire flows:
y • The system is not capable of delivering the required ISO fire flow of 3,500 gpm at the
minimum 20 psi pressure for the Leeds Elementary School, which is located on
J Florence Street.
• In addition to the school, there are several other commercial businesses within the
High Pressure System including Chartpak Industrial on Mulberry Street and
Berkshire Cable on River Road.
o It is likely that the fire flow requirements for these businesses cannot be
provided as well.
29
V Dewberry
Northampton, MA
7/15/2005
The High Pressure System contains small unlined mains which restrict flow and are incapable of
delivering the required fire flows to the school and other commercial users.
The existing booster pumping station is sized to provide domestic service only and is not
equipped with fire pumps. In addition, as discussed in Section 3, the existing storage tank does
not provide sufficient usable storage volumes for fire protection or equalization.
Alternatives to improve fire protection for the High Pressure System include:
• Upgrading the existing booster pump station with larger capacity fire pumps; andlor
• Providing afire service connection to the Main Service system to meet the fire flow
requirements for the school.
These and other upgrades to the system are further discussed in Section 5.
,4d
D
YYY
r'~e ~
Y
s h`
t
Water main construction
as
' 01
11 Dewberry
30
Northampton, MA
0,
~J
SECTION V - RECOMMENDED IMPROVEMENTS
GENERAL
7/15/2005
The previous sections of this report have presented the existing conditions and analysis of the
City's water system and have identified various deficiencies in meeting current and projected
future water demands. This section of the report presents the recommended improvements to
address these deficiencies based upon review of existing records, results of the hydraulic analysis
conducted with the computer model, and from discussions with City personnel.
RECOMMENDED WATER STORAGE IMPROVEMENTS
The City's current reservoir supply system provides a significant amount of storage volume due
to the direct connection with the distribution system.
With the construction of the new water filtration plant in Williamsburg, the required storage
volume for the City's system will be provided primarily through the new clearwell. Even though
the capacity of the new clearwell will be sufficient with respect to storage volume:
• Its supply availability will rely solely on the hydraulic capacity of the existing dual
transmission mains.
Based on the hydraulic analysis conducted, with the newer transmission main out of service:
• It was noted that insufficient capacity is available through the older transmission main to
deliver the high flows required during peak hour demands, and provide adequate fire
protection by itself.
However, by utilizing the City's two well supplies to offset the loss of the newer transmission
main, the total required capacity can almost be provided to meet the worst-case demand
I
scenarios as imposed on the system.
Another concern with respect to the storage being provided by the new clearwell is its location in
proximity to the distribution system. The significant distance between the clearwell and the high
demand areas within the system will limit its effectiveness in adequately providing equalization.
To provide more effective storage and system redundancy, it was recommended that
approximately 1.0 MG of additional usable storage be provided within the limits of the
distribution system.
410 Dewberry
31
Northampton, MA
To accomplish this approach:
7/15/2005
• It is recommended that the existing Turkey Hill Tank be raised to an overflow elevation
equal to at least the current system gradient.
Increasing the overflow elevation of the tank will provide approximately 1,000,000 gallons of
total usable storage at the far end of the system, and will allow the tank to properly fluctuate off
the system thereby reducing concerns regarding stagnant water.
This will improve localized fire protection within the service area of the tank and provide better
pressure equalization for the system.
Based on the analysis conducted, with a higher overflow elevation:
• The Turkey Hill Tank is expected to turnover approximately every five to seven days,
depending on system demands.
o This is a typical rate of turnover for water storage tanks, and should be sufficient
to avoid potential problems with stagnation and water quality, particularly when
the new treatment facility comes on-line.
o To further enhance the circulation of the tank, a tank mixing system consisting of
an internal riser pipe with separate inlet and outlet assemblies is recommended as
part of upgrading the tank. This system will draw water for system usage from
the lower portion of the tank, and fill the tank from the system through the top
portion of the tank; which will optimize tank circulation and further reduce the
potential for stagnant water.
As water quality regulations become more stringent, and changes with respect to treatment and
system operations are made, it may be desirable in the future to increase the turnover rate for the
Turkey Hill Tank.
One approach that the City could easily implement for this purpose:
• Is to provide a control system atone of the PRV stations, designed to periodically throttle
backflow from one of the transmission mains which would then allow the Turkey Hill
Tank to fluctuate more frequently as needed.
o This control scheme could be automated through the SCADA system at the new
treatment facility.
It should be noted that the recommended storage improvements presented herein are based on the
fact that:
• The City will continue to maintain and operate the two existing well supplies which, as
noted previously, are required to offset the lack of storage redundancy within the
distribution system upon loss of the one of the transmission mains.
4 Dewberry 32
i
Northampton, MA 7/15/2005
The results of the hydraulic analysis:
• Confirm that one of the transmission mains alone cannot provide adequate supply for
peak hour demands and fire flows without the wells in service, particularly within the
downtown area, even with the added storage from raising the Turkey Hill Tank
o The Turkey Hill Tank is approximately four miles from the downtown area which
is a considerable distance away.
o Stored water within the tank cannot be efficiently delivered to this part of the
distribution system due to hydraulic losses through the connectingpipelines.
o If the well supplies are permanently taken off-line for any reason in the future, the
City will need to consider providing up to 0. S MG of additional storage within the
distribution system, preferably in the downtown high demand area, to compensate
for the loss of the well supplies.
RECOMMENDED PIPELINE IMPROVEMENTS
As discussed in Section IV, results of fire flow testing conducted by the ISO indicates that
several areas of the system have inadequate fire protection. From the computer modeling and
analysis, these areas were noted to be served by older, unlined mains which have a reduced
hydraulic capacity due to the buildup of tuberculation. Also, some areas were found to have
undersized mains which exhibited high headlosses under peak demand and fire flows. The water
main improvements recommended herein have been selected based upon the following criteria:
• Alleviate fire flow deficiencies;
• Increase water transmission; and
• Looping to eliminate dead ends and improve water quality
From discussions with City staff, some of the recommended pipeline improvements presented
are currently being completed, or are planned to ' be completed in the near future. These
improvements have been noted accordingly in the following tables.
Water Main Cleaning and Lining
7 There are a large number of older cast iron water mains which are suspected to be unlined. The
tuberculated and pitted interior surfaces of unlined mains can promote problems such as
discoloration, increased disinfection demand, and high pipeline head losses.
I~
040 Dewberry 33
Northampton, MA
7/15/2005
The Water Department maintains a list of water main installation dates and materials, as part of
the City's GIS program, for a majority of the existing water mains. This information was
utilized in the development of the computer model and subsequent analysis conducted to
evaluate the distribution system. Table 5-1 presents the recommended water mains to be cleaned
and lined based on providing adequate fire protection and eliminating possible restrictions due to
high pipeline head losess.
TABLE 5-1
RECOMMENDED WATER MAIN CLEANING AND LINING(')
Location
North King St.
From
Hatfield St.
To
Laurel Park.
Size
(Inches)
10
Length
(Feet)
5,000
Hatfield St.
North King St.
Cooke Ave.
10
1,600
Cooke Ave.
Hatfield St.
Bridge Rd.
10
1,200
Bridge Rd.
North Main St.
Industrial Dr.
12
13,250
King St.
Damon Rd.
Barrett St.
12
1,750
King St.
Barrett St.
Main St.
10
5,500
Pleasant St.
Holyoke St.
Wright St.
12
1,100
Wright St.
Pleasant St.
Conz St.
12
500
Conz St.
Wright St.
Pleasant St.
12
775
Pleasant St.
Conz St.
Atwood Dr.
12
3,000
Federal St.
Nonotuck St.
Washington Ave.
16
4,600
Washington
Ave.
Federal St.
Dryads Green.
16
400
Dryads Green.
Washington
Ave.
Paradise Rd.
16
1,300
Paradise Rd.
Dryads Green.
Elm St.
16
1,000
Elm St.
Paradise Rd.
College Lane.
16
520
College Lane.
Elm St.
Green St.
16
2,000
Earle St-(2)
Grove St.
the north
12
800
Grove St.
Chapel St.
Earle St.
10
2,500
Grove St.
Earle St.
South St.
12
1,000
Main St.
Pleasant St.
West St.
16
1,700
West St.
Main St.
Green St.
16
500
(1) The actual conditions of these water mains should be verified through coupons, or
conducting C-value tests, prior to cleaning and lining.
(2) This main is scheduled for replacement as part of State Hospital build-out project.
4 Dewberry 34
Northampton, MA 7/15/2005
A majority of these pipelines are larger-sized unlined transmission mains which were noted to
have apparent low C-values during the balancing of the computer model. As noted in Section 4,
~I the C-values for these mains were initially determined based on pipeline age and material, and
further adjusted in the model to simulate the results of hydrant flow tests to develop a calibrated
model for predicting future needs.
The model cannot differentiate hydraulic losses that are caused by either low C-values or other
possible restrictions within a pipeline, such as partially closed valves. Both conditions can
produce similar results with respect to flows and pressures, particularly over long pipeline
lengths.
• Prior to scheduling these mains for cleaning and lining, field verification should be
made, either from taking a coupon or conducting C-value tests in the field, to determine
their actual physical condition and if the main, indeed, needs to be cleaned and lined.
Water Main Replacement
Pipelines have been recommended for replacement in areas where inadequate fire flows were
noted or where the evaluation of the distribution system identified the need for a larger main to
I~ improve system hydraulics. Also, there are portions of the distribution system which consist of
IF_,1 dead-end mains and are subject to inadequate flows and poor water quality. Table 5-2 presents
the water mains recommended to be replaced to provide a more efficient flow of water
throughout the distribution system and eliminate dead ends.
~J
35
Dewberry
Northampton, MA
TABLE 5-2
RECOMMENDED WATER MAIN REPLACEMENT
7/15/2005
Present Proposed
Location From To Size Lenoth
Size
(Feet)
i
h
I
(
nc
es) (
I nches)
REPLACEMENT WATER MAIN
Westhampton
Westh~
Glendale Road
Florence Road
8
12
14,000
Rocky Hill Road
Florence Road
Old Wilson
8
12
3
000
Road
,
Glendale Road
Westhampton Road
South on
6
8
1
800
Glendale Road
,
Burts Pit Road
Redford Drive
Rural Lane
8
12
400
West Farms Road
Ryan Road
Westhampton
8
12
3
900
Road
,
Ryan Road
Florence Road
Clark Street
10
12
1,600
Coles Meadow
Road
North King Street
Marian Street
8
12
400
South Street
South Park Terrace
Charles Street
6
8
1,000
Earle Street (2)
West Street
South on Earle
6
12
800
Street
NEW WATER MAIN
Damon Rd.
Old Water St. Bridge St. N/A 12
1,400'~3~
(1) This main is scheduled for replacement as part of the MHD reconstruction project.
(2) This main is scheduled for replacement as part of the State Hospital build-out project.
(3) Length as determined by the City - completed September 2005.
According to the City, the Massachusetts Highway Department (MA Highway) is planning to
reconstruct Westhampton Road (Rt. 66) within the next couple of years. Part of that
reconstruction will include replacing the existing 8-inch cast iron main within the roadway that
extends from Old Wilson Road to Glendale Road. This pipe has been recommended for
replacement as shown above in Table 5-2. It is our understanding that the size of the
replacement main is proposed at this time to be 8-inches.
36
Dewberry
Northampton, MA 7/15/2005
As shown in Table-5=2, Dewberry-has-recommended-that a 12-inch main be provided for several
reasons:
• First, this water main is one of the cross-city mains along with the 12-inch main in Ryan
Road that serves the southwest portion of the system, including the Turkey Hill Tank.
o Coupled with the recommended improvements on West Farms Road and Ryan
Road, a 12-inch main in Westhampton Road will provide an important redundant
link between the downtown area and the Turkey Hill Tank, in addition to creating
an improved transmission loop for the existing system.
• Secondly, the results of the computer analysis indicates that a 12-inch main would
greatly improve fire protection for the existing residents along Westhampton Road and.
on Glendale Road, which currently is inadequate.
• Thirdly, the inherent capacity of a 12-inch main would be more beneficial for the
operation of the Turkey Hill Tank once it is raised as recommended. .
• Finally, based on its overall length and physical location, this pipeline will function more
like a transmission main for this section of the system as opposed to a service main, and
therefore, its diameter should really be no smaller than 12-inches.
Miscellaneous Water Main Improvements
According to City records, there are a number of 8-inch diameter and smaller unlined water
mains scattered throughout the distribution system. These unlined mains can lead to a reduction
in water quality, plugged servcies and produce flow restrictions in the system.
It is recommended that the City:
J • Develop a continuing pipeline improvements program to replace and/or clean and line
these mains.
o This will improve water transmission and water quality throughout the system, as
~J well as localized fire flows.
o Cleaning and lining should restore the carrying capacity of these mains to a level
almost equal to their original capacity, thus increasing the useful life of these
Li mains.
o It is typically less expensive to replace mains 6-inches or less than to clean and
line them. However, there are conditions where replacement would be difficult
due to the proximity of other mains or utilities and cleaning and lining would be a
better alternative.
If 37
If Dewberry
Northampton, MA
7/15/2005
When improving or upgrading the distribution system, the proper size selection and location of
water mains and the manner which they are incorporated into the system are important factors in
providing adequate flows and pressures. As a rule of thumb:
• Any water main that extends up to 1, 000 feet in length without a cross connection should
have a minimum diameter of 8-inches.
• For lengths less than 500 feet, the minimum pipe diameter may be reduced to six-inches if
the water main is used to complete a water main loop and the required fire flow is
minimal.
• For pipeline lengths greater than 1, 000 feet that have no cross connections, the minimum
pipe diameter should be 12-inches.
Wherever possible:
• Dead ends should be eliminated by looping or interconnection; and
• All water mains should be cross-connected at reasonable intervals.
• In addition, the system should not contain any "bottlenecks" in which a smaller water
main is the sole means of transporting water between larger mains.
A review of the distribution system map shows that there are several short segments of smaller
unlined mains which are situated between larger mains. Also, based on the recommended water
main replacements, other similar short segments will be created.
• These sections of main should be replaced with mains equal in size to the connected main
to eliminate possible flow restrictions and/or "bottlenecks. These segments include:
o Replace 400 feet of 8-inch main in Burt's Pit Road with 12-inch main
o Replace 1,250 feet of 6-inch main in North Street with 8-inch main
o Replace 1, 600 feet of 10-inch main in Ryan Road with 12-inch main
RESTRUCTURING OF MAIN SERVICE SYSTEM
As mentioned in Section 4, the lower lying downtown area of the City served by the Main
Service system is under extreme system pressures, as high as 135 psi, based on the service
elevations. Although no regulation has been established:
• It is generally accepted that pressures at street level exceeding 110 psi are considered
excessive.
Such pressures can increase leakage and breakage of water mains and services, and require a
higher level of maintenance. The effects of water hammers are also more pronounced at higher
system pressures.
0 Dewberry 38
Northampton, MA 7/15/2005
' The City has historically experienced a high incident of breaks in this part of the system. A -
review of the City's water system indicates that the lower service elevations are concentrated
within one particular section of the system.
i I • A separate pressure zone could be created by installing pressure-reducing valves
(PRVs) at critical locations which will isolate the section and allow the system pressures
to be reduced to a more practical range. Based on the results of the computer analyses
conducted to evaluate this alternative, it is recommended to install four PRV stations.
Each station should include two PRVs:
• One sized for domestic service; and
• One sized for fire flows as well as by-pass piping.
In order to restructure the Main Service system as recommended, several water main
i improvements will need to be completed. Table 5-3 summarizes the improvements for creating
the recommended Low Pressure Service System. The creation of the recommended Low
Pressure system does not impact the effectiveness of the other recommended system
- improvements, and can be completed independently or in conjunction with other system
improvements.
TABLE 5-3
RECOMMENDED CREATION OF LOW PRESSURE ZONE
U
~I
LA
Size Length
Location From To (inches) (Feet)
NEW WATER MAIN
Liberty Street
Lexington
Warner Street
8
800
Avenue
Warner Street
Federal Street
Maplewood
Terrace
8
2,300
Maplewood
Hinckley Street
Warner Street
8
1,400
Terrace
Hinckley Street
Maplewood
Nonotuck Street
8
700
Terrace
In addition to the extreme system pressures experienced within the Main Service system, there
are several areas which, due to their high service elevation, are below or barely at the
recommended minimum system pressure of 35 psi under normal demand conditions.
Based on the computer analyses, it is recommended that:
• The City encourage private%wner installation of individual booster pumps to existing
services above 340 feet.
Dewberry
J
39
Northampton, MA 7/15/2005
Another approach to further improve pressures throughout the system:
• Is to raise the current hydraulic gradient of the Main Service System.
o This will be possible with the creation of the recommended Low Service System and
the construction of the new water filtration plant.
o Based on the reported operating ranges for the water treatment plant clearwell, the
current gradient maintained in the Main Service system could be increased by 10 to
15 feet, or approximately 5 psi.
o This increase in pressure will improve flows into the higher elevated areas and
provide additional fire protection for the Main Service System.
To increase the gradient of the Main Service system, additional improvements will be needed for
the Turkey Hill Tank. As previously discussed:
• It was recommended to raise the overflow elevation of the tank to the current system
gradient to provide more usable storage and allow the tank to properly fluctuate off the
system.
o Raising the current gradient by 10 to 15 feet as proposed will result in the Turkey Hill
tank being hydraulically isolated again from the system.
To allow the City the flexibility to increase the Main Service system gradient, Dewberry
recommends:
• Raising this tankfurther to an overflow elevation which is 40 feet higher than its current
overflow elevation.
o Tank shells come in 8 -foot increments and adding tank height by a factor of 8 is
typically more cost-effective. With respect to storage volumes, operating the tank at a
40 foot higher gradient will provide an additional 250, 000 gallons of usable storage
within this section of the system
The only concern that needs to be considered with raising the operating gradient of the Main Service
system is the impact to the older existing transmission mains within the City's system including:
• The older transmission main that extends from Williamsburg into the Leeds Service area.
• The main that extends from Leeds to Spring Street, and to Elm Street.
• The 16-inch main that extends from Leeds, into North Main Street and eventually Locust
Street.
411 Dewberry 40
Northampton, MA 7/15/2005
These mains are over 100 years old and consist of lead-caulked joints which are prone to leaking.
Any increase in system pressure should be done gradually to minimize breakage and allow these
mains to slowly adjust. Still, there could be incidents of water main breaks and repairs. It is
recommended that:
- l • Prior to increasing the hydraulic gradient of the Main Service System, the City conduct
an investigation of the valves for these mains to identify which valves are operational and
which valves should be replaced to isolate the mains for emergency repairs as needed
o Additional valves and cross-connections may need to be installed to assist in
isolating certain sections.
RECOMMENDED IMPROVEMENTS TO LEEDS VILLAGE HIGH PRESSURE
SYSTEM
As with the Main Service system, there are areas of the Leeds Village High Pressure System
which cannot be provided with the recommended minimum system pressure of 35 psi from the
overflow elevation of the Audubon Tank due to their service elevations, particularly along the
upper portion of Audubon Road. These higher elevations are also responsible for the
equalization storage deficit noted in Section 3. Based on the computer analyses, it is
recommended that:
• The City encourage the installation of individual booster pumps to existing services
above 440 feet.
o This recommendation will improve system operations and address the
equalization storage deficiency.
As previously discussed, the Leeds Village High Pressure System cannot provide adequate fire
protection, primarily due to the ISO fire flow of 3,500 gpm needed for the Leeds Elementary
School located on Florence Street. This system is primarily designed for residential usage and
demands, consisting of only small unlined mains, which are not adequate for delivering the
required fire flow to the school.
In addition, both the existing booster pumping station and storage tank are not sized to meet such
a demand as needed for the school. Also, there are other commercial establishments within the
system including Chartpak Industrial and Berkshire Cable, which require higher flows for fire
protection.
Currently, it is our understanding that the City's fire department may address the noted supply
J deficiency by utilizing the Leeds Reservior to draw/pump additional supply for fire protection
when needed.
41
0.11 Dewberry
Northampton, MA
7/15/2005
One alternative to address the estimated storage deficit discussed in Section 3, and provide a
more reliable means of fire protection for the system is to upgrade the existing booster pump
station with:
Larger capacity fire pumps; and An emergency generator
These two items will greatly reduce the need for emergency storage and alleviate a portion of the
storage deficit for the High Pressure System.
Another consideration to meet the fire flow requirements for the Leeds Elementary School is:
• To extend a water main from the Main Service system up to the School site to provide a
fire service loop including hydrants.
o Based on the location of the School and its proximity to the Main Service system,
this connection would be physically feasible from the 16-inch main either at Main
Street, or towards the end of Florence Street.
o A connection to the main on Haydenville Road is also possible, but this would
require a greater length of water main, and easements to cross private property.
This fire service connection will greatly reduce the storage deficit for the High Pressure System
as discussed in Section 3, and will provide the needed fire flows for the school without having to
conduct significant upgrades to the existing booster station and storage tank.
It is therefore recommended that:
• The City include this fire loop connection to the 16-inch main as part of its improvement
program.
There are also two other known commercial establishments that need to be addressed with
respect to fire protection including Chartpak Industrial on Mulberry Street and Berkshire Cable
on River Road. Both of these sites are served by small existing mains.
One alternative is to install a large capacity fire pump at the existing booster pump station as
stated above. Another consideration is to utilize the existing Main Service system to provide the
1111I 'Dewberry 42
Northampton, MA 7/15/2005
I- needed fire flows similar tothe school site. The existing transmisson main thatenters the Leeds
1 Village High Pressure System parallels the two smaller mains.
• Hydrants could be installed on the transmission main near each of the sites to allow the
Fire Department to draw directly from the Main Service system to provide the needed fire
protection.
o This is a relatively low cost solution and will eliminate the need to provide a large
capacity fire pump at the existing pumping station.
• It is therefore recommended to install these hydrants on the transmission main at the
required locations.
• It is also recommended to provide standby power for the existing booster pump station.
' o This will further reduce the estimated emergency storage deficit and provide a
more reliable source of supply for the system.
• The need for providing a larger capacity fire pump for the existing booster pump station
should be re-evaluated based on system needs with respect to growth.
According to City records, the connecting main for the Audubon Tank is undersized for
servicing a tank, and reduces the ability of the tank to provide equalization and fire protection.
To allow efficient use of this storage tank, it is recommended:
• To replace this entire main from the tank to Audubon Road with anew 12-inch main to
LJ'
provide sufficient capacity.
As with the Main Service System, there are a number of older, smaller, unlined water mains
within the High Pressure System. These unlined mains can lead to a reduction in water quality
-j and produce flow restrictions in the system.
• It is recommended that the City should include these mains as part of the recommended
continuing program to replace and/or clean and line older and undersized mains.
J"b
U`
r
Dewberry
43
Northampton, MA
SECTION VI a PHASED CAPITAL IMPROVEMENTS
GENERAL
7/15/2005
In the previous section, various improvements to the City's distribution system have been
recommended to address deficiencies with respect to providing adequate fire protection and
improving the transmission of flow through the system as determined from the hydraulic
analysis. In order to assist the City of Northampton in implementing these improvements with
consideration to available funding, the recommended improvements to the distribution system
have been prioritized and are presented in this section as a phased capital improvement program.
Estimated costs presented in the following tables are total project costs and include:
Construction;
Engineering; and
Contingencies.
Construction costs were developed in part using recent construction cost data for new water
mains, water main cleaning and lining, pumping stations, water storage tanks and appurtenances.
Other sources include the latest Means `Building Construction Cost Data" publication and
manufacturers' quotes. These costs have been updated to reflect the March 2005 Boston ENR
construction cost index.
The estimated costs do not include:
• Land acquisition;
• Right-of-way procurement;
• Permitting; and
• Legal fees.
CAPITAL IMPROVEMENTS
The recommended improvements for the City's water distribution system have been tabulated
into the following three categories based on the City's immediate deficiencies, estimated needs,
and benefit to the system.
• Initial System Improvements
• Phased Pipeline Improvements
• Main Service System Restructuring Improvements
The initial system improvements presented in Table 6-1 address immediate deficiencies with
respect to system operations and fire protection, and should be considered the highest priority for
implementation.
• The total costfor these improvements is $1,650,000.
9 Dewberry 1 44
i
Northampton, MA 7/15/2005
j j The phased-pipeline-improvements-were developed to address current-and projecteddeficiencies -
} with respect to fire protection, hydraulic capacity, and transmission of flow as determined from
the computer modeling conducted.
I
1 !i I
TABLE 6-1
INITIAL SYSTEM IMPROVEMENTS COST
Description
(Inches) (Feet)
Turke Hill Tank Im rovements
Upgrade Turkey Hill Tank Foundation
$375,000
Raise and paint entire Turkey Hill Tank
$750,000
Install internal tank mixing system
$90,000
Subtotal
$1,215,000
Leeds Village High Pressure S stem Im rovements
Installation of new emergency generator to existing booster station
$60,000
New fire, service connection for Leeds Elementary
School (off 16-inch main in Main Service)
12
2,000
$300,000
Replace 8" Audubon Tank connection with 12" main
12
500
$75,000
Subtotal
$435,000
Total - Initial System Improvements
$1,650,000
(1) Costs do not include land acquisition and legal fees.
A summary of the phased pipeline improvements is presented in Table 6-2.
sJ
Dewberry
45
Northampton, MA
7/15/2005
Phase I pipeline improvements eliminate the most serious fire flow deficiencies in the existing
distribution system and should be implemented over the next 5 years in conjunction with the
initial system improvements described above.
• The total costfor these improvements is $7,169,000.
TABLE 6-2
PIPELINE IMPROVEMENTS COST
Location From To Size L e n tgth Cost(l)
(Inches) (Feet)
Phase I 2005 - 2010
New Water Main / Re lacement
Westhampton Rd.
Glendale Rd.
Florence Rd.
12
14,000
$2,450,000(3)
Rocky Hill Rd.
Florence Rd.
Old Wilson Rd.
12
3,000
$525,000
Coles Meadow Rd.
North King St.
Marian St.
12
400
$70,000
Glendale Rd.
Westhampton Rd.
the south
8
1,800
$270,000
West Farms Rd.
Westhampton Rd.
Ryan Rd.
12
3,900
$683,000
Water Main Cleaning and Lining (2)
North King St.
Hatfield St.
Laurel Pk.
10
5,000
$600,000
Hatfield St.
North King St.
Cooke Ave.
10
1,600
$192,000
Cooke Ave.
Hatfield St.
Bridge Rd.
10
1,200
$144,000
Bridge Rd.
North Main St.
Industrial Dr.
12
13,250
$1,590,000
Pleasant St.
Holyoke St.
Wright St.
12
1,100
$132,000
Wright St.
Pleasant St.
Conz St.
12
500
$60,000
Conz St.
Wright St.
Pleasant St.
12
775
$93,000
Pleasant St.
Conz St.
Atwood Dr.
12
3,000
$360,000
tl
TO Dewberry i 46
i
J 7/15/2005
Northampton, MA
Phase II-pipeline improvements address moderate deficiencies in the existing distribution -
` system and should be implemented within the next 5 to 10 years.
• The total cost for these improvements is $3,204,000.
Size Length (1)
Location From To (Inche (Feet) Cost
Phase II 2010 - 2015)
New Water Main / Replacement
South Street
South Park
Terrace
Charles St.
8
1,000
$150,000
Earle Street
West St.
West Street to the
south.
12
800
$140,000
Water Main Cleaning and Lining (2)
King St.
Damon Rd.
Barrett St.
12
1,750
$210,000
King St.
Barrett St.
Main St.
10
5,500
$660,000
Grove St.
Chapel St.
Earle St.
10
2,500
$300,000
Grove St.
Earle St.
South St.
12
1,000
$120,000
Main St.
Pleasant St.
West St.
16
1,700
$230,000
West St.
Main St.
Green St.
16
500
$68,000
Federal St.
Nonotuck St.
Washington Ave.
16
4,600
$621,000
Washington Ave.
Federal St.
Dryads Gm.
16
400
$54,000
Dryads Gm.
Washington
Ave.
Paradise Rd.
16
1,300
$176,000
Paradise Rd.
Dryads Gm.
Elm St.
16
1,000
$135,000
Elm St.
Paradise Rd.
College Ln.
16
520
$70,000
Elm St.
Subtotal
Green St.
- Phase 11
16
2,000
$270,000
S3,204,000
Northampton, MA
7/15/2005
Phase III pipeline improvements address less critical deficiencies, eliminate noted restrictions or
"bottlenecks" within the system and provide additional system reinforcement. These
improvements can be implemented either after, in conjunction with the completion of the two
previous phases, or as part of the continuous pipeline improvements program recommended to
address the large quantity of older unlined 8-inch and 6-inch mains.
• The total cost for these improvements is $809,000.
Size Lena
Phase III 2015 - 202
New Water Main / Replacement
Ryan Rd.
Florence Rd.
Clark St.
12
1,600
$280,000
Burts Pit Rd.
Redford Dr.
Rural Ln.
12
400
$70,000
Damon Rd.
Old Water St.
Bridge St.
12
1,000
$175,000
North St.
Bates St.
Orchard St.
8
1,250
$188,000
Water Main Cleaning and Lining (2)
Earle St. Grove St. the North 12 800 $96,000
Subtotal - Phase 111 111
Total - Phase I, II, & III Pipeline Improvements $11,182,000
(1) Costs do not include land acquisition and legal fees.
(2) Prior to cleaning and lining, C-value tests should be conducted or coupons taken to confirm
condition of pipe.
(3) Some of the cost for this main may be carried as part of the road reconstruction project being
completed b the MHD.
1 Dewberry 1 48
1 Northampton, MA 7/15/2005
j The restructuring of the Main Service system to create a Low Pressure Zone is recommended to -
address the extreme system pressures within the low lying areas of the City and reduce
operations and maintenance costs associated with water main breaks and leakage.
As an added benefit, this new Low Pressure Zone will allow the City to increase the current
operating gradient of the Main Service system including the Turkey Hill Tank which will
improve system pressures to the higher elevated areas and provide additional storage volume.
This restructuring and subsequent adjustment will provide a more balanced distribution system
r by minimizing the high and lows.
0 The total cost for these improvements is $1,230,000.
A summary of the restructuring improvements is presented in Table 6-3. It should be noted that
the recommended restructuring is not a pre-requisite for the previous improvements, and does
not have any impact on their effectiveness. The City can implement the system restructuring
improvements as funds become available.
L~ TABLE 6-3
MAIN SERVICE SYSTEM RESTRUCTURING IMPROVEMENTS COST
Size Length (1)
Location From To (Inches) (Feet) Cost
Creation of New Low Service Area
Liberty St.
Lexington Ave.
Warner St.
8
800
$120,000
Warner St
Federal St.
Maplewood
g
2,300
$345,000
.
Terr.
Maplewood
Hinckley St.
Warner St.
8
1,400
$210,000
Terr.
Hinckley St.
Maplewood
Nonotuck St.
8
700
$105,000
Terr.
Prospect St. PRV (No. 6)
12
N/A
$120,000
Bridge Rd. PRV (No. 7)
10
N/A
$110,000
Rt. 66 PRV (No. 8)
10
N/A
$110,000
Nonotuck St. PRV (No. 9)
10
N/A
$110,000
Total - Main Service Restructuring Improvements
$1,230,000
(1) Costs do not include land acquisition and legal fees.
J
X11 Dewberry 49